Professional Documents
Culture Documents
Chapter 6 - PQ - Voltage Sag
Chapter 6 - PQ - Voltage Sag
NZA2009
Introduction
•Definition of voltage sag:
“A sag is decreased between 0.1 to 0.9 p.u in rms
voltage at the power frequency for duration from
0.5 cycle to 1 minute”
Figure 1
NZA2009
•VS measured near or away from fault
location give different value of sag
33 kV
PCC
F1
Figure 2
NZA2009
Causes of voltage sag
• There are few causes of voltage sag:
1. Faults on the branches of the supply network
& in the internal supply scheme of consumer’s
installation
Fault / SC : 3 phase balanced fault, unbalanced
fault (single line to ground, line to line, double line
to ground)
During fault, current is very high voltage is
drop
NZA2009
Figure 3: Voltage sag waveform due to fault
2. Energizing of transformer
NZA2009
Effects of voltage sag
• Impact of voltage sag to industrial
equipment:
– Electronic equipment & PLC
DC voltage applied ↓
Device/equipment shutdown, lock up or garble
data
PLC – damage (high current)
– Lighting
Lighting system will burn brighter or dimmer
Life span may be affected
NZA2009
– Motor
More tolerant to voltage sag
Severe enough motor lose rotational inertia &
draw high inrush current (CB trip)
NZA2009
Case Study
• Consider a simple power system schematic
diagram as shown in Fig. 6 & fault occur at
point X
E1
Z1 MA X MB Z2
Fault
Figure 6
NZA2009
• Fig. 7 & Fig. 8 show the waveforms
captured at both monitoring points
Voltage (kV) & current (kA) Voltage (kV) & current (kA)
Figure 7: a) Voltage & current sag Figure 8: b) Voltage & current sag
waveforms at MA waveforms at MB
NZA2009
MA MB
Pre-fault V & I: normal V & I: normal
i) IA ↑↑, VA ↓↓ i) IB ↑, VB ↓
ii) sag occur for ii) since IB <<IA; thus,
certain period voltage sag monitored
During fault at MB is lesser than
voltage sag at MA
iii) sag occur for certain
period
Post-fault V & I back to normal V & I back to normal
Table 1: Comparison of fault condition at monitoring point A (MA)
and monitoring point B (MB)
NZA2009
Mitigation technique
• Common approach: adjust setting for the
equipment to be at higher tolerance
• If it is not possible, then, voltage sag
mitigation equipment is installed
• Purpose of voltage sag mitigation
equipment: to support the missing voltage
during the sag condition
• This can be achieved using different kinds
of technologies such as battery, capacitor,
NZA2009
booster transformer, etc
• Among the mitigation equipment used
are:
1. Uninterrupted Power Supply (UPS)
Uses battery in its operation
Advantage: provide continuous & longer support
outage & voltage sag condition
Disadvantage: the batteries need to be stored in a
controlled environment & require regular
maintenance & replacement
NZA2009
2. Dynamic Voltage Restorer (DVR)
Consists of coupling transformer & gate turn-off
thyristor (GTO) DC voltage
Principle of operation:
NZA2009
Inverter is fully functioned when voltage sag
occur
Normal condition: inverter supply a small
injection voltage to Tx
NZA2009
3. Voltage Dip Proofing Inverters (DPI)
Consists of static switch, inverter & capacitor
DPI block diagram:
Static
switch
Inverter
Supply Load
Storage
capacitor
NZA2009
Sag occurred and OUTPUT
INPUT
inverter activated
INPUT OUTPUT
Figure 15
NZA2009
4. Voltage Dip Compensators (VDC)
Consists of compensator or booster Tx, static
switches & the controls
VDC: boosting the sag voltage through its
compensation Tx & ultra fast static voltage
It can fully compensate 50% of voltage sag for
about 3sec – because the Tx need a minimum
voltage of 50% to boost the missing voltage back
to normal
5. Dynamic Sag Corrector (DySC)
Consists of static switches, electronic controls,
converter, filter & capacitor
NZA2009
Figure 16: Block diagram for DySC