Section Two

General Technical Information

INSTALLATION METHODS (CONT.)


Figure 2.2 Minimum Spacings in Air to Avoid Derating
Method of Installation
a) Single Core Cables
Cables spaced away from
surfaces and supported on
ladders, racks, etc. or
suspended from a catenary
wire, such that impedance to air
flow around the cables is not
greater than 10%.
Cables spaced away from
surfaces and supported on
perforated or unperforated trays
such that air flow around the
cables is partially restricted.
Cables fixed directly to a wall,
floor, ceiling or similar surface
such that air circulation is
restricted.

Horizontal Spacings

Vertical Spacings

D
4D

4D

2D

4D

2D

2D

6D

6D

2D

b) Multicore Cables
Cables spaced away from
surfaces and supported on
ladders, racks, etc. or
suspended from a catenary
wire, such that impedance to air
flow around the cables is not
greater than 10%.

0.5D

4D
2D

4D

Cables spaced away from


surfaces and supported on
perforated or unperforated trays
such that air flow around the
cables is partially restricted.
Cables fixed directly to a wall,
floor, ceiling or similar surface
such that air circulation is
restricted.

2D
4D

2D
6D

Note: Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under
Copyright Licence 000926. Please see the Standards for full details.