1 . Introduction
(B) To check the adequacy of the grating for live load of personnel as 5 kN/m
LME drawing # EN-1563-101 Dt. 01.12.10 - " Plan Layout for Grating ".
Reference codes::
3D- View
Analysis and Design of the grating has been done using Staad Pro as per BS5950 code.
Proposed Grating is Lionweld grating as below made of 30 x 3 thk flats at pitch 30x100.
362816975.xls
900
1300
30
Consider Ladder load = 1 kN/m being exerted on the platform respective member.
Load combinations:
1.0DL+1.0LL
consider this UDL full on the grating span 8.34 x 1.3 = 11 kN/m
900
Deflection check :
362816975.xls
max deflection = 5 WL4 / 384 E I I=67x3x303/12=0.45x106mm4
= 1.03 mm
Fx = 6 kN
Fy = 78 kN
Fz = 1 kN
Refer HILTI chemical anchor bolt catalogue :: HVU adhesive with HAS rod.
Tensile capacity: ( for 20 dia bolts) Refer catalogue:
NRd,c = NoRd,c.fB,N.fT.fA,N.fR,N NoRd,c.= 52.4 kN
fB,N. = 1.16 for C40 grade concrete
\ NRd,c = 52.4 * 1.16 * 1.0 * 0.68 * 1.0 fT.= 1.0 full recommended anchor depth
= 41.3 kN > actual tension in bolt fA,N.= 0.68 for 120 mm spacing
fR,N = 1.0 no edge distance influence
Hence safe (egde distance > 180 mm)
End plate :
max moment in end plate = 2 x 6.25 x 0.05 = 0.62kNm
Moment capacity of end plate per unit width = py.tp/4 ..cl.6.3.4.3, BS5950-1:2000
\Moment capacity of end plate = py.b.tp/4
= 275 x 152 x 20 /4 = 4.18 kNm > actual moment in end plate
hence safe
Hence provided 4no. M20 chemical HILTI anchor bolts/rod and the end plate are safe.
362816975.xls
3.3 Bolted connection between main member UC 152x152x23 to secondary members CH 125x65x15.
4. Conclusion :
The proposed grating made of 30 x 3 thk flat at pitch 30 mm c/c and the support system
is structurally safe.