Field test form

7UT613 Transformer Protection Relay

CUSTOMER: SHARQ PROJECT: TAM-2018


EQUIPMENT TAG NO.: AUX-1A PT-A DESCRIPTION: Transformer Relay
Drawing No.: C26102S3 PLANT NO. / LOCATION: SS#3/3SG-1A/AUX-1A
TEST COMPLETION DATE: 18-11-2018

RELAY DETAILS

RELAY FUNCTION TRANSFORMER PROTECTION AUX SUPPLY VOLTAGE 125 V

RELAY MAKE Siemens NOMINAL CURRENT 5A


ACTIVATED
TYPE / STYLE 7UT6135-5EB92-2AAO 87T, 50, 51, 50G
FUNCTIONS
S. NO. BF1203052236
Note:

1- Relay test were done as found activated protection functions.

SECTION 1: GENERAL INSPECTION:

DESCRIPTION STATUS NOTE


Preliminary general examination, prior to energizing OK
Energizing OK
Parameter and protection settings OK
Logic input connection OK
Logic output connection OK
Verify type/connections as per drawings. OK
Temperature sensor input connection to the relay ( if applicable ) NA
Actual trip test conducted (By perform trip test to the C.B coil). OK
Relay Setting Was Updated as per Sheet Provided by Sharq. OK

EEIC SHARQ AED


Name Ganesh Krishnamoorthy Ahmed Swelam
Signature
Date 18-11-2018
# Uncontrolled Form, Customer Requirement.
1
Field test form
7UT613 Transformer Protection Relay

CUSTOMER: SHARQ PROJECT: TAM-2018


EQUIPMENT TAG NO.: AUX-1A PT-A DESCRIPTION: Transformer Relay
Drawing No.: C26102S3 PLANT NO. / LOCATION: SS#3/3SG-1A/AUX-1A
TEST COMPLETION DATE: 18-11-2018

SECTION 2: PRIMARY SETTINGS RECORD:

General Description Relay Setting

Transformer rating MVA: 12 MVA

Transformer Type DYN1

Transformer primary voltage 34.5kV

Transformer secondary voltage 4.16kV

Network frequency HZ 60 Hz

HV side Phase CT ratio 400/5A

Characteristics HV Residual current CT Ratio (if applicable) NA

LV side Phase CT ratio 4000/5A

LV Residual current CT Ratio (if applicable) 100/5 A

Number of VTs Input NA

LV Side (W2) VT Ratio (if applicable) NA

I Diff Min Set 0.2

Slope-1 Set 25%

Slope-2 Set 50%

I Diff high Set 35

EEIC SHARQ AED


Name Ganesh Krishnamoorthy Ahmed Swelam
Signature
Date 18-11-2018
# Uncontrolled Form, Customer Requirement.
2
Field test form
7UT613 Transformer Protection Relay

CUSTOMER: SHARQ PROJECT: TAM-2018


EQUIPMENT TAG NO.: AUX-1A PT-A DESCRIPTION: Transformer Relay
Drawing No.: C26102S3 PLANT NO. / LOCATION: SS#3/3SG-1A/AUX-1A
TEST COMPLETION DATE: 18-11-2018

SECTION 3: INPUT ACCURACY TEST:

Checking the relay Accuracy for the metering function

For w1/SCR1 CT Ratio: 400/5 A

Current Expected Measured Measured Measured Tolerance


injected current reading current Phase A current Phase B current Phase C ±5%
(A) (A) (A) (A) (A)
1.25 100 100 100 100 OK
2.5 200 200 200 200 OK
3.75 300 300 300 300 OK
5 400 400 400 400 OK

Checking the relay Accuracy for the metering function

For w2/SCR2 CT Ratio: 4000/5 A

Current Expected Measured Measured Measured Tolerance


injected current reading current Phase A current Phase B current Phase C ±5%
(A) (kA) (kA) (kA) (kA)
1.25 1.00 1.00 1.00 1.00 OK
2.5 2.0 1.20 1.99 2.00 OK
3.75 3.0 3.00 3.00 2.99 OK
5 4.0 4.00 4.00 4.00 OK

For w2/SCR2 CT Ratio: 100/5A

Ground Expected Measured Tolerance


Current injected Ground current ground current ±5%
(A) (kA) (kA)
2.5 50 0.05 OK
5 100 0.1 OK

EEIC SHARQ AED


Name Ganesh Krishnamoorthy Ahmed Swelam
Signature
Date 18-11-2018
# Uncontrolled Form, Customer Requirement.
3
Field test form
7UT613 Transformer Protection Relay

CUSTOMER: SHARQ PROJECT: TAM-2018


EQUIPMENT TAG NO.: AUX-1A PT-A DESCRIPTION: Transformer Relay
Drawing No.: C26102S3 PLANT NO. / LOCATION: SS#3/3SG-1A/AUX-1A
TEST COMPLETION DATE: 18-11-2018

SECTION 4: PROTECTION TESTS

1- Stability Test

W1/ SCR1 W2/ SCR2

Phase Injected Current (A) Injected Current (A) Status

R 2.5103 ∟0 2.062 ∟150

Y 2.5103 ∟240 2.062 ∟30 No Trip

B 2.5103 ∟120 2.062 ∟270

2- 87T Pickup & Timing Test:


(I Diff Trip = I diff set * I trans Rated / I CTR)
W1/ SCR1 Calculated 87T Pickup = 0.426 A
W2/ SCR2 Calculated 3phase 87T Pickup = 0.351 A, 1 phase pickup = 0.599 A

W1/ SCR1 W2/ SCR2

Fault I I I T I I I T
Pickup Drop Trip Measured Pickup Drop Trip Measured
(A) (A) (A) (Secs) (A) (A) (A) (Secs)

R-E 0.420 0.348 0.505 0.028 0.598 0.501 0.714 0.026

Y-E 0.420 0.350 0.508 0.024 0.599 0.502 0.714 0.029

B-E 0.421 0.353 0.507 0.021 0.599 0.499 0.714 0.027

R-Y-B 0.422 0.339 0.503 0.029 0.352 0.285 0.424 0.024

EEIC SHARQ AED


Name Ganesh Krishnamoorthy Ahmed Swelam
Signature
Date 18-11-2018
# Uncontrolled Form, Customer Requirement.
4
Field test form
7UT613 Transformer Protection Relay

CUSTOMER: SHARQ PROJECT: TAM-2018


EQUIPMENT TAG NO.: AUX-1A PT-A DESCRIPTION: Transformer Relay
Drawing No.: C26102S3 PLANT NO. / LOCATION: SS#3/3SG-1A/AUX-1A
TEST COMPLETION DATE: 18-11-2018

3- Harmonic’s Restrain: 2ND Har Ratio= 15%

I1 ( F =60 Hz ) I2 ( F = 120 Hz )
Phase I2 / I1 ratio %
(Pickup Value) Expected Blocking Measured

R 15 0.502 0.0754 0.073

Y 15 0.502 0.0754 0.075

B 15 0.502 0.0754 0.074

4- Harmonic’s Restrain: 5th Har Ratio= 30%

I5 ( F = 300 Hz )
Phase I5 / I1 ratio % I1 ( F =60 Hz )
Expected Blocking Measured

R 30 0.502 0.151 0.150

Y 30 0.502 0.151 0.151

B 30 0.502 0.151 0.151

EEIC SHARQ AED


Name Ganesh Krishnamoorthy Ahmed Swelam
Signature
Date 18-11-2018
# Uncontrolled Form, Customer Requirement.
5
Field test form
7UT613 Transformer Protection Relay

CUSTOMER: SHARQ PROJECT: TAM-2018


EQUIPMENT TAG NO.: AUX-1A PT-A DESCRIPTION: Transformer Relay
Drawing No.: C26102S3 PLANT NO. / LOCATION: SS#3/3SG-1A/AUX-1A
TEST COMPLETION DATE: 18-11-2018

5- Slope Test:

Idiff / IN

Sec 2
Sec 1

Id Min

IREST / IN

END SECTION 1

END SECTION 2

i) Section 1:

Where bias current is between 0 ≤ Ibias≤ section 1, Idmin = 0.2, set End section 1 = 0.8

Injected at Injected at ID
Fault IR Measured Relay Action Status
W1/SCR1 W2/SCR2 Measured

0.502 0.413 0 0.4 No Trip OK


R-E
0.502 0 0.2 0.2 Trip OK

0.502 0.413 0 0.4 No Trip OK


Y-E
0.502 0 0.2 0.2 Trip OK

B-E 0.502 0.413 0 0.4 No Trip OK

0.502 0 0.2 0.2 Trip OK

EEIC SHARQ AED


Name Ganesh Krishnamoorthy Ahmed Swelam
Signature
Date 18-11-2018
# Uncontrolled Form, Customer Requirement.
6
Field test form
7UT613 Transformer Protection Relay

CUSTOMER: SHARQ PROJECT: TAM-2018


EQUIPMENT TAG NO.: AUX-1A PT-A DESCRIPTION: Transformer Relay
Drawing No.: C26102S3 PLANT NO. / LOCATION: SS#3/3SG-1A/AUX-1A
TEST COMPLETION DATE: 18-11-2018

ii) Section 2:
When bias current is between End sections 1 ≤ I bias ≤ End section 2
End section 2 = 5

Injected at Injected at ID
Fault IR Measured Relay Action Status
W1/SCR1 W2/SCR2 Measured

2.510 2.062 0 2.01 No Trip OK


R-E
2.510 1.231 0.4 1.61 Trip OK

2.510 2.062 0 2.01 No Trip OK


Y-E
2.510 1.232 0.4 1.61 Trip OK

2.510 2.062 0 2.01 No Trip OK


B-E
2.510 1.231 0.4 1.61 Trip OK

iii) Section 3:
When bias current is more than Ibias ≥ End section 2

Injected at Injected at ID
Fault IR Measured Relay Action Status
W1/SCR1 W2/SCR2 Measured

5.02 4.124 0.0 4.02 No Trip OK


R-E
5.02 7.204 1.5 5.42 Trip OK

5.02 4.124 0.0 4.01 No Trip OK


Y-E
5.02 7.204 1.5 5.43 Trip OK

B-E 5.02 4.124 0.0 4.02 No Trip OK

EEIC SHARQ AED


Name Ganesh Krishnamoorthy Ahmed Swelam
Signature
Date 18-11-2018
# Uncontrolled Form, Customer Requirement.
7
Field test form
7UT613 Transformer Protection Relay

CUSTOMER: SHARQ PROJECT: TAM-2018


EQUIPMENT TAG NO.: AUX-1A PT-A DESCRIPTION: Transformer Relay
Drawing No.: C26102S3 PLANT NO. / LOCATION: SS#3/3SG-1A/AUX-1A
TEST COMPLETION DATE: 18-11-2018

5.02 7.204 1.5 5.43 Trip OK

6- Over Current & Earth Fault

Setting and Testing Points


I I I T T
Function
Phase Curve Set Pickup injected Td (expected) (measured) Acceptance
(A) (A) (A) Sec Sec

A 9.97 10 0.128 OK
50 B DMT 10 9.98 10 0.1 0.12 0.124 OK
Over C 9.98 10 0.122 OK
current A 3.428 6 10.6 OK
ANSI-
51 B 3.13 3.427 6 3.3 10.7 10.6 OK
INVERSE
C 3.427 6 10.5 OK
Earth
fault 50G N DMT 1.25 1.24 2 0.7 0.7 0.71 OK

Relay Healthy status Please Tick √

After performing the test, the Relay was Yes No Comment


found in Healthy condition
√ PASSED

SECTION 5: TEST EQUIPMENTS LISTING AND CALIBRATION DATA

DEVICE MAKE CALIBRATION DATE CALIBRATION EXP.

EEIC SHARQ AED


Name Ganesh Krishnamoorthy Ahmed Swelam
Signature
Date 18-11-2018
# Uncontrolled Form, Customer Requirement.
8
Field test form
7UT613 Transformer Protection Relay

CUSTOMER: SHARQ PROJECT: TAM-2018


EQUIPMENT TAG NO.: AUX-1A PT-A DESCRIPTION: Transformer Relay
Drawing No.: C26102S3 PLANT NO. / LOCATION: SS#3/3SG-1A/AUX-1A
TEST COMPLETION DATE: 18-11-2018

Relay Test Unit ISA DRTS66 17-10-2018 16-10-2019

EEIC SHARQ AED


Name Ganesh Krishnamoorthy Ahmed Swelam
Signature
Date 18-11-2018
# Uncontrolled Form, Customer Requirement.
9