RC Structural Assessment
Formwork assessment
Dimensions
Alignment, plumb & Level
Condition
3
Formwork Assessment
Item 1
Formwork Dimension
+ 10mm / -5mm for dimension
+ 10mm for size of opening
+/- 25mm for location
4
Formwork Assessment
Item 2
5
Formwork Assessment
Item 3
Formwork Condition
free from defects
free from debris
no gap at joints
sound support, bracing &
tie back
6
Reinforcement Assessment
Items 1, 2 & 3
No / Size / Spacing
according drawings
bar spacing not > than specified
7
Reinforcement Assessment
Items 4 & 5
Rebar Condition
securely & properly tied
free from concrete dropping,
corrosion, etc
8
Beam Width Measurement
Tolerance: +10mm / -5mm 9
Beam Depth Measurement
Tolerance: +10mm / -5mm 10
Slab Thickness Measurement
11
Slab bar length measurement
12
Slab bar anchorage
13
Slab & beam anchorage
14
Slab bar lap length measurement
15
Beam bar lap length measurement
16
Bars must be properly & securely tied at intersection
17
Bars must be properly supported by bar chairs
18
Finished Concrete Assessment
3 areas of
assessment
Dimension
Alignment, plumb &
level
Exposed Surface
19
Finished Concrete Assessment
Items 1
Dimension / Opening
+ 10mm / -5mm for
dimension
+ 10mm for size of
opening
+/- 25mm for location
20
Finished Concrete Assessment
Items 2
21
Finished Concrete Assessment
Items 3
Exposed Surface
no exposed coarse aggregates due to grout leakage
smooth cold joint and formwork joint
no bulging
formwork, nails, zinc strips, etc must be removed
22
Column Width Measurement
Tolerance: +10mm / -5mm 23
Column Width Measurement
Tolerance: +10mm / -5mm 24
Column Plumb Measurement
Tolerance: 3mm / 1m - max 20mm 25
Column Plumb Measurement
Tolerance: 3mm / 1m - Max 20mm
26
Slab Soffit Level Measurement
Tolerance: Max. 10mm departure from any point
27
Beam Soffit Level Measurement
Tolerance: Max. 10mm departure from any point
28
Material &
Functional Tests
for Reinforced Concrete
Structures
Concrete Cube
Strength
Rebar Tensile Strength
NDT : Concrete
Uniformity
NDT : Concrete Cover
for rebars
29
Concrete Cube Test
based on compressive
strength results at 28
days
passing criteria as per
SS289
endorsed by PE
30
Concrete Cube Test
31
Steel Reinforcement : Tensile Strength Test
steel reinforcement bar shall
comply with
SS 2:1999 for Grade 500
ribbed bars or
SS 2:1987 for Grade 460
ribbed bars
No non-conforming
reinforcement installed in
structure
32
Ultrasonic Pulse Velocity for Concrete Uniformity
Minimum 2 and
maximum 20 sets
5 columns per set
and 2 readings per
column
to ensure
consistency in
density of concrete
33
Ultrasonic Pulse Velocity for Concrete Uniformity
Assessment based on :
Difference within a column,
the 2 reading not exceeding
0.05km/s
34
Electro-Covermeter Test for Concrete Cover
35
Electro-Covermeter Test for Concrete Cover
According to specification
For each reading
full point for 5mm
Half point for 8mm
For each location
No point if any of the readings exceeding
12mm
36
Assessment
A sample can be a beam, a column, a wall or a slab
Precast assessment* is required only if the precast concrete
volume exceeds 20% of the total structural concrete volume
Structural steelwork* or pre-stressed concrete assessment is
required only if each exceeds 20% of the total structural cost
37
Assessment Preparation
38
Assessment Process
Assessor to compute score and endorse
assessment form
Copy of the assessment will be given to the
contractor
Assessment approx. 45 mins per session
39