System Voltage in kV
Transformer % Impedance
HV Side CT - primary in Amps
HV Side CT - secondary in Amps
LV Side CT - primary in Amps
LV Side CT - secondary in Amps
HV Side Voltage
LV side Voltage
OLTC Range
Vector Group
Rated current of the Transformer HV side in Amps
Rated current of the Transformer at HV Side in
Secondary, Iref
Amplitude matching factor of HV side
Rated current of the Transformer LV side in Amps
Rated current of the Transformer at Sec. Side in
Secondary, Iref
Amplitude matching factor of LV side
The Recommended seting
Idiff>
Idiff>>
m1
m2
The base value for m2
The stability check is performed for the following
cases
1.The 20 MVA Transformer is fully loaded at
-7.5% tap
2.The20 MVA Transformer is fully loaded at
+7.5% tap
3. The 20 MVA Transformer through fault stability
at -7.5% tap & +7.5% tap.
1
REF PROTECTION
CT References for LV REF Protection:
Transformer Capacity in MVA
Transformer % Impedance
LV Phase side CT reference- primary
LV Phase side CT reference- secondary
LV Neutral side CT reference- primary
LV Neutral side CT reference- secondary
LV Side Voltage reference in kV
REF Settings:
Maximum Fault Current in Amps
Equivalent Fault Current in Sec. in Amps
Maximum Earth fault current in Amps (As per
Grounding Resistor rating)
Vp
20
33/6.9
10
1000
1
2500
1
33
6.9
7.50%
Dyn11
350
0.35
2.8571428571
1673.5
0.6694
1.493875112
0.2
8
0.25
0.5
2.5
20
0.3782913714
0.378
1.079946
1673.5
0.6694
1.0041
0.075846
1.042023
0.3884
200
3.4991951851 3499.2 A
3.4992
9.9972144
16.7352813201 16735.2A
6.69408
9.9741792
3.2550652885 3255A
3.255
9.299535
0.675
9.6365
20
10
2000
1
2000
1
6.9
16.7352813201 16735.2A
8.3676
400
10% of maximum
earth fault current
40
0.02
8
sqmm copper cable with a resistance of 7.81 Ohms/km.
79.93832
Vs/Is
3996.916