PROTECTION OF AC MACHINES
AGAINST INTERNAL FAULTS
INTERNAL & EXTERNAL FAULTS
TR 1
Ip Ip
TA TA
P ro te c te d
E q u ip m e n t
50 Ie 2 - Ie l
Ip - Ie l Ip - Ie 2
Differential Protection
T .A T .A
P ro te c te d
E q u ip m e n t
IL IR
IL IR
PRINCIPLE OF OPERATION OF DIFFERENTIAL RELAYS
G1
INTERNAL / EXTERNAL FAULTS
I1 I2 Id
NOTE :
1. THROUGH FAULT CONDITION HAS TO BE DETECTED BY
NORMAL O/C RELAY (SINCE FAULT CURRENT IS
HIGHER THAN 100%)
SATABILITY OF
DIFFERENTIAL RELAY
TYPES OF DIFFERENTIAL RELAYS
CIRCULATING CURRENT
(HIGH IMPEDANCE)
PERCENTAGE BIASED
(LOW IMPEDANCE)
CIRCULATING CURRENT
HIGH IMPEDANCE DIFFERENTIAL RELAY
I1 - I2 RELAY OPERATING
CURRENT
TRIP IN TERMS OF
SETTING CT PRIMARY
(20% OF In)
Is =20%
DISADVANTAGES :
ADD A
STABILISING RESISTOR
TO IMPROVE
PERFORMANCE
CIRCULATING CURRENT
HIGH IMPEDANCE DIFFERENTIAL RELAY
STABILISING RESISTOR
I1 - I2 RELAY OPERATING
CURRENT
INTERNAL FAULT
EXTERNAL FAULT
BIAS PERCENTAGE
PERCENTAGE BASED DIFFERENTIAL RELAY BIASE CHARECTERSTICS
( I1-I2)
%Id
I1+I2
MIN I1-I2 2 SUM CURRENT
SLOPE
DUAL SLOPE ?
DIFFERENTIAL RELAYS
INTERPOSING CTs
INTERPOSING CTs
R R
1. YY0
B B
Y Y
R B
Y
2. YY6
B
Y R
B
3. YD1 Y
4. YD11 B
Y
PHASE ANGLE COMPENSATION
THROUGH INTERPOSING CT’S
CONNECTION DIAGRAM MD32-T RELAY
WHY REF ?
RESTRAINTS IN DIFFERENTIAL RELAYS
1. PERCENTAGE BIASED
2. DUAL SLOPE
3. DISPLAYS OF Id
4. VECTOR/AMPLITUDE
COMPENSATION
(W/O ICTs)
5. 2ND HARMONIC RESTRAINT
6. 5TH HARMONIC RESTRAINT
7. WAVE FORM CAPTURE
8. INBUILT REF