Professional Documents
Culture Documents
Fire Presentation With Elite Fire Calculations
Fire Presentation With Elite Fire Calculations
Codes used:
NFPA 13,14 ,20
Units :
Now Please click on
New
This is the
open project
button
Calc Demand Flow Rate (GPM): After calculations have been performed, the
program will put the total system demand flow in this field. This information will
.get printed on the General Project Data report
Hydrant test data
And this is the info at Two flow values can be selected here,
each one corresponding to a set of 3 test data values below
it (test flow rate, static pressure and residual pressure). The
first set of test data is without an exterior hose flow reducing
supply, while by default the second set of test data is not
.entered, and all values are 0
0 والن النظام لم يتم عمل تجربة له بعد ال ندخل هذه القيم و نتركها ب
Click on the Enter/Edit pipe data
.Add Pipe: This button will add a blank pipe section to the end of the existing pipe sections -1
.Delete Pipe: This button will delete the current pipe section from the existing pipe sections -2
.Sort Pipe: This button will sort the pipe sections and is useful in organizing the pipe information -3
Clear Pipe: This button will erase all the pipe data entered into this window. You will be asked to -4
.confirm this deletion
Mark Inflow Node: This button will mark the current pipe section as the inflow node. This will -5
.place a blue arrow () to the left of the pipe section as well
.Unmark Inflow Node: This button will unmark the inflow node -6
CPLD: This button will open a window where you can edit the names and abbreviations used to -7
represent material type A, the Alternate CPLD (Constant Pressure Loss Device). The default name
.for this device is Alarm Check Valve. Not used because we use standard items
1
2
.Beg: This field represents the beginning node of the pipe section
.End: This field represents the ending node of the pipe section
Because each pipe have beg. & End
But please enter pipes as small numbers and sprinklers as big number
..…,like 100,101
.
Diameter: This field shows the diameter of the pipe in the section. -1
It can be selected from the existing valid pipe sizes or can be entered
. .as zero to be auto sized
Length: This field represents the length in feet of the pipe without -2
.considering any fittings
.
Sprk Elev: This field represents the elevation of the node with
respect to the zero elevation line in feet. The Zero Elevation Line
is usually located at the point of demand/supply that is usually the
system inflow node. Sprk Elev: This field represents the elevation
of the node with respect to the zero elevation line in feet. The
Zero Elevation Line is usually located at the point of
.demand/supply that is usually the system inflow node
These fields represent the K-Factor for the pipe section. If-1
you have a sprinkler node this number shall be 5.6 or what
ever is the sprinkler k-factor and if it was a pipe it shall equal
0
.Or you could use D for sprinkler or I for pipe
.
Press Est: This field represents the nodal pressure estimate.
Although FIRE can generate its own pressure estimates,
computations can be performed faster if you input good
.residual pressure estimates for each node
Sprk Elev: This field represents the elevation of the node with
respect to the zero elevation line in feet. The Zero Elevation Line
is usually located at the point of demand/supply that is usually the
system inflow node. Sprk Elev: This field represents the elevation
of the node with respect to the zero elevation line in feet. The
Zero Elevation Line is usually located at the point of
.demand/supply that is usually the system inflow node
This field represents the area of coverage provided by the -1
sprinkler located at this node, assuming that there is a
.sprinkler at this node
Area Grp: This field represents a sprinkler grouping -2
reference letter. The area group is a way to group sprinklers
together that cover the same area. You may, for example,
put all sprinklers that cover office 1 in area group 'A', and the
sprinklers that cover office 2 in area group 'B'. When you
choose "Use Automatic Peaking Calculations" from the
Calculation window, FIRE will automatically calculate which
.area group has the worst HMD node
NSprk Flow: This field is only used to specify a fixed discharge
rate for a hose stream or an in-rack sprinkler allowance. When
inside hose stations are planned or are required by other
standards, a water allowance of 50 GPM for one hose station or
100 GPM for two or more hose stations should be applied at the
point of connection to the system. If more than one hose station is
needed in the design, add 50 GPM to the two hose streams most
remote to the sprinkler system but we usually take it 250 gpm for
.2.5” hose
Std Fit: This field represents the number of fittings associated
with the pipe. Simply enter the number of fittings followed by
the letter designating that fitting. For example, "3E" would
.designate 3 - 90 degree elbows
F - 45 Degree Elbow
E - 90 Degree Elbow
L - Long Turn Elbow
T - Tee or Cross
B - Butterfly Valve
G - Gate Valve
C - Check Valve
NStd: This field represents an equivalent length for non-
.standard fittings. Not used because we use standard fitting
Eq Len: This field is output only and prints the total equivalent
.length of the pipe and all the fittings that are included on the pipe
P Type: This field represents the pipe type group reference
number. Pipe type groups are used if you are going to have FIRE
automatically size your pipes. You can group pipes together so
that during auto sizing, pipes of the same pipe type group will all
.have the same diameter
Global Editor:used to Edit and create your own pipe reference not
.used because we use standard fitting
Tree and grid builder shall not be used due to because they do not
.show UP and DN
Demand This design mode calculates the minimum total system demand pressure and
demand flow that will satisfy the minimum residual pressure requirement for the HMD
.(hydraulically most demanding )sprinkler
it can greatly speed up the calculations the program performs by checking the Use Residual
.Pressure Estimates in the Options frame described below
The minimum residual pressure is the lowest acceptable pressure allowed the hydraulically
most demanding (HMD) (hydraulically most demanding )sprinkler node. Note that NFPA 13
does not allow any HMD sprinkler residual pressures to be less than 7 psi
Min residual pressure we get it for density/area method
Here appears the number of inflow node we determined in pipe data
tab
Maximum Nodal Pressure (psi): This field is used to enter the maximum nodal pressure in psi for the
.imbalance restrictions
Average Nodal Pressure (psi): This field is used to enter the average nodal pressure in psi for the
.imbalance restrictions
:Oscillation Damping Factor
The oscillation damping factor (from 1 to 99) is a parameter FIRE uses to control the nodal pressure
adjustments it makes in attempting to find a solution. Small damping factors (1 - 4) allow FIRE to make
relatively large pressure adjustments per iteration so that a solution can more quickly be obtained;
however, the problem with using small damping factors is that FIRE can sometimes overadjust nodal
pressures such that a divergent situation arises. If a divergent situation occurs, FIRE will print a
message indicating the situation. If this ever happens, increase the damping factor and run the
calculation again. If divergence still persists, some changes in the piping system may be required. For
.example, missing or grossly oversized pipes will cause wild oscillations in the calculations
Initial Damping Factor: This field is used to enter the initial damping factor. In general, all systems
.should be started with a damping factor of 4 or greater
Minimum Damping Factor: This field is used to enter the minimum damping factor. Most normal pipe
network systems should have minimum damping factors of 1 or 2. If a pipe changes abruptly in size at
one point or the solution is oscillating and not converging, you should use a minimum damping factor of
3 to 8. The minimum damping factor must be either equal to or less than the initial damping factor
.specified
Maximum Allowable Water Velocity: This field is used to enter the maximum water velocity, in ft/sec -1
.by default, that you will allow to flow through the pipe sections that you want FIRE to autosize
Maximum Allowable Frictional Loss Per 100' Of Pipe: This field is used to enter the maximum -2
.frictional loss per 100' of pipe, in psi by default
Total number of pipe in your network -1 HMD:Hydrulically most demanding-3
Total number of sprinkler you entered -2 . sprinkler node number
of (should we say pipe with K-factor not residual pressure at HMD node as we-4
equal 0.(check 1) stated earlier the min is 7 psi and
maximum 175 but typically it will range
between (7-20) psi. (check 2)
Actual flow at HMD Node: ranges-5
depending on K-factor. (check 3)
Max flow velocity and the pipe which it -1 Residual pressure at inflow node (Fire-4
is high choose higher pipe size .(check pump) in Psi. (check 7)
4) Total Demand flow for the system at -5
Total Sprinkler flow for all sprinklers. -2 inflow node (Fire Pump) (check 8)
(check 5) Those 2 out puts are fire pump flow
. and head
Total non Sprinkler flow for all Hoses-3
or hydrants. (check 6)
Note: 1 m3/hr = 4.4 gpm
Questions & answers
Q.1.I can't get the FIRE to give me a solution for the system.
Solution:
There are several things to help with this problem.
First, BE SURE YOUR DATA IS ENTERED CORRECTLY.
Check for abrupt changes in pipe diameter. For example, see that you don't have a 10" main feeding a 1" branch line. Also, try
to avoid combinations of extremely long and short pipe sections.
Run the calculations in supply mode first, keep the residual pressures, and re-run the calculations in demand mode with "Use
Residual Pressure Estimates" checked. You can run the calculations in supply mode by setting a residual pressure at the
inflow node on the Enter/Edit Pipe Data screen. Choose Supply under the Mode heading on the Calculation tab of
Calculation screen.
Set the maximum nodal pressure imbalance higher than your target value and run the calculations. When a solution is reached,
set the maximum nodal pressure imbalance to your target value, choose to use the residual pressures, and run the
calculations again.
Use Auto sizing as a tool, not an absolute. Some “feel” for the system will be needed to use good judgment in pipe sizing.
Questions & Answers
Q.3.General Questions...What is the difference between the area of operation and the maximum sprinkler area?
Solution
The first is the Maximum Area Per Sprinkler on the GPD screen. This value provides the default area for any sprinklers whose
area is not explicitly specified on the Enter/Edit Pipe Data screen. This area is used to calculate the under-sprinkler density
by dividing the sprinkler's flow by the area it covers.
The next area is the Area of Sprinkler Operation on the GPD screen. Note that this doesn't necessarily mean the total building
area. This area is simply the area for which you are trying to cover. In most cases this will be the 1500 or 2500 sq. ft.
around the HMD node. Consult NFPA 13 and/or your AHJ for more information on your required area of coverage. This
area will be used for two purposes. The total sprinkler flow will be divided by this area to produce an "average" density.
Also, this area will be divided by the number of active sprinklers to give an average area per sprinkler. Both of these values
will print on the Overall Network Summary.
Selecting the pump
Go to Fire pump catalouges and select fire pump based on the Head and flow you Got
Please note that fire pumps have standard capacity
Also you have to know that fire pump have operating range from :
@ shut off head or no flow condition pressure will not be higher than 140% of pump
rated pressure .
@ 100% of flow pump will give 100% of rated pressure .
@maximum operating point 150% of pump rated flow it will give 65% of rated
pressure.
So the operating the pump is 90%-140% of rated flow taken pressure in consideration
and by that I mean check that will pump give min operating pressure at maximum
flow.
What happens if system pressure exceeds 175 Psi , a PRV( pressure reducing valve is
used before the fire control zone.
Fire pump
• NFPA 20 made fire pump flow fixed for strandirization and easy comparing pumps:
Thank you see you next time