PART 1 : CALCULATIONS OF LOADINGS AND DETERMINATION OF


ALLOWABLE IMPOSED LOADINGS

Taking Critical Case of Main Building

(1) Second Storey Slab Checking (** Worst Case)

l
y
/l
x
=2.2, One way slab (With Imposed loads of 4 KN/m
2
)

Slab thickness =150mm
d =150-2(20)-2(10) =90mm

Self Weight =24 x 0.15 x 1m strip width =3.6 kN/m

Service Dead Load =0.75 kPa (assumed) x 1m strip width =0.75 kN/m

Live Load =4 KN/m
2
(assumed) x 1m strip width =4 kN/m

W
ult
=SW +SDL +LL =8.35 kN/m

M
max
=W
ult
L
2
/8 =8.3 x 2
2
/ 8 =4.15 kNm

Assumed f
cu
=20 N/mm
2
(Concrete Characteristic Strength) Mild Steel of 250N/mm
2


k =M
max
/ f
cu
bd
2
=4.15 x 10
6
/ 20 x 1000 x 90
2
=0.0256 < 0.156

Z =90 {0.5 +[0.25 (0.0256/0.9)]
1/2
}=87.4mm > 0.95d =85.5mm

A
s(required)
=4.15 x 10
6
/ 0.87 x 250 x 85.5 =223 mm
2


A
s(provided
) =R12-225mm as scanned at the site
=5R12 =565 mm
2
> A
s(required)
=223 mm
2
Ok, assumption correct



Harvest
PART 2 : Checking of Main Building Foundation Loads
(All dimensions & structures are to be assumed
conservatively)









Elevation view
1st storey plan

Harvest





2nd storey plan
3rd storey plan

Harvest
(2a) First Storey:

(i) Dead Load:

Assume slab to be non-suspended slab
Floor finishes =0.75 kPa (assumed) x (6/2 +4/2) x (5.6/2 +4.4/2) =18.75 kN
Column =0.45 x 0.4 x 4.75 x 24 = 20.52 kN
Brickwall =20 x 0.175 x (6/2 +4/2) x 4.75 = 83.13 kN
Total =122.4 kN

(2b) Second Storey:

(i) Dead Load:

Slab =0.15m (assumed) x 24 x (6/2 +4/2) x (5.6/2 +4.4/2) = 90 kN
Floor finishes =0.75 kPa (assumed) x (6/2 +4/2) x (5.6/2 +4.4/2) = 18.75 kN
Column =0.45 x 0.4 x 3.46 x 24 = 15 kN
Brickwall =20 x 0.175 x (6/2 +4/2) x (5.6/2 +4.4/2) = 60.55 kN
Main Beam =24 x 0.6m x 0.8m x (6/2 +4/2) = 57.6 kN
Secondary Beam =24 x 0.25 x 0.45 x (6/2 +4/2) = 13.5 kN
Total =255.4 kN

(ii) Live Load:

LL =4 KN//m
2
(assumed) x (6/2 +4/2) x (5.6/2 +4.4/2) = 100 kN

(2c) Third Storey or 2
nd
Upper Storey:

(i) Dead Load:

Slab =0.15mm (assumed) x 24 x (6/2 +4/2) x (5.6/2) = 50.4 kN
Beam =24 x 0.6m x 0.8m x 6 = 69.1 KN
Floor finishes =0.75 kPa (assumed) x (6/2 +4/2) x (5.6/2) = 10.5 kN
Column =0.45 x 0.4 x 3.06 x 24 = 13.22 kN
Brickwall =20 x 0.175 x (6/2 +4/2) x 3.06 = 53.55 kN
Total =196.77 kN
(ii) Live Load: (2
nd
Upper Storey Rooms)

LL =4 KN/m
2
(assumed) x (6/2 +4/2) x (5.6/2) = 50 kN

Harvest

(2d) Roof Level:

Brickwall =20 x 0.175 x 1.81 x (6/2 +4/2) = 32 kN
Service Dead Load
=0.75 kPa (assumed) x (5.6/2 +4.4/2) x (6/2 +4/2) = 18.75 kN
Total =50.75 kN

Roof Live Loads =0.75KN/m
2
x 5 x 5 = 14.07 KN

ROOF Materials =1.5KN//m
2
x 5 x 5 = 56.25 KN


Total Dead Load = 122.4 + 255.4 + 196.77 + 50.75 + 56.25 = 681.57 kN


Total Live Load = 100 + 50 + 14.07 = 164.07 kN
Total DL + LL = 776.54 kN

Strip Footing Size of 2m width (instead of 4m) x 4m (Span Length) x .75 Thk



Ground Footing Foundation Weight =24.0 x 2 x 4 x .75 = 144.0 KN

Acting Soil Pressure =989.64 / (2.0 x 4.0) =123.71 KN//m
2



Refer to Section 5.6 of the report, the tested foundation allowable bearing soil
pressure is 140.00 KN//m
2
>123.71 KN//m
2
which is O.K.!