Professional Documents
Culture Documents
Hướng Dẫn Sử Dụng Bộ Lưu Điện Online Santak
Hướng Dẫn Sử Dụng Bộ Lưu Điện Online Santak
Khi chy ch in li th Led 10 (ch th c quy) v Led 7 (ch th Bypass) tt. Led 7 ch xut hin
khi UPS chy ch in li b li hoc lc mi khi ng ln s chuyn qua trc khi chuyn sang
ch Inverter.
Trng hp nu cm in li vo m khng bt On UPS ln, Led 8, Led 6 (5,4,3,2) s sng ln, Led 9
tt, tc l lc ny UPS cha hot ng ch Inverter v ng ra UPS cha c in, ch c in sc
cho c quy.
Khi UPS ang chy in li v cha bt On ln
Khi UPS chy ch c quy (tc l UPS mt in li
hoc khng cm in li vo UPS) v bt UPS On ln
Panel hin th khi UPS chy ch c quy
Led 3,4,5,6 cng sng mu xanh: dung lng c quy trn 96%
Led 3,4,5 cng sng mu xanh: dung lng c quy 75 95%
Led 3,4 cng sng mu xanh: dung lng c quy 55 74%
Led 3 sng mu xanh: dung lng c quy 35 54%
Ch cn Led 2 sng mu vng: dung lng c quy nh hn 35% v lc ny UPS sp tt do dung
lng c quy cn li t
Trn y l 02 ch hot ng ca UPS Santak dng Online C1K 20KVA, y l nhng trng thi
hot ng bnh thng, tuy nhin trong qu trnh s dng c lc bn s gp trng hp UPS b li, do
chng s bo trng thi nh sau:
Khi UPS li c quy: n bo c quy tc l Led s 10 s nhp nhy lin tc, nn thay c quy mi
Khi UPS li bo mch: Led 1 (mu ) s sng ln km theo cc Led 2,34,5,6 (mu xanh) cng sng.
Lc ny s c tn hiu ci ku lin tc v UPS s chuyn qua chy qua ch Bypass.
Vi cc UPS Santak Online dng C1KE, C2KE, C3KE, C1KR, C2KR, C3KR, C6KR cng hin th trn
Panel tng t nh cch b tr Led khc nhau.
Trng thi hin th trn dng UPS Santak C2KE, C3KE Lc cm in m cha On UPS
Trng thi hin th trn dng UPS Santak C2KE, C3KE Lc cm in vo v bt On l
Trng thi hin th trn dng UPS Santak C2KE, C3KE khi chy ch c quy