System Psychrometrics for CORRIDOR 3

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:55AM

June DESIGN COOLING DAY, 1700

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 44.6 0.02061 0 400 0 0
Vent - Return Mixing Outlet 25.5 0.01009 2288 6162 - -
Central Cooling Coil Outlet 13.1 0.00873 2288 6162 34140 9099
Supply Fan Outlet 13.2 0.00873 2288 6162 212 -
Cold Supply Duct Outlet 13.3 0.00873 2265 6162 - -
Zone Air - 21.6 0.01010 2265 6165 22736 9098
Return Plenum Outlet 25.6 0.01010 2265 6165 10961 -
Duct Leakage Air Outlet 13.2 0.00873 23 6162 - -
Return Duct Outlet 25.5 0.01009 2288 6162 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.3 W/(L/s)
Site Altitude = 14.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 23141 Cooling 22736 21.6 2265 6165 0 0

Hourly Analysis Program v4.50 Page 1 of 2


System Psychrometrics for CORRIDOR 3
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:55AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 12.0 0.00682 0 400 0 0
Vent - Return Mixing Outlet 18.2 0.01112 2288 800 - -
Central Cooling Coil Outlet 18.2 0.01112 2288 800 0 0
Supply Fan Outlet 18.3 0.01112 2288 800 212 -
Cold Supply Duct Outlet 18.3 0.01112 2265 800 - -
Zone Air - 18.2 0.01112 2265 800 -136 0
Return Plenum Outlet 18.2 0.01112 2265 800 0 -
Duct Leakage Air Outlet 18.3 0.01112 23 800 - -
Return Duct Outlet 18.2 0.01112 2288 800 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.3 W/(L/s)
Site Altitude = 14.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 -2108 Deadband -136 18.2 2265 800 0 0

Hourly Analysis Program v4.50 Page 2 of 2