You are on page 1of 20

List

1 Characteristics 1
2 Stipulation



1
3 Technical Data 2
4 Structure and installation 3
4.1 outside drawing 3
4.2 inside construction drawing 4
4.3 installation dimension drawing 6
4.4 external wiring requirement 6
4.5 external terminal layout drawing 6
5 From installation to operation 7
6 Basic functions 7
6.1 start up 7
6.2 register external device 7
6.3 fire alarm 8
6.4 monitoring information 9
6.5 associate operation information 9
6.6 fault alarm


9
6.6.1 main power supply fault 9
6.6.2 back-up power supply fault 9
7 Menu operation function 9
7.1 device information 10
7.2 register information 11
7.3 event record 12
7.4 adjust time 12
7.5 associated setup 12
7.5.1or1 logic setup 13
7.5.2or2 logic setup 13
7.5.3and logic setup



13
7.5.4 pulse mode module 14
7.6 system setup 14
7.7 exit 14
8 System self-check



15
9 Lock key/Unlock 15
10 Automatic/Manual switch 15
11 Associated control 16
12 Repair and Maintenance 16
13 Notice 17
14 Our service 17
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Hello
Welcome to Brightsky WorldConnecting newest technology 5iserise fire alarm system that will
Exceed your imaginationdirectly and plenty figure interface you will be the first time to feel our
products reliabilityThe speed of fire alarm system is quicker than before, Brightsky Electronic
Co., Ltd quests system reliability and accurately that will be embodied completely.

This customer manual will let you know the super function of this kind of machine step by step.

Characteristics
Graphic menu operation, new design
Black box record function
Detector condition display
250 intelligent bus device points capacity
Alarm address information second-conversion accurate locating fire addresscan input in the
form of pre-programming at desk computer or laptop
All fire protection linkage operation relationship on-site programming
Standard 485 interface, LAN network and remote communication function

Our Stipulations
In below descriptions

all display letter or icon is buttonFor example this is Down button this

is Reset button.
Bus equipments which are including heat detectors, smoke detectors, manual call points,
signal input module etc fire alarm touching equipments and Long-range control module etc
Linkage control equipments.
According to habit or descriptions requirementsIt will be possible to useDetectorletter
can take place smoke detector, heat detector, manual call point, signal input module etc fire
alarm touching equipments
In the system, from No.001 to No.250, it is standard device address (detector, remote control
module, etc), from No.251 to No.256, it is six multi-line control modules.

Wuxi Brightsky Electronic Co., Ltd


1
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Technical Data


Main Power AC 220V (+10%~-15%) 50HZ
Back-up power supply DC 24V2.3AHbuilt in
Work consumption Monitor state2.4WAlarm state10W
Basic monitoring capacity 5i series addressable device 250 pieces
Direct external control contact 6 pairs
Polling cycle 10 secondwhen Condition abnormity, single point
continues to poll
Signal transportation distance 1500 meters.
Wiring method 1 5i series detectors2-wire bus, non-polarity
2 5i series modules2-wire bus, polarityT+anode
T-cathode
Wire application RVS-21.5mm2 two color plastic soft wire.
Outside control touch points KA1KA2 first time alarm, then closed immediately.
YA1YA2 first time alarm under nobody controlled machine
delay 2 minutes closed.
Outside control touch points capacity DC 30V2A.
Operation Environment Temperature 0~55
Relatively humidity 95%
External dimension 44034082HWTmm3
Installation form Wall mounted type
Weight About12Kg
Black box record data Be able to save 500 recordsincluding open, close, alarm, fault
and linkage information
Linkage programming amount 150 itemsor one, or two, with logic 50 items
Room number conversion capacity 250 pieces
Room number conversion 30 pieces English characters
maximum allowable characters
numbers

2
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Wuxi Brightsky Electronic Co., Ltd


5
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Fire alarm controller should be installed in a room or place where can be controlled by manat the
same time please install fire alarm controller on the wall. Normally fire alarm controllers bottom
is far away from the ground 1.5 metersIt will leave more than 0.5 meter distance in two sides. So
that it will be easy operate and maintenance.

This is installation dimension drawing

6
JB-QB-5Si fire alarm control panel (associate operation type) operation manual
MeanwhileAccording to position array figures, in order to check whether wiring
is right or notEach of hardware whether is solid or not.
4 Start up.
5 According to fire code and project linkage operation relationship requirement,
edit linkage operation relationship list based on linkage operation
programmingsection.
6 Re open the panel, according to register external device section, register
external devices.

Basic functions
Start
First time start please press control panel buttonMeanwhile please press main/ reserved
power switchAfter controller initialized, indicator and sounder check itselfThen all devices of
bus are loadingat the moment let loose It takes about 2 minutes. Then system comes to
normally monitor and control statePower of indicate in controller flashes. AttentionEach time
restart system linkage is manually stateat the moment automatic/manually indicator
always flashes.


Fire Alarm Panel
: 010011
2004/10/23 10:28
:

Register outside devices


Register outside devices include to register detectors, modules etc connect with bus devices in the
return circuit. Register operating, after start the controllerPress controller power switchwhen
controller panel indicator flashes. Press registerafter finish to register, then indicate to have
registered bus devices number and address code. Press or You can check the details
listingPress return to monitor and control state.

004
register :device
026
008: 026
:

Fire alarm
Under normally monitor and control state, the controller patrols registered each
of detectorsmonitor each of detectors current smoke consistency or temperature
valuethen using the data to calculate and recognize by formula. Using the data
according to formula calculate and recognize. If it is be fit for fire alarm
conditionit can be put into fire alarm state. At the momentthe controller sounds

8
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

the alarmthe controller panels fire alarm indicator flashesthe displayer


indicates alarm address, number etc informationprinterwhen you install this
printercan print alarm address, alarm timeMeanwhile the outside controller
position KA1KA2 closedYA1YA2 begin to delayIf nobody controls controller
reduce sounder or reducethis position closed. If linkage position is in the
automatic statethe controller is according to be the first time addressable linkage
logic relation which can set out command in order to start corresponding long-range
control moduleso that start or close outside devices.For example fire pump
System uses different pages approach among fire alarm, linkage and default
information If there are two or many kinds of alarm information exist at the same
time Please press or switch to another fire alarm type page,
Press or you can check the up or down information.
Therein
fire alarm page displays fire detector, manual call point, etc alarm information
monitoring page displays feedback signal from signal input module and remote control
module.
Linkage operation page displays activation signal of remote control module.
All fault information is displayed in fault page besides power supply and back-up
power supply fault information.

Fire:03 Associate:01

Fault:01 Monitor:02 004
* * * * * *
Fire
01/03 002 : 026
smoke detector
: 026
2004/10/23 10:26
:
Memo:room1

In above figure
Fire:03express there are three fire alarm signals for the time being.
Fault:01express there is one fault signal for the time being.
Associate:01express there is one linkage operation for the time being.
Monitor:02express there are two monitoring feedback for the time being.
Fire 01/03 002shows that it is first page of fire alarm page. Alarm number is
No.002 device.
smoke detectorexpress No.002 is one smoke detector
2004/10/23 10:26express it is the alarm time.
memo:room1express this detector is installed in room1.
Fire alarm display will not disappear by itself. We should use manually reset to
disarm detector alarm condition, then the page will come back to front page.

Monitoring information
All information from signal input module alarm information and remote control
modules feedback information will be displayed in this page. This page displayed
information format is almost same as in fire alarmsection. So it is not shown

Wuxi Brightsky Electronic Co., Ltd


9
JB-QB-5Si fire alarm control panel (associate operation type) operation manual
once again here. After the monitoring signal disappears, the relevant display will
also disappear, which is one important different point from fire alarm display.

Associate operation information


Remote control module activated information is shown here. This page displayed
information format is almost same as the one in fire alarm section. So we do
not repeat it here. After the module is closed, the display will disappear.

Fault Alarm
In order to ensure fire alarm control system can be longer normally runningThe
controller must monitor circuit, detector, long-range control module etc bus
equipment and power, accumulator etc devicesthat means there are alarm and default
function. When there has default and alarmIt will set out default alarm sound
the indicator will flash in the controller the monitor displays default type
If detectors or long-range control module defaultThe printerwhen you set up this
printerprint default address, alarm timethe monitor will display alarm address,
number etc information. At the momentthe operator should obviate the default
After obviated default ,the controller can reduce automaticallychange to normally
Alarm state. This page displayed information format is almost same s the one in fire
alarm section. So we do not repeat it here.

Main power fault


Main Power fault is AC 220V Power voltage is not lower than 187VIncluding no
electricthe controller indicates main power abortMain power abort indicator
flashes. At the momentthe controller must have reserved powerotherwise, the
controller is due to no electric so that the controller stops working.

Back-up power supply fault


Reserved power abort tat means reserved power in the controller is lower than
19.2V,reserved power opened wire, reserved power is no chargethe controller
indicates reserved power abortreserved power abort indicator flashes.

Menu operation function


Under monitor stateaccording to menu button display input password:

Menu password

10
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

After inputted password is correct, enter main menu, otherwise, be back to monitor
state.
There are seven menu options in main menuthese include Device information
Register information Event record
Adjust time Associated setup System
setupExit

Main
Menu


Device information

According to or press to your need informationAccording to enter


function listing.

Device information
Device information function is look at each devices detailed information,
which include registered analogue value, current analogue value (smoke value and
temperature value), device type, status (whether isolated or not) and remark
information.

Device No. : 001



Base Value : 028 004
Current Value: 028/003

Type: smoke : 026
detector
Status: normal
: 026
Memo: room1
:

Device No. :001express current querying No.001 device


Base Value: 028express this device registered value is 028
Current Value: 028/003express this device current smoke value 028heat value
is 003
Type: smoke detectorexpress this device type is smoke detector
Status: normalexpress this device currently works normally. If in isolated,it
expresses this device has been isolated and it cannot alarm
Memo:room1 express this devices annotation, that is to say, this devices installation
location is in room1
Push down or plus one or minus one to change current device number
Push down or plus ten or minus ten to change current device number
Push down (self-test) to change device condition;
Push down (silence) to return;
Push down menu key (middle key in below small box) and one sub-menu will appear.
This sub-menu has three itemsedit memo copy memoreturn

Wuxi Brightsky Electronic Co., Ltd


11
JB-QB-5Si fire alarm control panel (associate operation type) operation manual


1:edit memo
004
2:copy memo
: 026
0:return
: 026
:

push down corresponding digital key to enter relevant function

Edit Memois one text edition interface. Its function mainly is input device
installation location, that is remark, in order to show its accurate alarm lication.

Memo edit No.001


Hello world
000
ABC 001 012
,

push down (self-test) switch input method


push down (silence) delete current cursor location character
push down menu key( middle key in below small box) to store modification and return

Copy Memo is copy current device remark to other device

Copy No.001 to
1 00

: 001020
From: 002 to 006

: 120123

push down (self-test)to start copy


push down (silence) to return

Register information
Register information function is check registered external device numbers

Device Total:120
:100
001 002 003 004 005
006
001 007
002 008
003 009
004 010
005
011 012 013 014 015
006
016
007
017
008
018
009
019
010
020
011
021 012
022 013
023 014
024 015
025

Press or check details listingPress return main menu

Event Record

12
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Event Record is query historic alarm records, which include: FireFault


MonitorAssociatePower-OnPower-OffResetAC FaultDC Fault Manual Status
Auto Status, etc.

Event Record Total:500 406


001
001 017
manual status
2002/02/24 10:32:20
Time:2004/10/23 10:28
002
002 fire 005
Type:smoke detector
2002/02/24
Time:2004/10/22 10:20:10
10:28

The latest record will be first shown.


Push down or to query above or next record. Push down (silence) to
return main menu.
Push down 1 to print(when ancillary device is installed) events record.

Adjust Time
Adjust Time is set up date and time in the system

Time
Adjust

2002/04/22 10:53:21
2004/10/22

Push down or to move cursor


Push down digital key to change time value
Push down (self-test) to store date and time modification and start to use new
date and time.
Push down (silence) to give up modification and directly return main menu.

Associated Setup
Associated Setup is automatic associated/linkage operation after the fire alarm
happens. The control panel will make a judge from alarm information and start or
close relevant devices based on linkage operation programmed logic relationship ( in
manual operation condition, all linkage operation dependency relationship is not
valid). It has five menu items, which include :OR1 Logic SetupOR2 Logic Setup
AND Logic SetupPulse Mode Setupand Exit

Associated operation
1:OR1 Logic setup
2:OR2 Logic setup
3:AND Logic setup
4:pluse mode setup
0:exit

Push down corresponding digital key to enter relevant function.

OR1 Logic Setup


Wuxi Brightsky Electronic Co., Ltd
13
JB-QB-5Si fire alarm control panel (associate operation type) operation manual
OR1 Logic Setup: if any one detector in one detectors group alarms, it will
initiate or close corresponding device.

OR1 logic setup 000


1 00
Activate source:
:From: 001020
001 to 003
Activate object:
:
From: 120123
011 to 012

now we use above chart example to explain all data meaning in OR1 Logic Setup
programming. That is: set up any one detector (from No.001 to No.003) to alarm within
Activate sourcerangeit will activate remote control modules(from No.011 to
No.012) within Activate objectdate range. Top right corner 000express current
one is No.00 item (one item per page).
Push down digital key to edit various data items. Push down or to move
cursorpush down or to edit or query above or next item(page) data. After
the setup is completed, input end item, that is, set up this pages first data
item as 0 Push down (silence) to return associated/linkage operation
programming menu.

OR2 Logic Setup


OR2 Logic Setup: if any two detectors alarm in one detectors group, it will start
or close relevant devices.
Chart example and setup method is referred to OR1 Logic Setup

AND Logic Setup


AND Logic Setup: if any one detector in one group and any one detector in another
group alarm simultaneously, it will start or close relevant devices.

AND logic setup 000


1
Activate source: 00
From: 001 to 003
:From: 001020
006 to 009
Activate object:
: From: 120123
015 to 015

Now we use above chart example to explain various data meaning in AND logic
programming, that is: any one detector (from No.001 to No.003) set up within
Activate source1data item range and any one detector (from No.006 to No.009)
set up within Activate source2 data item range alarm simultaneously, it will
activate the remote control module(from No.015 to No.016) set up in Activate
object data item range. Top right corner 000 express current item is No.00
item(each item per page).
This pages other operation is referred to OR1 Logic Setup section.

Pulse Mode Module

14
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Pulse Mode module expresses remote control module activation is point activated
method, that is, after the module is closed and two seconds delay, it will be broken
up once again.

pluse mode module 000


1 00

: 001020
From: 021 to 023

: 120123

For example, in above figure, the control modules from No.021 to No.023 has been
set up into point activation mode.
This pages other operation is referred to OR1 Logic Setup section.

System Setup
In this sub-menu, you can set up and decide whether the printer need to print the
information on real-time base and the control panel need to monitor main power supply
and back-up power supply, etc.

System setup

real time print > yes
AC monitor : yes
1
DC monitor :
: yes
real time polling : no
2
address code :
: 000
capacity : 000
3
fire repeater :
: 000

Push down or to move cursor to next or above item.


Push down (self-check) to change item status.
Push down digital key to edit item content.
Push down (silence) to store setup and return main menu.
If we set up the printer into non-workable status, the printer will not print out
real-time information when there is fire alarm, fault, associated operation and
monitoring signal input. But this setup will not influent printing operation in
Event Record.

Exit
It expresses to return monitoring condition. In any interface in main menu, you can
directly push down 0 to return monitoring condition.

System self-check
System self-check: check systems display LCD, condition indication LEDs and alarm
sounders. In polling condition, push down (self-check) to enter this function
Wuxi Brightsky Electronic Co., Ltd
15
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Test Sound

during self-check process, all status LEDs in the front face of the panel will flash,
the sounder will send out ambulance car sounder, printer ( if the ancillary device
has been installed) will print out Fire Alarm PanelAfter self-check is completed,
it will return to monitoring condition.

Lock key/Unlock
To avoid non-operators non-proper operation, this control panel has lock key
function. In monitoring condition, push down lock key( fourth key start from left
to right in small box in the panel)button to enter this function.


Keyboard lock

Input lock password. If it is correct, lock key LED will flash. If the key is locked,
it cannot do other operation besides silence and unlock operation. If you want to
unlock the key, please push down lock key button, it will show Keyboard Unlock
in the LCD display interface.

Automatic/Manual switch
If the system is not monitored by the operator, we can set up the fire alarm control
panel into automatic status, that is: when there is fire alarm, the control panel
can open or close relevant external devices based on pre-set associated operation
logic relationship and it does not need manual interference. When we open the fire
alarm control panel, it is in manual condition. In this condition, all associated
logic relationships are not valid. That is, associated device cannot be
automatically closed based on fire alarm. In monitoring condition, push down
manual/automatic switch button (the fourth key from left to right in the small
box of the panel) to enter this function.


Switch to auto status

16
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

The same as lock key operation procedure, input switch password. If it is correct,
the system will be switched from automatic condition to manual condition. Or vice
versa, corresponding manual/automatic LED in the panel will be illuminated in
manual condition.

Associated control
Except that we can use associated logic relationship to active the devices in
automatic condition, we also can use system provided Associate Operate function
to open or close the devices. For example, for some kind of requirement, you want
to some one ventilation fan in third floor, and the remote control module number
is No.008 which controls this ventilation fan, you can do following operation:
In polling condition, push down 1 key to enter associated function
Push down digital key to input remote control module number 008
Other push-key operation will have indication in the LCD.

Associate operate

module No : 008
000
Keysilence open
Keyselfcheck close
,
Keyreset return

Repair and Maintenance


Open the machine and it does not implement self-check function, the panel does
not have any response
please check main power supply and back-up power supply to see whether they are
in normal condition. After check and repair, please open the machine once again.
After the machine is open, LCD display mixed codes(cannot be read)
character library piece or program slice is broken or it is not plugged tightly.
Please change or plug the microprocessor once again and the issue will be solved.
After the machine is open, control panel LEDs and sounder self-check are normal,
but the LCD does not have back light and display
The reason is that LCD contrast degree is too small. Therefore, we cannot see
any display content. Please adjust main boards contrast degree potentiometer
and the issue will be solved.
After the machine is open, LCD always displays system initialization, please wait
This expresses that the serial EEPROM microprocessor is broken, the control
panel always fetch the data. Please change the microprocessor and the issue will
be solved.
The devices cannot be registered
Possible reason is that we set up non-proper device type in the system
Wuxi Brightsky Electronic Co., Ltd
17
JB-QB-5Si fire alarm control panel (associate operation type) operation manual
management. 5i series bus device should be set up into intelligent
condition.
Device registration is not complete
Possible reason is that device address exceeds the system capacity. For example,
if the system capacity is 32 points, then the device address which exceeds 32
points cannot be registered.

Notice
Fire alarm control panel should have good ground connecting protection. In the
control panel, there should be have earth-connecting sign. The earth connection
requirement should follow the stipulation in GBJ116-88 automatic fire alarm
th
system design code 4 section.
Fire alarm control panel is specific fire protection device. The system owner
need to appoint one full-time person to manage and maintain and check its
function on regular time and make written record. If the system is in fault
condition, please ask professional person or contact original manufacturer to
repair it.
When the main power source is cut off and the system uses back-up battery power
source, if the control panel sends out back-up battery power fault alarm signal,
it expresses the back-up battery voltage is too low. In this time, we need to
take other offset measures to avoid battery damage caused by back-up battery
unrestrained discharge.

Our Service
The control panel operator must be trained by our company. For some basic
maintenance work, the persons who have been trained can deal with. But during the
operation, if you meet some abnormal situation which you are not familiar with,
please call us and our technical engineers will make relevant answers for you. Or,
we can dispatch our persons to your site system to make service(based on China
market).
Also you can visit our company website (www.bsky.cn) to understand our company
development and read any document you are interested in.

Special notes
Wuxi Brightsky Electronic Co., Ltd follows continuous development strategy. So we
keep the rights to modify our current product ranges and technical specification
which does not need to inform our customers in advance.

18
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

This operation manual copy right belongs to Wuxi Brightsky Electronic Co., Ltd

Wuxi Brightsky Electronic Co., Ltd


19