1 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

Page:

(4)-G71000-V0022-D001

Date:10.01.08

Client

FIATINDIA AUTOMOBILES (P) LTD.

Project

220 kV Switchyard at Ranjangaon.

Consultant

TCE Consulting Engineers Ltd, Pune.

Title

220kV CT Adequacy check calculations.

Document no:

(4)-G71000-V0022-D001

For Approval

For Review

For Information

Rev

Date

Page

Prepared

Checked

10.01.08

All

SGP

SGP

Approved

2 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

Page:

(4)-G71000-V0022-D001

Date:10.01.08

ABBREVIATIONS USED FOR CALCULATION :


ISSC =

Maximum symmetrical short circuit current.

Ipn =

CT rated primary current.

Isn =

CT rated secondary current.

ISCC EXT FAULT =

External short circuit fault current.

VK =

Knee point voltage.

Ktd =

Transient dimensioning factor.

KSSC =

Rated symetrical short circuit current factor.

K'SSC =

Effective symetrical short circuit current factor.

R'b =

Connected resistive burden.

Rb =

Rated resistive burden.

Rct =

Secondary winding resistance at 75 Deg. C

CT dimensioning formula

Rct Rb
K ' SSC
Rct R 'bI

K SSC

Page:

(4)-G71000-V0022-D001

Date:10.01.08

SUMMARY OF CT DATA :
Sl.No
A

Description
220kV Line From
Ranjangaon
Ratio

Bay No
Bay 05

Class
Burden
Application

Relay details
220kV Line From
Ranjangaon
Ratio
Class
Burden
Application

Relay details
220kV Point of sulpply
Breaker
Ratio
Class
Burden
Application

Relay details
220kV Trfo Bay- 01
Ratio
Class
Burden
Application
Relay details

3 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

Core 1

Core 2

800-400-200/
1A
PS
NA

800-400200/ 1A
PS
NA

Pilot wire
differential

Spare

7SD

Core 3

Core 4

Core 5

0.2
20 VA

800-400200/ 1A
PS
NA

800-400200/ 1A
PS
NA

Metering &
SCADA

OC & EF
Protection

Bus Bar
Protection

NA

7SJ62

7SS52

0.2
20 VA

800-400200/ 1A
PS
NA

800-400200/ 1A
PS
NA

Metering &
SCADA

OC & EF
Protection

Bus Bar
Protection

NA

7SJ62

7SS52

0.2
20 VA

800-400200/ 1A
PS
NA

800-400200/ 1A
PS
NA

TOD Metering

Spare

Bus Bar
Protection

800-400-200/ 1A

Bay 06
800-400-200/
1A
PS
NA

800-400200/ 1A
PS
NA

Pilot wire
differential

Spare

7SD
800-400-200/
1A
PS
NA

800-400200/ 1A
PS
NA

OC & EF
Protection

Spare

7SJ62

800-400-200/ 1A

800-400-200/ 1A

NA

7SS52

150 / 1A

150 / 1A

150 / 1A

150 / 1A

PS
NA

5P 20
5 VA

0.2
30 VA

0.2
30 VA

800-400200/ 1A
PS
NA

Trafo
Differeential

OC & EF
Protection

FIAPL Metering

MSETCL
SCADA

Bus Bar
Protection

7UT613

7SJ62

150 / 1A

150 / 1A

150 / 1A

150 / 1A

PS
NA

5P 20
5 VA

0.2
30 VA

0.2
30 VA

800-400200/ 1A
PS
NA

Trafo
Differeential

OC & EF
Protection

FIAPL Metering

MSETCL
SCADA

Bus Bar
Protection

7UT613

7SJ62

7SS52

220kV Trfo Bay- 02


Ratio
Class
Burden
Application
Relay details

7SS52

Page:

(4)-G71000-V0022-D001

Date:10.01.08

A 220kV Line From Ranjangaon


A-1-1

Core 1 - Pilot wire differential Protection

Fault current Iscc =

V K K td
Ktd =

40000

I SCC
1 . 3 x I PN
1.2

( R ct + R ' b ). I SN

for Transmission Line as per Siemens catalog

Core-1 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6
A-1-2
Rrelay

800
1
NA
PS

CT Sec. resistance(Ohms)- Rct

Core-1
400
1
NA
PS

200
1
NA
PS

NA

NA

NA

16

Burden on secondary side of Core 1 For 7SD Relay


0.05 VA

for 7SD Relay

Cable Resistance (Rc)


Length of cable from CT to relay (L)

9.48 ohm/kM
150 mtrs.

CT lead burden in two way (RL)

2 I SN 2 Rc L 1000

Connected resistive burden

R'b=Rrelay+Rlead

for 2.5 sq. mm CU. Cable

=
=

2.844 Ohm
2.844 VA @ Isn=1A

2.894 VA @ Isn=1A

Accordingly Required resistive burden R'b=3.844 VA


A-1-3

Selecting PS Class core for 800/ 1A Ratio

Minimum required Vk as per 7SD protection manual

VK K td
A-1-4

I SCC (EXT. FAULT)


1.3 x I PN

(R CT R' B ).I SN

872.03 V

for Ipn 800A

1005.60 V

for Ipn 400A

Selecting PS Class core for 400/ 1A Ratio

Minimum required Vk as per 7SD protection manual

VK K td

4 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

I SCC (EXT. FAULT)


1.3 x I PN

(R CT R' B ).I SN

Page:

(4)-G71000-V0022-D001

Date:10.01.08

Conclusion
With ratio as 800/1 A, class PS, Rct=16 ohm connected to 7SD relay requires a minimum Vk as 872.03V , and with
ratio as 400/1 A, class PS, Rct=8 ohm connected to 7SD relay requires a minimum Vk as 1005.60V. However
selected Knee point voltage of CT is 30 ( Rct + 36) i.e. For 800/1A Vk = 1560V & for 400/1 Vk = 1320V. Hence
selected Knee point voltage is adequate.
A-2-1

Core-2 Spare

Core-2 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6

800
1
NA
PS

CT Sec. resistance (Ohms) - Rct

Core-2
400
1
NA
PS

200
1
NA
PS

NA

NA

NA

16

Knee Point Voltage Selected Vk = 30(Rct +36)


A-3-1

Core-3 MSETCL Metering & SCADA Purpose

Core-3 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6
A-3-2

800
1
20
0.2

CT Sec. resistance (Ohms) - Rct

Core-3
400
1
20
0.2

200
1
20
0.2

NA

NA

NA

16

Burden at secondary side of core-3 for metering.

Equipment
MFM
Analog Amm. 3 No
Analog MW Meter
Total

5 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

Burden in VA
0.2
4.5
1.0
5.7

CT lead burden in two way (Rlead) =

Connected resistive burden

2.844 Ohm
2.844 VA @ Isn= 1 A
R'b=Rm+Rlead

(As calculated in B-1-2)

8.544

VA @ Isn= 1 A

Conclusion
As calculated from above , the required VA burden is 8.544 VA , Hence selected ratio of 800-400-200/1 A with class
0.2 & 20 VA burden is adequate.

A-4-1

Page:

(4)-G71000-V0022-D001

Date:10.01.08

Core 4 - OC & EF Protection with relay 7SJ62

Maximum Fault current Issc =

40000 A

Core-4 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6
A-4-2

800
1
NA
PS

CT Secondary resistance (Ohms)-Rct

Core-4
400
1
NA
PS

200
1
NA
PS

NA

NA

NA

16

Burden at secondary side of core-4 for protection

Rrelay

6 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

0.05 VA

For 7SJ62 relays as per SIEMENS Relay manual

Cable Resi. (RC)


Length of cable from CT to relay (L)
CT lead burden in two way (RLead)

9.48 ohm/kM
150 mtrs.

= 2I

SN 2

2 Nos.

for 2.5 sq. mm CU. Cable

R LL1000

Connected resistive burden


R'b=Rrelay+Rlead
A-4-3
Checking of CT adequacy

=
=

2.844 Ohm
2.844 VA @ Isn=1A

2.944 VA @ Isn=1A

Accordingly required resistive burden R'b=2.894VA


As per Siemens Manual the minimum required symetrical short circuit current factor (K'ssc) shall be at least 20
Minimum required Vk as per siemens protection manual

VK

K'ssc
(R CT R'B ).ISN =
1.3

291.45 V

for Ipn 800A

VK

K'ssc
(R CT R'B ).ISN =
1.3

168.37 V

for Ipn 400A

VK

K'ssc
(R CT R'B ).ISN =
1.3

106.83

for Ipn 200A

Conclusion
With ratio as 800/1 A, class PS, Rct=16 ohm connected to 7SJ62 relay requires a minimum Vk as 291.45V , and
with ratio as 400/1 A, class PS, Rct=8 ohm connected to 7SJ62 relay requires a minimum Vk as 168.37,with ratio
as 200/1 A, class PS, Rct=4 ohm connected to 7SJ62 relay requires a minimum Vk as 106.83V However selected
Knee point voltage of CT is 40 ( Rct + 7) i.e. For 800/1A Vk = 920V & for 400/1 Vk = 600V, for 200/1 A Vk = 360V.
Hence selected Knee point voltage is adequate.

A-5-1

7 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

Page:

(4)-G71000-V0022-D001

Date:10.01.08

Core 5 - Bus Bar Protection with relay 7SS52

Fault current Issc =

40000 A

Core-5 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5

800
1
NA
PS

CT Sec.resistance (Ohms) - Rct

6
A-5-2

Core-5
400
1
NA
PS

200
1
NA
PS

NA

NA

NA

16

Burden at secondary side of core-5 for Busbar protection

Rrelay

1.8 VA

For 7SS5 relays

Cable Resistance. (Rc)


Length of cable from CT to relay (L)

CT lead burden in two way (RLead)

Connected resistive burden


A-5-3

9.48 ohm/kM
150 mtrs.

= 2I

SN 2

R LL1000

R'b=Rrelay+Rlead

for 2.5 sq. mm CU. Cable

=
=

2.844 Ohm
2.844 VA @ Isn=1A

4.644 VA @ Isn=1A

Checking of CT adequacy

K'SCC K td

ISCC
I PN

= 0.5 X 40000 / 800

25.00 with Ktd as 0.5 as per Siemens


Manual for Ipn = 800A

K'SCC K td

ISCC
I PN

= 0.5 X 40000 / 400

50.00 with Ktd as 0.5 as per Siemens


Manual for Ipn = 400A

Selecting class PS for bus bar protection core


Minimum required VK for Ratio 800 / 1A ,RCt=16 Ohms, as per siemens protection manual for 7SS52 relays.

V K Ktd

I SCC ( EXT . FAULT)


1. 3 x I PN

(R CT + R' B ). I SN

397.00 V

Minimum required VK for Ratio 400 / 1A ,RCt=8 Ohms, as per siemens protection manual for 7SS52 relays.

V K Ktd

I SCC ( EXT . FAULT)


1. 3 x I PN

(R CT + R' B ). I SN

486.31 V

Conclusion :With ratio as 800/1 A, class PS, Rct=16 ohm connected to 7SS52 relay requires a minimum Vk as 397.00V, and
With ratio as 400/1 A, class PS Rct=8 ohm connected to 7SS52 relay requires a minimum Vk as 486.31V, However
selected Knee point voltage of CT is 40 ( Rct + 7) i.e. For 800/1A Vk = 920V & for 400/1 Vk = 600V. Hence selected
Knee point voltage is adequate.

Page:

(4)-G71000-V0022-D001

Date:10.01.08

B 220kV Point of supply Breaker


B-1-1

Core 1 - OC & EF Protection with relay 7SJ62

Fault current Iscc =

40000

Core-1 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6
B-1-2

800
1
NA
PS

CT Sec.resistance (Ohms) - Rct

Core-1
400
1
NA
PS

200
1
NA
PS

NA

NA

NA

16

Burden at secondary side of core-1 for protection

Rrelay

8 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

0.05 VA

For 7SJ6 relays as per SIEMENS Relay manual

Cable Resi. (RC)


Length of cable from CT to relay (L)
CT lead burden in two way (RLead)

9.48 ohm/kM
150 mtrs.

= 2I

SN 2

for 2.5 sq. mm CU. Cable

R LL1000

Connected resistive burden


R'b=Rrelay+Rlead
B-1-3
Checking of CT adequacy

=
=

2.844 Ohm
2.844 VA @ Isn=1A

2.894 VA @ Isn=1A

Accordingly required resistive burden R'b=2.894VA.


As per Siemens Manual the minimum required symetrical short circuit current factor (K'ssc) shall be at least 20
Minimum required Vk as per siemens protection manual

VK

K'ssc
(R CT R'B ).ISN =
1.3

290.68 V

for Ipn 800A

VK

K'ssc
(R CT R'B ).ISN =
1.3

167.60 V

for Ipn 400A

VK

K'ssc
(R CT R'B ).ISN =
1.3

106.06

for Ipn 200A

Conclusion
With ratio as 800/1 A, class PS, Rct=16 ohm connected to 7SJ relay requires a minimum Vk as 290.68V , and with
ratio as 400/1 A, class PS, Rct=8 ohm connected to 7SJ relay requires a minimum Vk as 167.60,with ratio as 200/1
A, class PS, Rct=4 ohm connected to 7SJ relay requires a minimum Vk as 106.06V However selected Knee point
voltage of CT is 30 ( Rct +36) i.e. For 800/1A Vk = 1560V & for 400/1 Vk = 1320V, for 200/1 A Vk = 1200V. Hence
selected Knee point voltage is adequate.

B-2-1

Page:

(4)-G71000-V0022-D001

Date:10.01.08

Core-2 Spare

Core-2 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6

800
1
NA
PS

CT Sec.resistance (Ohms) - Rct

Core-2
400
1
NA
PS

200
1
NA
PS

NA

NA

NA

16

Knee Point Voltage Selected Vk = 30(Rct +36)


B-3-1

Core-3 TOD Metering

Core-3 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6
B-3-2

800
1
20
0.2

CT Sec.resistance (Ohms) - Rct

Core-3
400
1
20
0.2

200
1
20
0.2

NA

NA

NA

16

Burden at secondary side of core-3 for metering.

Equipment
TOD
Analog Amm. 3 Nos.
Total

Burden in VA
0.2
4.5
4.7

CT lead burden in two way (Rlead) =

Connected resistive burden

2.844 Ohm
2.844 VA @ Isn= 1 A
R'b=Rm+Rlead

(As calculated in B-1-2)

7.544

VA @ Isn= 1 A

Conclusion
As calculated from above , the required VA burden is 7.544 VA , Hence selected ratio of 800-400-200/1 A with class
0.2 & 20 VA burden is adequate.
B-4-1

Core-4 Spare

Core-4 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6

9 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

CT Sec.resistance (Ohms) - Rct

Knee Point Voltage Selected Vk = 40(Rct + 7)

800
1
NA
PS

Core-4
400
1
NA
PS

200
1
NA
PS

NA

NA

NA

16

B-5-1

Page:

(4)-G71000-V0022-D001

Date:10.01.08

Core 5 - Bus Bar Protection with relay 7SS52

Core-5 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6

Core-5
400
1
NA
PS

800
1
NA
PS

CT Sec.resistance (Ohms) - Rct

200
1
NA
PS

NA

NA

NA

16

Note :- Please refer CT sizing calculation A-5 & C-5


C 220kV Line To Transformer Bay
C-1-1

Core 1 - Transformer differential Protection

Transformer rating =

50

MVA

Voltage Ratio =

220/22

KV

Percentage Imp =

13.25

Fault MVA =
(3 Ph Short Circuit)

419.287212 MVA

Fault Current Iscc =


at 220 KV side

1100.37584 A

V K K td
Ktd =

I SCC
1 . 3 x I PN
4

( R ct + R ' b ). I SN

for Transformer as per Siemens catalog

Core-1 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6
C-1-2
Rrelay

10 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

Core-1
150
1
NA
PS
NA

CT Secondary resistance(Ohms)- Rct

Burden on secondary side of Core 1 For 7UT613 Relay


0.1 VA

Cable Resistance (Rc)


Length of cable from CT to relay (L)

for 7UT612 Relay


9.48 ohm/kM
150 mtrs.

for 2.5 sq. mm CU. Cable

11 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

Page:

(4)-G71000-V0022-D001

Date:10.01.08

CT lead burden in two way (RL)

2 I SN Rc L 1000

Connected resistive burden

R'b=Rrelay+Rlead

=
=

2.844 Ohm
2.844 VA @ Isn=1A

2.944 VA @ Isn=1A

89.02 V

Accordingly Required resistive burden R'b=3.844 VA


C-1-3

Selecting PS Class core for 150/ 1A Ratio

Minimum required Vk as per 7UT612 protection manual

VK K td

I SCC (EXT. FAULT)


1.3 x I PN

(R CT R' B ).I SN

for Ipn 150A

Conclusion
With ratio as 150/1 A, class PS, Rct=1 ohm connected to 7UT613 relay requires a minimum Vk as 89.02V .
However selected Knee point voltage of CT is 500V. Hence selected Knee point voltage is adequate.
C-2-1

Core2- OC & EF Protection with relay 7SJ62

Maximum Fault current Issc =

40000 A

Core-2 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6
C-2-2
Rrelay

Core-2
150
1
15
5P
20

CT Secondary resistance (Ohms)-Rct

Burden at secondary side of core-2 for protection


0.05 VA

For 7SJ62 relays as per SIEMENS Relay manual

Cable Resi. (RC)


Length of cable from CT to relay (L)

9.48 ohm/kM
150 mtrs.

CT lead burden in two way (RLead)

= 2I

Connected resistive burden

R'b=Rrelay+Rlead

SN 2

R LL1000

for 2.5 sq. mm CU. Cable

=
=

2.844 Ohm
2.844 VA @ Isn=1A

2.894 VA @ Isn=1A

C-2-3

12 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

Page:

(4)-G71000-V0022-D001

Date:10.01.08

Checking of CT adequacy

Accordingly required resistive burden R'b=2.894VA. However , Selected resitive burden = 15 VA


As per Siemens Manual the minimum required symetrical short circuit current factor (K'ssc) shall be at least 20
Minimum required Vk as per siemens protection manual

VK

K'ssc
(R CT R'B ).ISN =
1.3

59.91 V

for Ipn 150A

246.15 V

for Ipn 150A

Vk of CTs for rated class 5P20, 15VA

V K=

K SCC ( R B + RCT ). I SN
1 .3

Conclusion
With ratio as 200/1 A, class 5P20, 15VA, Rct=1 ohm connected to 7SJ62 relay requires a minimum Vk as 59.91V &
the CT's Vk is 246.15 Volts. Hence adequate.

C-3-1

Core-3 Metering Purpose

Core-3 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6
C-3-2

Core-3
150
1
30
0.2
NA

CT Sec.resistance (Ohms) - Rct

Burden at secondary side of core-2 for metering.

Equipment
MFM
Analog Amm. 3 Nos.
Total

Burden in VA
0.2
4.5
4.7

CT lead burden in two way (Rlead) =

Connected resistive burden

2.844 Ohm
2.844 VA @ Isn= 1 A
R'b=Rm+Rlead

(As calculated in B-1-2)

7.544

VA @ Isn= 1 A

Conclusion
As calculated from above , the required VA burden is 7.544 VA , Hence selected ratio of 150/1 A with class 0.2 &
30 VA burden is adequate.

C-4-1

Page:

(4)-G71000-V0022-D001

Date:10.01.08

Core-4 MSETCL SCADA.

Core-4 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6

C-5-1

Core-4
150
1
30
0.2
NA

CT Sec.resistance (Ohms) - Rct

Core 5 - Bus Bar Protection with relay 7SS52

Fault current Issc =

40000 A

Core-5 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
Accuracy Limit factor - KSSC
5
6
C-5-2
Rrelay

800
1
NA
PS

CT Sec. resistance (Ohms) - Rct

Core-5
400
1
NA
PS

200
1
NA
PS

NA

NA

NA

16

Burden at secondary side of core-5 for Busbar protection


1.8 VA

For 7SS52 relays

Cable Resistance. (Rc)


Length of cable from CT to relay (L)

CT lead burden in two way (RLead)

Connected resistive burden


C-5-3

13 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

9.48 ohm/kM
150 mtrs.

= 2I

SN 2

R LL1000

R'b=Rrelay+Rlead

for 2.5 sq. mm CU. Cable

=
=

2.844 Ohm
2.844 VA @ Isn=1A

4.644 VA @ Isn=1A

Checking of CT adequacy

K'SCC K td

ISCC
I PN

= 0.5 X 40000 / 800

25.00 with Ktd as 0.5 as per Siemens


Manual for Ipn = 800A

K'SCC K td

ISCC
I PN

= 0.5 X 40000 / 400

50.00 with Ktd as 0.5 as per Siemens


Manual for Ipn = 400A

14 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

Page:

(4)-G71000-V0022-D001

Date:10.01.08

Selecting class PS for bus bar protection core


Minimum required Vk for Ratio 800 / 1A ,Rct=16 Ohms, as per siemens protection manual for 7SS52 relays.

V K Ktd

I SCC ( EXT . FAULT)


1. 3 x I PN

(R CT + R' B ). I SN

397.00 V

Minimum required Vk for Ratio 400 / 1A ,Rct=8 Ohms, as per siemens protection manual for 7SS52 relays.

V K Ktd

I SCC ( EXT . FAULT)


1. 3 x I PN

(R CT + R' B ). I SN

486.31 V

Conclusion :With ratio as 800/1 A, class PS, Rct=16 ohm connected to 7SS52 relay requires a minimum Vk as 397.00V, and
with ratio as 400/1 A, class PS Rct=8 ohm connected to 7SS52 relay requires a minimum Vk as 486.31V, However
selected Knee point voltage of CT is 40 ( Rct + 7) i.e. For 800/1A Vk = 920V & for 400/1 Vk = 600V. Hence selected
Knee point voltage is adequate.