Professional Documents
Culture Documents
Bus Bar Protection Scheme 2003
Bus Bar Protection Scheme 2003
IMPROVE THE RELIABILITY OF SUPPLY. ALTHOUGH, THE VARIOUS SCHEMES HAVE BEEN DEVELOPED FOR THE PROTECTION OF BUS-BARS BUT THE MOST COMMON SCHEME IS DIFFERENTIAL PROTECTION
SCHEME EMPLOYED FOR THE PROTECTION OF SUB- STATION BUS-BARS IS SHOWN IN PREVIOUS SLIDE.
THE SECONDARY'S OF ALL THE CTS CONNECTED IN INCOMING &
OUTGOING FEEDERS ARE CONNECTED IN PARALLEL AS BEFORE. THE CTS DESIGNED IN SUCH A WAY THAT UNDER NORMAL CONDITION , THE EMFS INDUCED IN SECONDARYS OF THE CTS PLACED ON OUTGOING FEEDER. THEN NO CURRENT FLOWS THROUGH THE OPERATING COIL OF THE RELAY WHICH IS CONNECTED ACROSS THE CONNECTING WIRES.
OPEARTION
UNDER NORMAL CONDITIONAL OR EXTERNAL FAULT CONDITIONS, THE SUM
OF THE CURRENT ENTERING THE BUS BAR IS EQUAL TO THE SUM OF CURRENT LEAVING IT. THEREFORE, NO CURRENT FLOWS THROUGH THE OPERATING COIL. HOWEVER, WHEN FAULTS OCCURS WITHIN THE PROTECTED ZONE ( BUS- BAR), THE CURRENT ENTERING THE BUS-BAR WILL NO LONGER BE EQUAL TO THOSE LEAVING IT. THUS, A DIFFERENTIAL CURRENT FLOWS THROUGH THE OPERATING COIL OF THE RELAY WHICH CLOSES THE TRIP CIRCUIT.
CT SATURATION OFTEN BECOMES A PROBLEM AS CTS MAY NOT BE SUFFICIENTLY RATED FOR WORST FAULT CONDITION CASE
LARGE DYNAMIC FORCES ASSOCIATED WITH BUS FAULTS REQUIRE FAST CLEARING TIMES IN ORDER TO REDUCE EQUIPMENT DAMAGE
WITH BOTH DEPENDABILITY AND SECURITY IMPORTANT, PREFERENCE IS ALWAYS GIVEN TO SECURITY.
INTERLOCKING SCHEMES OVER-CURRENT (UNRESTRAINED OR UNBIASED) DIFFERENTIAL OVER-CURRENT PERCENT (RESTRAINED OR BIASED) DIFFERENTIAL LINEAR COUPLERS HIGH-IMPEDANCE BUS DIFFERENTIAL SCHEMES
COORDINATION
TIME
REQUIRED .
50
BLOCK
CARE
MUST
BE
TAKEN
WITH
50
50
50
50
50
OF
ALL
CURRENTS
CT
RATIO
MATCHING
MAY
BE
REQUIRED.
ON EXTERNAL FAULTS, SATURATED
CURRENT.
TIME DELAY USED TO COPE WITH CT
SATURATION.
External Fault
40 V
10 V
10 V
0V
20 V
0V
59
ESEC= IPRIM*XM - SECONDARY VOLTAGE ON RELAY TERMINALS IR= IPRIM*XM /(ZR+ZC) MINIMUM OPERATING CURRENT WHERE, IPRIM PRIMARY CURRENT IN EACH CIRCUIT XMLINER COUPLER MUTUAL REACTANCE (5V PER 1000AMPS => 0.005 @ 60HZ ), ZR RELAY TAP IMPEDANCE ZC SUM OF ALL LINEAR COUPLER SELF IMPEDANCES
If = 8000 A
40 V 0V 10 V 10 V 0V 20 V
59
0A
2000 A
2000 A
0A
4000 A
REQUIRE DEDICATED AIR GAP CTS, WHICH MAY NOT BE USED FOR ANY
OTHER PROTECTION.
CANNOT BE EASILY APPLIED TO RECONFIGURABLE BUSES. THE SCHEME USES A SIMPLE VOLTAGE DETECTOR IT DOES NOT PROVIDE
OSCILLOGRAPHY,
BREAKER
FAILURE
PROTECTION,
OTHER
FUNCTIONS)
OPERATING
SIGNAL CREATED BY CONNECTING ALL CT SECONDARY'S IN PARALLEL. CTS MUST ALL HAVE SAME RATIO. MUST HAVE DEDICATED CTS OVERVOLTAGE ELEMENT OPERATES ON VOLTAGE DEVELOPED ACROSS RESISTOR CONNECTED IN SECONDARY CIRCUIT. REQUIRES VARISTORS OR AC SHORTING RELAYS TO LIMIT ENERGY DURING FAULTS. ACCURACY DEPENDENT ON SECONDARY CIRCUIT RESISTANCE. USUALLY REQUIRES LARGER CT CABLES TO REDUCE ERRORS HIGHER COST
59
PERCENT
CHARACTERISTIC USED
RESTRAINING
SIGNAL
CAN
BE
I DIF I1 I 2 ... I n
I RES I1 I 2 ... I n
DIGITALLY.
CT RATIO MATCHING DONE INTERNALLY (NO AUXILIARY CTS). DEDICATED CTS NOT NECESSARY. ADDITIONAL
ALGORITHMS
IMPROVE
SECURITY
OF
PERCENT
BUSES.
DIFFERENTIAL COMPUTATION.
SWITCHING OF CT SECONDARY CIRCUITS NOT REQUIRED. LOW SECONDARY BURDENS. ADDITIONAL FUNCTIONALITY AVAILABLE. DIGITAL
A) BETTER FILTERING
B) FASTER RESPONSE
ADDITIONAL
SECURITY
TO
THE
MAIN
DIFFERENTIAL
INSTALLED IN BAYS.
52 DAU 52 DAU 52 DAU
DAUS.
COMMUNICATIONS BETWEEN DAUS
AND
CU copper fiber
CPU
OVER
FIBRE
USING
PROPRIETARY PROTOCOL.
SAMPLING
SYNCHRONISATION
ALL
52 52 52
CURRENTS APPLIED TO A
SAMPLING NECESSARY
SYNCHRONISATION
HARDWARE NEEDED)
WELL SUITED TO BOTH NEW AND
RETROFIT APPLICATIONS.
THE OPERATING TIME OF INVERSE DEFINITE MINIMUM TIME LAG RELAYS IS INVERSELY PROPRTIONAL TO THE OPERATING CURRENT, BUT IS NEVER LESS THAN THE MINIMUM DEFINITE FOR WHICH IT IS SET.
IF A FAULT OCCURS BETWEEN STATION E AND F, IT WILL BE CLEARED IN 0.1 SECOND BY THE RELAY AND CIRCUIT BREAKER OF SUBSTATION E BECAUSE ALL OTHER RELAYS HAVE HIGHER OPERATING TIME. IF THE RELAY AT SUB STATION E FAILS TO TRIP, THE RELAY AT D WILL OPERATE AFTER A TIME DELAY OF 0.5 SECONDS I.E. AFTER 0.6 SECONDS FROM THE OCCURRENCE OF FAULT.
RELAYS ARE CONNECTED WHEREAS DIRECTIONAL OVER CURRENT INSTANTANEOUS RELAYS ARE CONNECTED AT SUB-STATION END.
IF
FAULT IS FED; (A) DIRECTLY FROM FEEDER 2 VIA RELAY B. (B) FROM FEEDER I VIA A , P AND SUB-STATION Q AS SHOWN IN FIG. BY THE
DOTTED ARROWS.
THIS CLEARLY SHOWS THAT DIRECTIONAL RELAY P CARRIES THE CURRENT IN NORMAL DIRECTION WHERE AS DIRECTIONAL RELAY Q CARRIES THE CURRENT IN REVERSE DIRECTION MOMENTARILY. THIS OPEARATES THE RELAY Q INTANTANEOUSLY. THE RELAY B HAVING INVERSE TIME CHARACTERISTICS ALSO OPERATES BECAUSE OF HEAVY FLOW OF CURRENT .
INTER-CONNECTED BY THE NUMBER OF FEEDERS FORMING A CLOSED CIRCUIT IS CALLED A RING- MAIN SYSTEM.
RELAYS HAVING INVERSE TIME CHARACTERISTIC ARE EMPLOYED. WHEREAS DIRECTIONAL OR REVERSE POWER ARE EMPLOYED ON BOTH THE SIDES OF EACH SUBSTATION. THE MINIMUM DEFINITE TIME OF ALL THE RELAY ARE SET PROPERLY AS SHOWN IN FIG.
THE SCHEMATIC
WINDING (B OR B)
UNDER NORMAL CONDITIONS, THE CURRENTS AT TWO ENDS OF THE FEEDER ARE EQUAL SO THAT THE SECONDARY CURRENT IN BOTH SETS OF CTS ARE EQUAL. CONSEQUENTLY, THE E.M.FS INDUCED IN THE