Slip form: -
Height= 1- 1.5m
Consist of vertical panels, walings, yokes, horizontal cross bars,
jacks, jack rods, and a working platform
Tests: -
Penetration resistance: -
Initial and final setting determined by penetration resistance
Penetration resistance (Initial setting time) = 3.5Mpa
Penetration resistance (final setting time) = 27.6Mpa
ASTM C – 403
Case study- Quality Control of Concrete during the Slip Form
Erection of Pylon
• 10 m-high pylon with a hollow section.
• Real time quality monitoring by surface velocity
• Minimum surface velocity= 1100 m/s
• Early setting time is defined as the time at which the penetration resistance reaches 3.5 Mpa
• High temperatures fasten the rate of cement hydration accelerating setting
Compressive strength-
Minimum compressive strength= 0.2 MPa
Surface velocity test: -
• Ultrasonic waves are generated.
• Velocity of the ultrasonic wave increases according to the progress of
the hardening of concrete.
Horizontal slip form:-
• Pavements
• High strength concrete(minimum M30)
• More fine materials
• Appropriate admixture dose
• Flexural Strength = 4.5MPa
• Minimum cement content
• OPC = 360 Kg/cu.m
• OPC (Blended with FA- 20%) = 340 Kg/cu.m
• PPC(OPC + 20% FA) = 425 Kg/cu.m
• Workability
• Slump = 25±10 mm
• Water/Cement Ratio = max. 0.45 (OPC)
= max. 0.50 (OPC Blended with FA)