Sub:- Earthing conditions at your site Dear sir, This is with reference to your complaint .. . On thorough checking we have found out that the site conditions in your branch is not proper. We would like to bring to your notice that such a situation can damage the hardware gravely and hinder the smooth functioning of the branch. Hence we request you to take immediate action on this. And also noted, any damage occurred due to improper earthing conditions at the site is chargeable. For your kind information we are listing out the desired site conditions as well as the current site conditions prevailing. Desired 230 +/- 5 V 0 to 3 V 230 +/- 5 V Open Clean and moisture free Existing

Phase to Neutral Neutral to Earth Phase to Earth Continuity between Earth and Neutral Cleanliness of site

Expecting appropriate action from your side. This will help us in rendering good services to you at all times.

With good wishes, (Customer Engineer) CC to:- RO / HO / ZO Computer Cell