Perlindungan Kilat 2012 - Rev00 (Ir. Hamzah)
Perlindungan Kilat 2012 - Rev00 (Ir. Hamzah)
SISTEM
PERLINDUNGAN
KILAT
2
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Type of Damage
Injury of living beings due to step and
touch voltages
Physical damage (fire, explosion, etc.)
Failure of internal systems due to
Lightning Electromagnetic Impulse
(LEMP)
3
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Type of Loss
Loss of human life
4
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Design and Installation Standard
MS IEC 62305-1: General principles
5
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Basic Design Criteria
To enclose the structure within an
earthed and perfectly conducting
metallic shield (box)
6
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Lightning Protection Level (LPL)
Also known as Class of LPS
LPL I
─ 3 kA to 200 kA with a probability that:
99% of strikes will be lower than 200 kA
99% of strikes will be higher than 3 kA
LPL II
─ 5 kA to 150 kA with a probability that:
98% of strikes will be lower than 150 kA
97% of strikes will be higher than 5 kA
7
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Lightning Protection Level (LPL)
LPL III
─ 10 kA to 100 kA with a probability that:
97% of strikes will be lower than 100 kA
91% of strikes will be higher than 10 kA
LPL IV
─ 16 kA to 100 kA with a probability that:
97% of strikes will be lower than 100 kA
84% of strikes will be higher than 16 kA
8
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
LPS Design Considerations
Air termination system
9
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Air Termination System
To capture the lightning discharge
current and dissipate to earth via the
down conductor and earth
termination
Design of the air termination
─ Air terminals (or finials)
10
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Air Termination System
─ Catenary (or suspended) conductors
11
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Air Termination System
─ Natural components
Class of LPS Material Thickness
(mm)
Lead -
Stainless Steel ≥4
Galvanized Steel ≥4
I to IV Titanium ≥4
Copper ≥5
Aluminium ≥7
Zinc -
12
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Air Termination System
3 basic methods recommended for
determining the POSITION of the air
termination systems:
─ Protective angle method
─ Rolling sphere method
─ Mesh method
13
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Protective Angle Method
The protective angle afforded by an
air terminal is clearly a three
dimensional concept
A – tip of air terminal
B – reference plane
OC – radius of protected area
h1 – height of an air terminal above the
reference plane of the area to be protected
α – protective angle according to Table 1
14
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Protective Angle Method
Protective angle according to Table 1
is a change to the simple 450 zone of
protection in BS 6651
15
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Protective Angle Method
View from A
16
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Down Conductor System
An equal spacing of the down
conductors is preferred around the
perimeter
Typical values of the distance
between down-conductors
Class of LPS Typical Distances (m)
I 10
II 10
III 15
IV 20
17
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Down Conductor System
There should always be a min. of 2
down conductors distributed around
the perimeter of the structure
18
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Structural Steelwork
The electrical continuity of the
reinforcing bars shall be determined
by electrical testing between the
uppermost part and ground level
The overall electrical resistance
should not be greater than 0.2 Ω
If this value is not achieved, or it is
not practical to conduct such testing,
the reinforcing steel shall not be used
as a natural down-conductor
19
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Earth Termination System
For the dispersion of the lightning
current safely and effectively into the
ground
A low earthing resistance is required
(with an overall earth termination
system of ≤ 10 Ω)
3 basic earth electrode arrangements
are used:
─ Type A arrangement
─ Type B arrangement
─ Foundation earth electrodes
20
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Type A Arrangement
Consist of vertical earth electrodes,
connected to each down conductor
fixed on the outside of the structure
21
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Type B Arrangement
Comprise a ring conductor external to
the structure
22
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Foundation Earth Electrodes
This is essentially a type B earthing
arrangement
23
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
References
Protection Against Lightning, MS IEC
62305 series, 2007
“A Guide to BS EN 62305:2006,
Protection Against Lightning”, U.K:
Thomas & Betts
24
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
25