Professional Documents
Culture Documents
Response – Steam
Generation Webinar
November 13, 2018
2 RELIABILITY | ACCOUNTABILITY
3
EI
Summary:
3 RELIABILITY | ACCOUNTABILITY
Frequency
EI Frequency
11/12/18
8-9 P M
60.04
60.03
60.02
60.01
60
59.99
59.98
59.97
59.96
59.95
8:07:1
8:14:2
8:28:4
8:00:0
8:21:3
8:36:0
8:43:1
8:50:2
8:57:3
0 PM
2 PM
4 PM
6 PM
0 PM
2 PM
4 PM
6 PM
8 PM
4 RELIABILITY | ACCOUNTABILITY
Western Interconnection
Interconnection: Western
WI_2017-08-08_100816
Event ID:
Event Date & Local Time: 8/8/2017 10:08:16
Report Percent Processed: 0
Report Date: 0
Total Units
Survey Participant Online
Information Submittal Submittal
Submittals Rate Rate
Unit Information Completed
EIA 860 Plant Name: 211 100% 21.1%
EIA 860 Plant Code: 205 97% 20.5%
EIA 860 Unit ID: 211 100% 21.1%
GADS ID: 184 87% 18.4%
Planning Case Bus Number: 172 82% 17.2%
Balancing Authority: 0 0% 0.0%
Generator Type: 213 101% 21.3%
Generator Base MVA: 209 99% 20.9%
Inertia Constant (H): 202 96% 20.2%
Droop Setting (%): 201 95% 20.1%
Deadband Setting (Hz): 198 94% 19.8%
Maximum Operating Level (MW): 201 95% 20.1%
Minimum Operating Level (MW): 200 95% 20.0%
5 RELIABILITY | ACCOUNTABILITY
Primary frequency response - GE
Notable issues
Communications • Few recent questions
• Gas Turbine PSIB 20150203
• Focuses on PFR at plant level
• PFR should be implemented at highest
plant level closed loop load control
• Steam turbine TIL-1961-R1
and coordinated as needed inside the
• Deadband checks /
outer loop
recommendations
• Disabling load control or AGC outside
dead band sometimes done to “free “
governor ….but this disables correction
of frequency / ACE by AGC
1) October 30, 2012, NERC published Frequency Response Initiative Report: The Reliability Role of
Frequency Response.
Frequency Response Withdraw is discussed multiple times on multiple pages.
2) Feb 5, 2015, NERC issues an industry advisory specifying the method to improve grid stability
by;
Frequency Response Withdraw is discussed in one sentence “Related outer-loop
controls within the DCS, as well as other applicable generating unit or plant controls,
should be set to avoid early withdrawal of primary frequency response.”
3) Dec 15 2015, NERC Operating Committee approved the “Reliability Guideline: Primary
Frequency Control”
Frequency Response Withdraw is only mention in the performance assessment.
Guidelines do not identify withdraw problem or requirements a solution to resolve
frequency response withdraw.
1) The survey assesses both the secondary frequency control and primary frequency control
response.
Consider adding Unit Master Setpoint (demand) to data collection. Unit Master setpoint
should be subtracted from the megawatt response in order to evaluate the primary
frequency control. OK to also assess the response of secondary frequency control
2) NERC needs to verify the calculation can correctly compute the front end withdraw behavior.
In my opinion, the current calculation do not.
1) The Reliability Guidelines for Primary Frequency Control and MOD 27 are related but
separate NERC requirements.
2) NERC intends that the Generator Owners/Operators implement both of these documents.
3) The data collected from the MOD 27 test can be used to calibrate the boiler frequency
correction
bias required by the Reliability Guidelines for PFC.
Thor Honda
Steam Turbine Business Development Manager
(412) 963-4272
thor.honda@emerson.com
Emerson Power & Water Solutions
Unit Coordinated Control (UCC)
digital)
UCC Periodic Revisions by Subject Matter Expert (SME) Teams
Emerson Proprietary
2018 Emerson SME Teams’ Decisions Regarding UCC Frequency
Control
the operator
2018 Emerson SME Teams’ Decisions Regarding UCC Frequency
Control
Emerson Proprietary
2018 Emerson SME Teams’ Decisions Regarding UCC Frequency
Control
Emerson Proprietary
FPL Frequency Response
Improvements
FPL I&C Fleet Team
Background
• Poor frequency response is the result of using
megawatt generation control without frequency
error bias.
• The following cases illustrate improvements FPL
made to plant load control logic to improve
frequency response.
Cases
Case Plant control Turbine Change
control
1 Feed forward with Load control Added freq bias to
feedback trim and no w/no freq plant control feed
freq err bias err bias forward and
feedback controller
setpoint
Operations
Biography
30
Agenda
31
Outer Loop Control Philosophy
• Outer Loop Controls should not affect the Turbine Controls Frequency Megawatt
Response
• Outer Loop Controls if Not Accounted for will NULL out the Frequency Megawatt
Response during a Frequency Event
– Outer Loop Megawatt Controller “Sees’ the Unit Megawatts are off Setpoint
Target
and Moves the Megawatt Setpoint to Correct the Error
32
External Outer Loop Controls – Fossil Steam
33
External Outer Loop Controls – Fossil Steam
34
External Outer Loop Controls – Fossil Steam
• Fossil Steam Turbine Controls Set the MW Output of the Turbine Generator by
Changing the Flow Demand
• During a Frequency Event, the Fossil Steam Turbine Controls Provide the Outer
Loop Controls with either the Flow Demand Bias or Speed Error after Deadband
• The Flow Demand Bias or Speed Error after Deadband is converted to the
Droop
MW Bias based on the Flow Demand Curve
– If Using Flow Demand Bias and Flow Demand is Linear:
‣ Droop MW Bias = Flow Demand Bias (%) * Unit MW Capability
– If Using Speed Error after Deadband and Flow Demand is Linear :
‣ Droop MW Bias = Speed Error/Deadband (%) * Unit MW Capability / Droop
• The Droop MW Bias is subtracted from the Unit MW and Unit Demand Output is
Adjusted as Needed
35
External Outer Loop Controls – Fossil Steam
• During normal unit operation with the frequency within the droop deadband:
– Assume the Unit Setpoint is 500 MW, Unit MW is 500 MW and Droop MW Bias is
0 MW Calculated from the Flow Demand Bias or Speed Error after Deadband.
The Droop MW Bias (0 MW) is subtracted from the Unit MW (500 MW) results in
the Total Corrected MW being 500 MW. The inputs to the PID controller will be
Total Corrected MW of 500 and setpoint of 500. This results in no change of the
Flow Demand setpoint output.
36
External Outer Loop Controls – Fossil Steam
• During normal unit operation with the frequency outside the droop deadband and the
Unit supplying 10 MW response to the frequency deviation over the droop
deadband:
– Assume the Unit Setpoint is 500 MW, Unit MW is 510 MW (increased by 10 MW
due to the Droop Response of the Turbine) and Droop MW Bias is 10 MW
Calculated from the Flow Demand Bias or Speed Error after Deadband. The
Droop MW Bias (10 MW) is subtracted from the Unit MW (510 MW) results in the
Total Corrected MW being 500 MW. The inputs to the PID controller will be Total
Corrected MW of 500 and setpoint of 500. This results in no change of the Flow
Demand setpoint output and thus does not affect the droop response of the
Turbine.
37
External Outer Loop Controls – Fossil Steam
38
External Outer Loop Controls – Fossil Steam in Turbine Manual
780 3601
775 3600
Speed, RPM
Power, MW
770 3599
765 3598
760 3597
755 3596
750 3595
745 3594
0 20 40 60 80 100 120 140 160 180 200
Time, Seconds
39
External Outer Loop Controls – Fossil Steam in Turbine Manual
76.8 3601
3600
76.6
Flow Bias, %
Speed, RPM
3599
76.4
3598
76.2
3597
76
3596
75.8 3595
75.6 3594
0 20 40 60 80 100 120 140 160 180 200
Time, Seconds
40
External Outer Loop Controls – Fossil Steam in Turbine Manual
Speed, RPM
Power, MW
748 3602
747 3601
746
3600
745
3599
744
743 3598
0 20 40 60 80 100 120 140 160 180 200
Time, Seconds
41
External Outer Loop Controls – Fossil Steam in Turbine Manual
75.8 3604
75.6 3603
Flow Bias, %
Speed, RPM
75.4 3602
75.2 3601
75 3600
74.8 3599
74.6 3598
0 20 40 60 80 100 120 140 160 180 200
Time, Seconds
42
External Outer Loop Controls – Fossil Steam
• The Megawatt Response is different from starting at 750 MW and 700 MW due to
non-linear valve curve
43
External Outer Loop Controls – Fossil Steam in Turbine Manual
708 3602
3601
706
Speed, RPM
Power, MW
3600
704
3599
702
3598
700
3597
698 3596
696 3595
0 50 100 150 200 250
Time, Seconds
44
External Outer Loop Controls – Fossil Steam in Turbine Manual
700 3605
698
3604
Speed, RPM
Power, MW
696
3603
694
3602
692
3601
690
688 3600
686 3599
0 50 100 150 200 250
Time, Seconds
45
External Outer Loop Controls – Fossil Steam
• MW Response was greater due to decreasing frequency (speed) during the test
• Outer Loop Controls can help Support Droop Megawatt Response
• Note that Turbine Output will be Dependent on Boiler Operating Conditions at the
Time of the Event
46
External Outer Loop Controls – Fossil Steam with Outer
Loop Control
708 3600
3599
706
Speed, RPM
Power, MW
3598
704
3597
702
3596
700 3595
698 3594
0 20 40 60 80 120 140 160 180
100
Time, Seconds
GEN WATTS SPEED FB
47
External Outer Loop Controls – Fossil Steam with Outer
Loop Control
Speed, RPM
Power, MW
3602
696
3601
694
3600
692
690 3599
688 3598
686 3597
0 20 40 60 80 120 140 160 180
100
Time, Seconds
GEN WATTS SPEED FB
48
Conclusions/Recommendations
49
A Southern
Company