You are on page 1of 2

SMOKE EXTRACT VENTILATION SYSTEM

LG/FLOOR
SMOKE VENT MODE
ROOM REF. ROOMS AREA HEIGHT VOLUME SMOKE EXTRACT MAKE UP AIR
m² m m³ @6AC/HR @6AC/HR
m³/s m³/s
LG/20 Sprinkler Tank Room 61.04 3.395 207.23 0.35 0.35
LG/23 Main Switch Room 43.02 3.395 146.05 0.24 0.24
LG/26 Cold Water Tank Room 32.19 3.395 109.29 0.18 0.18
TOTAL 0.771 0.771
BACKGROUND VENT
Extract Supply
@3AC/HR @3AC/HR
m³/s m³/s
0.17 0.17
0.12 0.12
0.09 0.09
0.385 0.385