Sample Setting Calculation for REF Protection (MCAG Relay)

Substation

: 220 kV GSS HISSAR

Transformer Name : BHEL


Relay Name : MCAG, EE

Calculation:
Transformer Name: BHEL
MVA = 100
Voltage Ratio = 220/132
Rated Voltage in kV (HV Side) = 220
Rated Voltage in kV (LV Side) = 132
Vector Group = YNA0d1
% Impedance of the transformer=0.1132
Relay Operating Current

= 0.2A

Magnetizing Current of the Ref (Ct) = 60mA


Knee Point Voltage of the Ref (Ct) = 1000 V
Relay Burden

= 1VA

CT Ratio (HV Side) = 500/1


CT Ratio (Neutral Side) = 500/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 500/1
CT LV Side Vector Group = Star/Star
CT resistance (Rct) =5
Lead Resistance value=2.5
Rated Current (HV Side) = MVA / (3*kV)
=100*10^6/ (3*220*10^3)
=262.43 A

Maximum fault current contributed =Rated current /Percentage Impedance


=262.43/0.1132
=2318.286A
Maximum fault current contributed secondary=2318.286/500
= 4.636 A

I Operating Current

=If *(Irelay Operating +n*Imag)


= 4.636 /1000 (0.2 /1000+4*60)
=1.112 mA

Operating Voltage Vs

= If*(Rct+2*Rl)
=4.636*(5+2*2.5)

Vs

=46.36V

=Vs/I operating R burden/Ioparating2

R stable

=(46.36/0.2)-(1/0.22)
R stab =206.8

Stability Check

Stable If 2*Vs<Knee point Voltage

2*46.36<1000

Relay setting is stable.


Setting is in order.