Professional Documents
Culture Documents
Generation
Overview 2
Distributed Generation
• What is Distributed Generation (DG)?
• Types and Operating Characteristics of DG
DG Impacts
• Islanding
• Power Quality
• Fault Current
• Peak Load Shaving
• Subtransmission
Mitigation Methods
Inductive Generation
• Identical design to the AC induction motor
• Multi-phase armature windings within solid core stator
• Electromagnetically driven squirrel-cage rotor
• Reactive power is consumed during motor mode operation
• Active power is produced during generator mode operation
• Operates at rotor rotational speeds greater than synchronous
speed (rpm)
• Generally found in variable-speed applications
T y p e s o f Di s t r i b u t e d Ge n e r a t i o n 7
Synchronous Generation
• Similar in design to inductive generator
• Solid core stator designed with armature windings within laminated
slots
• Rotor creates rotating magnetic flux via three methods
Permanent Magnets
DC-powered electromagnets via slip rings/commutator system
Brushless exciter alternator
• Induced current imposed upon armature windings
• More costly than inductive generators due to:
Increased cost of permanent magnets
Higher complexity in comparison to inductive motors
Maintenance required for commutator and slip ring adjustments,
replacements, etc.
Op e r a t i n g Ch a r a c t e r i s t i c s 8
Inductive Generation
• Field excitation requires leading VARS supplied by capacitors
• Difference between actual rotor driving speed and utility-dictated
synchronous speed is known as slip
• Generator rotational speeds above synchronous speed, or
negative slip, achieves power production
• Prime mover required to achieve negative slip
• Voltage and frequency regulated by utility
• Generation decays to zero steady-state post fault isolation
Op e r a t i n g Ch a r a c t e r i s t i c s 10
Synchronous Generation
• Driving speed (rpm) determined by number of poles and desired
frequency
• Variable rotor torque dictates real power generation
• Variable excitation level dictates reactive power generation
• Power factor can be controlled via torque and excitation level
• Generation generally persists longer than induction generation due to
rotor inertia and residual magnetic field
B e n e f i t s o f Di s t r i b u t e d Ge n e r a t i o n 11
Customer Benefits
• Reduced apparent power consumption visible to utility, resulting in
reduced electric bill
• If net metering is employed, excess energy may be exported back to
utility in exchange for billing credits
Utility Benefits
• Reduced apparent power consumption may reduce overall losses
• Depending upon characteristics of DG and high voltage feeder,
service transformer, and DG system, voltage support possible in some
cases
• Dispatchable DG provides alternate sources of power generation to
provide system redundancy and hardening
Increased renewable energy DG systems (PV, Wind, Geothermal, etc.)
supports AEPS Act 213 initiatives
I m p a c t s o f Di s t r i b u t e d Ge n e r a t i o n 12
Secondary Overvoltage
• Voltage rise on secondary service cables
ANSI Service Voltage Range A, or ANSI Range A, dictates service voltage to remain
within +/- 5% of nominal4
Most inverter-connected systems operate in voltage-following mode
Injected power causes voltage rise in correlation to impedance of conductor
between inverter and point of common coupling (PCC)
I m p a c t s o f Di s t r i b u t e d Ge n e r a t i o n 13
Voltage Fluctuation
• Voltage may become highly variable within short periods of time
Voltage “rise” induced by inverter-based DG varies with variable DC input (i.e. PV,
Wind)
Voltage swing between DG inverter “maximum output” and “minimum output”
induced voltages measured at customer can produce significant voltage dips
Resultant voltage dips, or “flicker”, must be evaluated against IEEE 519-1992
flicker curve
Large voltage swings may also cause sporadic capacitor bank switching and/or
regulator voltage “hunting”
Generally severity increases with DG penetration and/or concentration level, as well as
system strength
I m p a c t s o f Di s t r i b u t e d Ge n e r a t i o n 14
Primary Overvoltage
• DG service transformer is delta primary, grounded-wye secondary
• Occurs when substation breaker isolates multi-grounded-wye
source from faulted facilities and DG continues to operate
• During line-to-ground faults, “neutral shifting” occurs affecting
single-phase loads on non-faulted phases
I m p a c t s o f Di s t r i b u t e d Ge n e r a t i o n 16
Unintentional Islanding
• Condition established when a section of the grid is isolated from the
substation supply while the load continues to be maintained by DG
within the isolated section that continues to provide power.6
• Results in potentially non-phasing automatic reclosing between
utility and island
I m p a c t s o f Di s t r i b u t e d Ge n e r a t i o n 17
Unintentional Islanding
• Island remains energized at a different frequency, voltage, and/or
power factor
• DG generally has insufficient regulatory controls to maintain
frequency and voltage within ANSI Range A limits
• Possible damaged conductors contacting ground could remain
energized
Poses risk to public of additional source of electrical injury
Poses additional risk to line crews performing restorative work
I m p a c t s o f Di s t r i b u t e d Ge n e r a t i o n 20
F1
F3 F2
Fu t u r e Di s t r i b u t i o n Sy s t e m De s i g n 27