Professional Documents
Culture Documents
Prepared by:
Er. Madhav P. Nagarkoti
(Visiting Faculty)
1
CONTENTS
Introduction
Necessity of substations
Substation layouts
Communication system
2
Switching stations
INTRODUCTION
The assembly of apparatus used to change some
characteristic (e.g. voltage, a.c. to d.c., frequency, etc.) of
electric supply is called a sub-station.
Sub-stations are important part of power system. The
continuity of supply depends to a considerable extent upon
the successful operation of sub-stations.
It is, therefore, essential to exercise utmost care while
designing and building a sub-station. The following are the
important points which must be kept in view while laying out
a sub-station :
a. It should be located at a proper site.
b. It should provide safe and reliable arrangement.
c. It should be easily operated and maintained.
3
d. It should involve minimum capital cost.
NECESSITY OF SUBSTATIONS
Practical Considerations
a. To satisfy load growth
b. To accommodate new generation
c. To maintain reliability requirements
Technical Considerations
a. To step up or step down AC voltage using transformer
b. To switch the power lines
c. To correct the power factor
d. To change the frequency
e. To convert ac power into dc power
4
SUBSTATION LAYOUTS
5
6
7
DISTRIBUTION SUBSTATION
The electric power from 11 kV lines is delivered to
distribution sub-stations.
These sub-stations are located near the consumers localities
and step down the voltage to 400 V, 3-phase, 4-wire for
supplying to the consumers.
The voltage between any two phases is 400V and between
any phase and neutral it is 230 V.
The single phase residential lighting load is connected
between any one phase and neutral whereas 3-phase, 400V
motor load is connected across 3-phase lines directly.
It may be worthwhile to mention here that majority of the
distribution sub- stations are of pole-mounted type.
8
MAJOR EQUIPMENT AT SUBSTATIONS
Instrument transformer
Current transformer
Potential transformer
Isolators
Bus-bars
Lighting arrestors
Circuit breakers
Capacitor Banks
Power transformers
9
SYMBOLS FOR EQUIPMENTS IN SUBSTATION
10
11
12
BUS- BAR ARRANGEMENT
Bus-bars are the important components in a sub-station. There
are several bus-bar arrangements that can be used in a sub-
station.
The choice of a particular arrangement depends upon various
factors such as system voltage, position of sub-station, degree
of reliability, cost etc.
The following are the important bus-bar arrangements used in
sub-stations :
a. Single bus-bar system
b. Single bus-bar system with sectionalisation
c. Duplicate bus-bar system
13
SINGLE BUS-BAR SYSTEM
14
As the name suggests, it consists of a single bus-bar and
all the incoming and outgoing lines are connected to it.
The chief advantages of this type of arrangement are low
initial cost, less maintenance and simple operation.
However, the principal disadvantage of single bus-bar
system is that if repair is to be done on the bus-bar or a
fault occurs on the bus, there is a complete interruption of
the supply.
This arrangement is not used for voltages exceeding 33kV.
16
In this arrangement, the single bus-bar is divided into sections
and load is equally distributed on all the sections. Any two
sections of the bus- bar are connected by a circuit breaker and
isolators.
Two principal advantages are claimed for this arrangement.
Firstly, if a fault occurs on any section of the bus, that section
can be isolated without affecting the supply from other sections.
Secondly, repairs and maintenance of any section of the bus- bar
can be carried out by de-energising that section only, eliminating
the possibility of complete shut down. This arrangement is used
for voltages upto 33 kV.
Above figure shows bus-bar with sectionalisation where the bus
has been divided into two sections. There are two 33 kV
incoming lines connected to sections I and II as shown through
circuit breaker and isolators. Each 11 kV outgoing line is
connected to one section through transformer (33/11 kV) and 17
circuit breaker. It is easy to see that each bus-section behaves as
a separate bus-bar.
DUPLICATE BUS-BAR SYSTEM
18
This system consists of two bus-bars, a “main” bus-bar and a
“spare” bus-bar. Each bus-bar has the capacity to take up the
entire substation load.
The incoming and outgoing lines can be connected to either bus-
bar with the help of a bus-bar coupler which consists of a circuit
breaker and isolators.
Ordinarily, the incoming and outgoing lines remain connected to
the main bus-bar. However, in case of repair of main bus-bar or
fault occuring on it, the continuity of supply to the circuit can be
maintained by transferring it to the spare bus-bar.
For voltages exceeding 33kV, duplicate bus-bar system is
frequently used.
Above figure shows the arrangement of duplicate bus-bar
system in a typical sub-station. The two 66kV incoming lines
can be connected to either bus-bar by a bus-bar coupler. The two
11 kV outgoing lines are connected to the bus-bars through 19
23
It is a very simple type of diverter and consists of two 1·5 cm
rods which are bent at right angles with a gap in between as
shown in figure above.
One rod is connected to the line circuit and the other rod is
connected to earth. The distance between gap and insulator
(i.e. distance P) must not be less than one-third of the gap
length so that the arc may not reach the insulator and damage
it.
Generally, the gap length is so adjusted that breakdown
should occur at 80% of spark- over voltage in order to avoid
cascading of very steep wave fronts across the insulators.
The string of insulators for an overhead line on the bushing of
transformer has frequently a rod gap across it. Above figure
shows the rod gap across the bushing of a transformer.
24
Under normal operating conditions, the gap remains non-
conducting. On the occurrence of a high voltage surge on
the line, the gap sparks over and the surge current is
conducted to earth. In this way, excess charge on the line
due to the surge is harmlessly conducted to earth.
Limitations
After the surge is over, the arc in the gap is maintained
by the normal supply voltage, leading to a short-circuit
on the system.
The rods may melt or get damaged due to excessive heat
produced by the arc.
The climatic conditions (e.g. rain, humidity, temperature
etc.) affect the performance of rod gap arrester.
The polarity of the surge also affects the performance of
25
this arrester.
2. HORN GAP ARRESTER
Above figure shows the horn gap arrester. It consists of two horn
shaped metal rods A and B separated by a small air gap. The
horns are so constructed that distance between them gradually
increases towards the top as shown.
The horns are mounted on porcelain insulators. One end of horn
Limitations
The bridging of gap by some external agency (e.g. birds) can
render the device useless.
The setting of horn gap is likely to change due to corrosion or
pitting. This adversely affects the performance of the arrester.
The time of operation is comparatively long, say about 3
seconds. In view of the very short operating time of modern
28
protective gear for feeders, this time is far long.
3. MULTI-GAP ARRESTER
31
This type of arrester is also called ‘protector tube’ and is
commonly used on system operating at voltages upto 33 kV.
They are improved form of rod gap arresters as they block the flow of
power frequency follow currents.
They can be easily installed.
Limitations
An expulsion type arrester can perform only limited number of operations
as during each operation some of the fibre material is used up.
This type of arrester cannot be mounted in an enclosed equipment due to
the discharge of gases during operation.
Due to the poor volt/amp characteristic of the arrester, it is not suitable for 33
the protection of expensive equipment.
5. VALVE TYPE LIGHTNING ARRESTER
34
Valve type arresters incorporate non-linear resistors and are
exten- sively used on systems operating at high voltages.
Fig. (i) shows the various parts of a valve type arrester. It
consists of two assemblies (i) series spark gaps and (ii) non-
linear resistor discs (made of material such as thyrite or
metrosil) in series.
The non-linear elements are connected in series with the
spark gaps. Both the assemblies are accommodated in tight
porcelain container.
Under normal conditions, the normal system voltage is
insufficient to cause the break- down of air gap assembly.
On the occurrence of an overvoltage, the breakdown of the
series spark gap takes place and the surge current is
conducted to earth via the non-linear resistors.
35
Since the magnitude of surge current is very large, the non-linear elements
will offer a very low resistance to the passage of surge.
The result is that the surge will rapidly go to earth instead of being sent
back over the line. When the surge is over, the non-linear resistors assume
high resistance to stop the flow of current.
Advantages
They provide very effective protection (especially for transformers and
cables) against surges.
They operate very rapidly taking less than a second.
Limitations
They may fail to check the surges of very steep wave front from reaching
the terminal apparatus. This calls for additional steps to check steep-
fronted waves.
Their performance is adversely affected by the entry of moisture into the
36
enclosure. This necessitates effective sealing of the enclosure at all times.
FAULT LIMITING REACTORS
A reactor is a coil of number of turns designed to have a large
inductance as compared to its Ohmic resistance.
The forces on the turns of these reactors under short-circuit conditions
are considerable and, therefore, the windings must be solidly braced.
It may be added that due to very small resistance of reactors, there is
very little change in the efficiency of the system.
Advantages
Reactors limit the flow of short-circuit current and thus protect the
Bus-bar reactors
Generator Reactor
When the reactors are
1. Ring system
In this system, bus-bar