Professional Documents
Culture Documents
Chapter 1
Introduction to Power Systems
(ECEG-3154)
Instructor:
Abiy. E (MSc)
Electrical & Computer Engineering Department
Wollega University
College of Engineering and Technology
ECEG-3154 Introduction to Power Systems
Generation Transmission
System System
15,20 kV 400,500 kV 400,500 kV 66,45 kV
Generator-1
Large
Consumers
Step-up Step-down
Transformer 132,230 kV Transformer
Distribution
System
Generator-2 400,500 kV
15,20 kV 132,230 kV
66,45 kV
Step-down
Transformer
Step-up
Transformer 33,15 kV
11,11.5 kV
400/220 V
33/15 kV
Medium
Generator-3 and small
Consumers
CONSISTANCE OF TYPICAL POWER SUPPLY SCHEME
Generating station
Primary transmission
Secondary transmission
Primary distribution
Secondary distribution
Non-renewable energy sources: fossil fuels (coal, oil, natural gas (CH4))
Definition: Nonrenewable energy is energy obtained from static stores of
energy that remain bound unless released by human interaction.
Nonrenewable energy supplies are also called finite supplies.
2. Transmission Systems:
This component of the power system transmits bulk electrical energy from
generation stations where it is produced to the main load centres. The
transmission system is composed of:
•Step-up and Step-don substations
•Transmission lines
3.Distribution Systems
The distribution system gives out the energy from the medium voltage
substations to customers’ location. It is composed of:
•Medium Voltage (MV) lines (33kV, 15 kV)
•MV/LV transformer substations (33/15/ kV to 400/380/220 V)
•Distribution lines (33/15 kV, 380 V 3-phase and 220 v single phase)
The capital cost of hydro-electric scheme depends upon the nature of the
scheme, but is usually high. Such schemes usually are located at some
distance from load centres, therefore have associated high transmission costs.
Once the plant is operational, the subsequent costs are very low and
therefore are attractive for base load operation.
ECEG-3154, Generation - Hydro-electric Plant
ECEG-3154, Generation - Hydro-electric Plant
The quick starting facility of hydro-electric plant and its ability to handle rapidly
changing loads make it ideally suited to peak-load operation. It might appear at the
first sight that the high capital cost and low operating cost of a hydro-electric
scheme are the reverse of what is required for peak-load plant, I.e. it also can be
used as Base load Operation
TRANSMISSON LINE
TRANSMISSON LINE
A.C. TRANSMISSION
A.C. TRANSMISSION D.C.TRANSMISION
D.C.TRANSMISION
A.C.THREEPHASE
A.C.THREE PHASE MIDPOINT
MID POINTEARTH
EARTH D.C.TWOWIRE
D.C.TWO WIRE MIDPOINT
MID POINTEARTH
EARTH
FOURWIRE
FOUR WIRESYSTEM
SYSTEM A.C.SINGAL
A.C. SINGALPHASE.
PHASE. SYSTEM.
SYSTEM. TYPESYSTEM.
TYPE SYSTEM.
A.C.SINGAL
A.C. SINGALPHASE
PHASE A.C.THREEPHASE
A.C.THREE PHASE
TWOWIRE
TWO WIRESYSTEM
SYSTEM THREEWIRE
THREE WIRE
Transmission of electric power has been along the years and will still
continue one of the most important elements of today’s electric
power systems. Power transmission from generating stations to
industrial sites and to substations is the fundamental objective of
the transmission systems.
ELEMENT
ELEMENT OF
OF TRANSMISSION
TRANSMISSION SYSTEM
SYSTEM
PROTECTIVE
PROTECTIVE DEVICE
DEVICE STEP
STEP UP
UP TRANSFORMER
TRANSFORMER
REGULATOR
REGULATOR STEP
STEP DOWN
DOWN TRNSFORMER.
TRNSFORMER.
CONDUCTOR
CONDUCTOR LINE
LINE SUPPORT.
SUPPORT.
LINE
LINE ISULATOR
ISULATOR
Comparison of D.C. and A.C. Transmission
The electric power can be transmitted either by means of d.c. or a.c. Each system
has its own merits and demerits.
relatively easy to change the voltage levels, power grids tend to have many voltage
different levels.
ii. AC networks tend to be large and have a meshed core.
(b) Explain several reasons why AC power was ultimately chosen over DC.
i. Primarily losses. AC allowed for the relatively inexpensive conversion of
voltages, and thus moving power with lower currents.
Ehvdc transmission
HVDC TRANSMISSION
Advantages
The power can be generated at high voltages.
The maintenance of a.c. sub-stations is easy and cheaper.
The a.c. voltage can be stepped up or stepped down by transformers with ease and
efficiency. This permits to transmit power at high voltages and distribute it at safe
potentials.
Disadvantages
An a.c. line requires more copper than a d.c. line.
The construction of a.c. transmission line is more complicated than a d.c.
transmission line.
Due to skin effect in the a.c. system, the effective resistance of the line is
increased.
An a.c. line has capacitance. Therefore, there is a continuous loss of power due
to charging current even when the line is open.
Advantages of High Transmission Voltage
Reduces volume of conductor material.
Increases transmission efficiency
Decreases percentage line drop
Limitations of high transmission voltage
The increased cost of insulating the conductors
The increased cost of transformers, switchgear and other
terminal apparatus.
Electric Power/ Transformer Sub station
Electric Power/ Transformer Sub station
SUBSTATIONS
Substations are locations where transmission lines are tied together.
They fulfill a number of functions.
• They allow power from different generating stations to be fed into the main
transmission corridors.
• They provide a location where transformers can be connected to feed power into
the sub transmission or distribution systems.
• They provide a location where transmission lines can be de-energized, either for
maintenance or because of an electrical malfunction involving the line.
According to Design.
(b) Foundation
(a) Pole mounted
mounted
Sub-station.
Sub-station.
Substation Equipment
There are a number of designs used for substations. however, there are elements
common to all:
• Bus − the electrical structure to which all lines and transformers are
connected. - open air and enclosed type.
• Protective relays
- monitor the voltages and currents − The relays actuate circuit breakers.
• Circuit breakers
• Capable of interrupting the flow of electricity to isolate either a line or a
transformer.
Extinguishing the arc that forms using a variety of technologies such as oil,
vacuum, air blast or sulfur hexafluoride (SF6).
These fault current levels can be 20 or 30 times larger than the current
flow under normal operating conditions, that is, thousands of amperes.
Circuit breakers also allow lines or transformers to be removed from service for
maintenance.
Circuit breakers normally interrupt all three phases simultaneously.
Substation Equipment
• Transformers
To connect facilities operating at two different voltage levels.
On load and Off load or both Tap changing at the higher voltage side
An autotransformer, which is used when facilities at nearly the same voltage are to
be connected
• Disconnect switches
Used to open a circuit when only “charging” current present is due.
To connect or disconnect circuit breakers or transformers which are not carrying load current.
• Lightning arrestors
To protect transformers and switchgear from the effects of high voltage due to lightning
stroke or a switching operation.
To flashover when the voltage at the transformer exceeds a pre-selected level which is
chosen by the station design engineers to coordinate with the basic insulation level of the
transformer (BIL).
• Metering equipment
To measure line and transformer loadings and bus voltages so operating
personnel can ensure that these facilities are within acceptable limits.
• SCADA (system control and data acquisition)
The improvements in measurement, telecommunications and computing technologies
Electric Power/ Transformer Sub station
Depending on the electrical characteristics of the transmission system, other equipment
that may be located at a substation are:
• Shunt reactors
To control high voltages that occur especially at night due to the capacitive effect of lightly loaded
transmission lines.
to reduce or control the high voltages that can occur when a sudden loss of a block of customer
load occurs.
The windings, insulation and the external tank are similar to those used for transformers.
• Series reactors
Installed in a transmission line to increase the impedance of the line, to decrease current levels
in the event of short circuits, or to reduce its loading under various operating conditions.
• Shunt capacitors
• To provide mVArs to the system to help support voltage levels.
• Series capacitors
To reduce the effective impedance and the electrical angle between the sending and the receiving parts
of the system of a long transmission line and enabling more power to flow over the line and increasing
stability limits..
• Phase angle regulating transformers
• To control power flow through a transmission line
• FACTS (Flexible ac Transmission Systems)
Increased power transfer capability, rapid voltage control, improved system stability, and
mitigation of sub-synchronous resonance
Power distribution:
The final stage in the delivery of electricity to the end user
The network of a distribution system carries electricity
from the transmission system and delivers it to the
consumers.
The distribution system begins as the primary circuit
leaves the sub‐station and ends as the secondary service
enters the consumer meter.
The Consumer may be Industrial, Commercial or Domestic.
It is usual for Industrial Consumers and some Commercial
phase)
Distribution system components
• Nature of Current:
AC distribution system:
Primary distribution system
Secondary distribution system
DC distribution system:
2- wire dc system,
3- wire dc system.
• Type of Construction: OHL,UG
• Scheme of Connection:
radial system, ring main system and inter connected system.
AC distribution
• AC distributor with concentrated load;
1. three-phase, Three-wire distribution system-
Primary Distribution
2. three-phase, four-wire distribution system-
Secondary Distribution
Ac distribution system
Primary Distribution
The agricultural sector includes energy demand for low and medium
scale agro-industries and farming.
The public service sectors may include schools, medical centres, street
lighting, public offices and entertainments.
Reactive Power always oscillates in one direction and then reverses an equal amount. Its
average value is always zero.
Reactive Power (Q): power that does not perform work (sometimes called “wattless power”)
measured in VA reactive (VAr)
· Complex Power (S): the vector sum of the true and reactive power measured in volt amps
(VA)
Phase angle . This is the angle used to describe the phase shift between the voltage and current.
The larger the phase angle, the greater the reactive power generated by the system.
This
is also called the real power (it’s the power that’s provided to the resistive part
of the load over time)
• We want to assess the power delivered by different types of time-varying
signals
– The power delivered to a resistive load:
• P=R
Find a DC (constant) value which delivers the same average power as the time-varying
signal Called the effective or RMS value of the signal Used to “compare” different time-
varying signals.
• Effective DC value:
• VRMS, IRMS notation (RMS = “effective”)
Definition of RMS values
• The effective (or RMS) value of a signal is equal to the DC value which provides
the same average power to a resistor
• For sinusoidal signal with no DC offset:
CURRENT POTENTIAL
TRANSFORMER TRANSFORMER
INSTRUMENT TRANSFORMER
CURRENT POTENTIAL
TRANSFORMER TRANSFORMER
A simplified diagram by omitting the completed circuit through the neutral and by
indicating the components of the power system by standard symbols rather than by
their equivalent. The purpose of the single line diagram is to supply in concise
form of the significant information about the system.
Almost all modern power systems are three-phase systems with the phases of equal
amplitude and shifted by 120˚. Since phases are similar, it is customary to sketch
power systems in a simple form with a single line representing all three phases of
the real system.
Example: a power system containing two synchronous machines, two loads, two busses,
two transformers, and a transmission line to connect busses together.
The per unit value of any quantity is defined as the ratio of the actual value of the
any quantity to the base value of the same quantity as a decimal.
Per unit value= (Actual value)/ (Base value)
Need for per unit value
1. The per unit impedance referred to either side of a single phase transformer is
the same.
2. The chance of confusion b/n line and phase quantities in a three phase balanced
system is greatly reduced.
3. The manufacturers usually produce the impedance values in per unit.
An advantage of per-unit representation is that circuits containing transformers
can be easily analyzed.
Real power systems are convenient to analyze using their per-phase (since the system is three-
phase) per-unit (since there are many transformers) equivalent circuits. The per-phase base
voltage, current, apparent power, and impedance are