4.13 Monitoring Functions 4.13 Monitoring Functions Measured Current symmetry Quantities (for each side) — BAL. FAKT. | = BAL. | LIMIT Phase rotation *) Secondary values based on | Trip Circuit Number of supervised trip circuits Supervision 7UT612 Manual c53000-G1176-c14e-4 Operation of each trip circuit Und! Umax] < BAL. FAKT. iflmax/ I> BAL. I LINIT/Iy 0.10 to 0:90 (steps 0.01) 0.10 Ato 1.00 A") (steps 0.01 A) ys before I,» before I, (clockwise) or 1, before i, before I» (counter-clockwise) iFM Mall > 0-5 ly ‘A they must be multiplied by 5 1 with 1 binary input or with 2 binary inputs 279 4 Technical Data 414 An lary Functions Operational Measured Values (Operational measured values of currents 14; 112 Ika ‘-phase for each side = Tolerance at ly = 1 Aor5 A. = Tolerance at Iy = 0.1 A in A primary and secondary and % of Iwobj 1% of measured value or 1 % of ly 2.% of measured value or 2 % of In, Operational measured values of currents 3lp; ly; Ip ‘S-phase for each side ~ Tolerance Operational measured values of currents ‘phase for each feeder ~ Tolerance Operational measured values of currents for high-sensitivity input ~ Tolerance Phase angles of currents ‘S-phase for each side ~ Tolerance Phase angles of currents ‘-phase for each feeder ~ Tolerance Operational measured values of frequency ~ Range = Tolerance Operational measured values of power with applied or nominal voltage Operational measured values for thermal value Operational measured values (Temperature acc. IEC 60354) Measured values of differential protection ~ Tolerance (with preset values) Measured values of restricted earth fault protection ~ Tolerance (with preset values) in A primary and secondary and % of Iwobj 2.% of measured value or 2 % of ly 1; to Fy in A primary and secondary and % of Iwobj 2 % of measured value or 2 % of ly Ig in A primary and mA secondary 1% of measured value or 2 mA. (lis); (li2); @(lis) in ® referred to @(l-1) 1° at rated current (1.1) to @(I7) in® referred to @(lL4) 1° at rated current f in Hz and % of fy 10 Hz to 75 Hz 1% within range fy10 % at 1 = ly S (apparent power) in kVA; MVA; GVA primary O11; 2; O13; Ores referred to tripping temperature rise ©,,p ©pro1 t0 Opror2 in°C or °F relative aging rate, load reserve love Ls: lbirL2i loiFFLsi Irestuti Iresti2i IRestLa in % of operational rated current 2% of meas. value or 2 % of Iy, (50/60 Hz) 3.% of meas. value or 3 % of ly (162/3 Hz) loiter! IRastREF in % of operational rated current 2.% of meas. value or 2 % of Ij (50/60 Hz) 3.% of meas. value or 3 % of ly (162/3 Hz) Fault Event Storage of the messages Data Log of the last 8 faults, with a total of max. 200 messages 280 TUTG12 Manual ‘es2000-61176-C148-1 4.14 Ancillary Functions Fault Recording Number of stored fault records Storage period (start with pickup or trip) Sampling rate at fy = 50 Hz Sampling rate at fy = 60 Hz Sampling rate at fy = 164/3 Hz max. 8 max. 5's for each fault ‘approx. 5 s in total 1.67 ms 1.83 ms Sms Statistics Number of trip events caused by 7uTe12 Total of interrupted currents caused by 7UT612 Operating hours criterion segregated for each pole and each side Up to 7 decimal digits Excess of current threshold (Breaker $1 I>orBreaker $2 I>) Real Time Clock and Buffer Battery Resolution for operational messages Resolution for fault messages Buffer battery 1ms 1ms 3.VI1 Ah, type CR 1/2 AA Self-discharging time approx. 10 years Time ‘Synchronization Operation modes: Internal IEC 60870-5103, Time signal IRIG B Time signal DCF77 Time signal synchro-box Pulse via binary input Internal via RTC External via system interface (IEC 60870-5103) External via IRIG B External, via time signal DCF77 External, via synchro-box External with pulse via binary input User-configurable Functions (CFC) Processing times for function blocks: Block, Basic requirements STICKS Beginning with the 3rd additional input for ‘generic blocks per input Logic function with input margin Logical function with output margin In addition to each chart 1TIcK 6 TICKS 7 TICKS 1 TICK Maximum number of TICKS in sequence levels: WW/_BEARB (processing of meas. values) 1200 TICKS. PLE1_BEARB (slow PLC processing) PLC_BEARB (fast PLC processing) ‘SFS_BEARB (Switchgear interlocking) 255 TICKS 90 TICKS 1000 TICKS, 7UT612 Manual c53000-G1176-c14e-4 281 4.15 Dimensions Housing for Panel Flush Mounting or Cubicle Installation fe ‘es2000-61176-C148-1 Housing for Panel Surface Mounting a a oi Cy a be eens Figure 414 Dimensions 7U7612or panel sutace mounting Thermobox go27 : che ds ——H ign] eo. 29] ae ier Srapeon tearing Figure 4-15 Dimensions Thermobox 7XVS862~*AD10-0000 7UT612 Manual c53000-G1176-c14e-1 ouning i 2m 283 4 Technical Data 284 TUTG12 Manual ‘es2000-61176-C148-1 Appendix 7UT612 Manual c53000-G1176-c14e-4 A This appendix is primarily a reference for the experienced user. This Chapter provides ordering information for the models of 7UT612. General diagrams indicating the termi- nal connections of the 7UT612 models are included. Connection examples show the proper connections of the device to primary equipment in typical power system con- figurations. Tables with all settings and all information available in a 7UT612 equipped with all options are provided. (A1___ Ordering Information and Accessories 286 A2___ General Diagrams 291 A3___ Connection Examples 293 [Ad __ Assignment of the Protection Functions to Protected Objects 304 AS Preset Configurations 305 ‘AG _ Protocol Dependent Functions 307 AT Listof Settings 308 AB __ List of Information 323 AQ __ Listof Measured Values 340 285 A Appendix A.1— Ordering Information and Accessories Differential Protection Rated Current Wat ye8A ‘Auxiliary Voltage (Power Supply, Pick-up Threshold of Binary Inputs) DC 24,V to 48, binary input threshold 17'V 2) DC 60 V'to 125 V'), binary input threshold 17 V2) DC 110V 19250 V *), AC 115 ta 230 V, binary input threshold 73 V2) Housing / Number of n- and Outputs BE: Binary Inputs, BO: Binary Outputs Surface mounting housing with woe terminals, "/ x 19, 3B 4 BO, 1 tte contac, Flush meunting housing with plug-in terinas, )« 17,3, 4 80,1 He contact, Flush meuning housing with Screwed terminals,» 1°. 3B, 4 80,1 ie contact 7uTe12-]- -[TJA0 Region-Specific Default / Language Settings and Function Versions FRogion GE, 50160 Hz, 16 %s Hz language German (language can be changed) FRgion world, 50160 Hz, 16 Hz, language Engish, language can be changed) Region US, 60I50 He, language US-English (language can be changed) Region world, 0160 Hz, 16a He, language Spanish (language can be changed) mom> ‘System Interface: Functionality and Hardware (Port 5) No system interface IEC Protocol electrical RS222 IEC Protocol, electrical RS425 IEC Protocol, optical 820 nm, ST-plug Profs FMS Slave, elacrcal RS485 Profous FMS Slave, optical, singling, ST-connector Profs FMS Slave, optical, doubleng, ST-connector For further interfaces see adiional specication L ‘Additional Specification L Proftus OP Slave, R485 Proftus DP Slave, optical 820 nm, doubl Modbus, R48 Modus, optical 820 nm, ST-connector NP, RS485 DDNP. optical 820 nm, ST-connector ing, ST-connector DDIGSI/ Modem Interface Thermobox (Port C) No DIGS! interface on the rear sida DIGSI/ Modem, electrical RSZI2 DIGS! / Modem Thermabox, electrical RSABS DDIGSI/ Modem /Thermobox, optical 820 nm, ST-connector +) with plug-in jumpar one of2 voltage ranges can be selected 2 foreach binary input one of2 pickup threshold ranges can be selected with plugin jumpers 286 see page AS TUTG12 Manual ‘es2000-61176-C148-1 A.1 Ordering Information and Accessories roret2(]-CLT1L1-f1)a0 Fanetionaty Measured Values Basic messed vos 1 ‘ A Basic measured values, ransformer manag functions {connection to tharmonox het spot, overoad factor Differential Protection + Basie Functions Differential protection for transformer. gonerator, motor. busbar (87) Overload protection according to IEC fart winding (49) Leck out (86) ‘Time overcurrent protection phases (50151): >>, ip (inush stabilization) ‘Time overcurrent protection B10 (S0NIIN) ai, algS>-4i0p linruah stablteation) ‘Time overcurrent protection earth (0061516): TES, IE>>, Teg (ivush stabilzavor) Differential Protection + Basic Functions + Additional Functions: 8 Restricted earth fault protection, lw impedance (876) festcted earth fault protecion, high impedance (876 without resistor and vatiston, O/C 1-phase Tip creat supervision (7410) Unbalanced load protacion (46) Breaker fare pretecton (SOB) High-senstvtyme overcurent protection / tank leakage protection (64), OIC t-phase Ordering example: 7UT6121~AEAGI-1AAO *LOA, Differential protection here: pos. 11 = 9 porting at LOA, ie. version with Profibus.interface DP Slave, RS485 7UT612 Manual 287 c53000-G1176-c14e-4 A Appendix A1.1 Accessories Thermobox Matching / ‘Summation Transformer Interface Modules Terminal Block Covering Caps Short-Circuit Links 288 For up to 6 temperature measuring points (at most 2 devices can be connected to 7UT612) Name Order No, ‘Thermabox, Un = 24 16 60V AGIDG TXVS652-2AD10 “Thermabox, Uy = 80 t0 240 VAGIOG 7XVS662-5ADTO For single-phase busbar connection Name ‘Order No, Matching / summation transformer iy = 1A “GANS120-SDA00-OANZ Matching / summation transformer ly = 5A “4AMS120-4DA00-OAN2 Exchange interface modules Name ‘Order No RSza2 C58207-ASS1-DOATA S485 (C53207-A51-DB42—1 Optical 820 nm (053207-A351-DB4S-1 Profibus FMS RS4@5 (©53207-A351-D603-1 Profibus FMS double ring (©53207-A351-D606—1 Profibus FMS single ing (©53207-A351-D609-1 Profibus DP RS485 (C53207-ASS1-DEIT-1 Profibus DP double ring (©53207-A351-DBTS-1 Modbus RS485 (053207-A351-DE2T1 Modbus 620 nm (©53207-A351-DE23-1 DNP 5.0 RS485 (C58207-ASS1-DEST-1 DNP 3.0 620m (©53207-A351-DESS-1 Covering cap for terminal Block type ‘Order No, 18 terminal voltage block, 12 terminal current block C7S334AT-C3T-1 12 terminal voltage block, 8 terminal current block C7333 A1-C32-1 ‘Shor circuit links for purpose / terminal type ‘Order No, Voltage block, 18 terminal, 12 terminal CTSSSE ATC ‘Current block, 12 terminal, 8 terminal C7334 A1-C33-1 7UT612 Manual ‘es2000-61176-C148-1

You might also like