Professional Documents
Culture Documents
LENGTH/EQUIVALENT
Air qty. LENGTH
QTY
Si.No DUCT SPECIFICATION DUCT SIZE (CFM) mm feet Nos.
EXTERNAL STATIC PRESSURE
1 Straight 1200 x 1000 24000 850 2.79 1
2 Elbow 1200 x 1000 24000 26.00 1
3 Straight 1200 x 1000 24000 8820 28.96 1
4 Elbow 1200 x 1000 24000 26.00 1
5 Straight 1200 x 1000 24000 21105 69.29 1
6 Elbow 1200 x 1000 24000 26.00 1
7 Straight 1200 x 1000 24000 11995 39.38 1
8 Sound attenuator 1200 x 1000 24000
9 Elbow 1200 x 1000 24000 26.00 1
10 Straight 1200 x 1000 24000 1755 5.76 1
11 Elbow 1200 x 1000 24000 26.00 1
12 Straight 1200 x 1000 24000 370 1.21 1
13 Elbow 1200 x 1000 24000 26.00 1
14 Straight 1200 x 1000 24000 280 0.92 1
15 Fire Damper 1200x1000 24000
16 Straight 1200 x 1000 24000 515 1.69 1
17 Plenum 1500x1300 24000 7150 23.47 1
18 Straight 2050x620 24000 500 1.64 1
34.81
IR DUCT
FRICTION
CONSIDERED/100f TOTAL FRICTION
IN Inch OF WC IN INCH OF WC IN Millimeter OF WC
TIC PRESSURE
0.1 0.003 0.07
0.1 0.026 0.66
0.1 0.029 0.74
0.1 0.026 0.66
0.1 0.069 1.76
0.1 0.026 0.66
0.1 0.039 1.00
10.00
0.1 0.026 0.66
0.1 0.006 0.15
0.1 0.026 0.66
0.1 0.001 0.03
0.1 0.026 0.66
0.1 0.001 0.02
3.00
0.1 0.002 0.04
0.1 0.023 0.60
0.1 0.002 0.04
21.41