SIEMER Pages: 1 of 2

PRE-COMISSIONING TEST REPORT


TECHNOLOGIES

Client : KRISHNAPANTHAM PORT COMPANY LTD.


Project : 6.6 KV SWITCH GEAR PANEL FOR WAGON LOADING SYSTEM
Location : SILLO
Feeder Detail : PANEL 1-6.6 KV ICOG PANEL
Equipment Details : 1PH POTENTIAL TRANSFORMER
Make : ELECTRICAL CONTROL & SYSTEM
Sr. No. : RAITO Core-1 Core-2
R – 17/429539 : 6.6KV/√3 /110V/√3/110V/√3/110V/3 50VA, CL-0.5 50VA, CL-3P
Y – 17/429540
B – 17/429541

I. Insulation Resistance Measurement: 2.5KV for Prim. & 500V for secondary winding for 60 Sec
R-Ph (G Y-Ph (G B-Ph (G
Secondary - Earth 5.78/3.15 6.9 6.9
Primary – Secondary >100/>100 >100/>100 >100/>100
Between Secondary 20.0 25.1 19.9

II. Winding Resistance


Between R-PH Y-PH B-PH
Core 1 0.3 Ω 0.3 Ω 0.3 Ω
Core 2 0.5 Ω 0.5 Ω 0.5 Ω
Core 3 0.4 Ω 0.4 Ω 0.4 Ω

III. Ratio Test :


Voltages measured at the secondary (Volts)
Voltage applied at Primary (Volts)
Core 1 Core 2 Core 3
Phase ( R-N ) 1980 33.2 33.3 19.1
Phase ( Y-N ) 1980 33.1 33.0 19.2
Phase ( B-N ) 1980 33.0 33.1 19.0

________________________________________________________________________________________

Tested By : Vamish Umar Witnessed by: Witnessed by:

SIEMER Technologies VSE Ltd KPPCL

Date :
SIEMER Pages: 2 of 2
PRE-COMISSIONING TEST REPORT
TECHNOLOGIES

PT found healthy : YES

________________________________________________________________________________________

Tested By : Vamish Umar Witnessed by: Witnessed by:

SIEMER Technologies VSE Ltd KPPCL

Date :