STATE INVESTMENT PROGRAMME MANAGEMENT & COMMENTS REPLY SHEET (CRS)-CLIENT Page 1 of 2

IMPLEMENTATION UNIT (SIPMIU), URBAN DEVELOPMENT &


POVERTY ALLEVIATION DEPARTMENT, GOVERNMENT OF
MIZORAM

Eco
Owner SIPMIU Project 37MLD WTP - Aizawl Consultant M/s. GKW CONSULT GmbH, Aizawl Protection -
Project Ref
Client Package/
- WTP
Drg/Doc No. Structure
- ECO
ECO
Protection Current
Protection Analysis & Design of Chemical House 2
Doc/Drg Rev No.
Drg/Doc No.
Title

Reply Tracker
Rev No. ECO Protection Reply Reference/Date Client Letter Reference/Date Remarks

0 Submitted on 04.12.2017 Comments received via mail dated 27.02.2018 -

Sl.
SIPMIU/ GKW comments dated 27.02.2018 ECO Protection Reply Dated 01.03.2018
No
1. Please mention the grade of PCC in drawing Noted & incorporated in Sheet 1 of 1, Sheet 1 of 10, Sheet 2 of 10 & Sheet
10 of 10.
2. Please mention the slope of roof
Noted & incorporated in architectural drawing
3. In sheet 2/10, beam in Sec 1-1 should be 400 mm instead of 450 mm
Noted & incorporated in Sheet 2 of 10
4. In sheet 2/10, beam in Sec 2-2 should have top reinf of 2-Y25(T) instead of
Noted & incorporated in Sheet 2 of 10
2-Y20 (T)
5. In sheet 2/10, beam in Sec 8-8 and Sec 7-7 should have stirrup spacing S2
Noted & incorporated in Sheet 2 of 10
instead of S1
6. In beam PB4, PB5, SB3 reinf. of 28ɸ has been used which may not be
Noted & incorporated in both document & drawings
available in the market for such less quantity.

Form: JTP-WTP-01/2
STATE INVESTMENT PROGRAMME MANAGEMENT & COMMENTS REPLY SHEET (CRS)-CLIENT Page 2 of 2
IMPLEMENTATION UNIT (SIPMIU), URBAN DEVELOPMENT &
POVERTY ALLEVIATION DEPARTMENT, GOVERNMENT OF
MIZORAM

Sl.
SIPMIU/ GKW comments dated 27.02.2018 ECO Protection Reply Dated 01.03.2018
No
7. In sheet 3/10, beam in Sec 7-7 should have stirrup spacing S0 instead of S1
Noted & incorporated in Sheet 3 of 10
8. Location of SB2 could not be found
Noted & incorporated in Sheet 3 of 10
9. Sec 16-16 for SB5 is not matching with L.S
Noted & incorporated in Sheet 4 of 10
10. In sheet 8/10, Section 3-3 and section 14-14 are not matching with L.S.
Noted & incorporated in Sheet 8 of 10
11. In sheet 8/10, the location of Section 15-15 could not be found
Noted & incorporated in Sheet 8 of 10

Form: JTP-WTP-01/2