The End Cross Girder is designed as beam for service condition spanning between longitudinal girders, The reinforcement
required for the same is calculated and also check for jacking condition for both bending & shear.
Design End Cross Girder for Service Condition:
Effective Span : As per clause 29.1 of IS:456-2000, the effective span will be smaller of the following
l = 2.634 m
D = 1.775 m 1.065
l/D = 1.484 < 2.50 (for continuous beam)
Hence as per Clause 29.1 of IS:456-2000, the End cross girder shall be designed as deep beam.
Lever Arm:
2
Area of steel provided = 2592 mm > 1932 OK
Zone II
It is the zone measuring "0.3 D" on either side of the mid depth of the beam, which shall contain the
remainder of the tension steel evenly distributed.
2
Ast required in Zone II = = 1995 mm
2
Area of steel provided = 2945 mm > 1995 OK
Min. Side face reinf. req 0.01 * 320 * 1695 = 2712 mm2
2
Area of steel provided = 2815 mm
OK
Shear Reinforcement for Service Condition:
2
Max Shear reinforcement = Asw max = 1109.05 mm
OK
Max Long. Spacing = = 600
OK
2
Max Shear reinforcement = Asw max = 831.79 mm
OK
Max Long. Spacing = = 600
OK
Provide 2L-12mm dia stirrups @ 150mm c/c .
Design Intermediate Cross Girder:
The Inner Cross Girder is designed as beam for service condition spanning between longitudinal girders and reinforcement
shall be provided accordingly for service condition.
Design Intermediate Cross Girder for Service Condition:
Summary of Shear Force & Intermediate Bending Moment in Intermediate Cross Girder
Effective Span : As per clause 29.1 of IS:456-2000, the effective span will be smaller of the following
l = 2.900 m
D = 1.875 m
l/D = 1.547 < 2.50 (for continuous beam)
Hence as per Clause 29.1 of IS:456-2000, the Intermediate cross girder shall be designed as deep beam.
Lever Arm:
2
Area of steel provided = 3220 mm > 2526 OK
Zone II
It is the zone measuring "0.3 D" on either side of the mid depth of the beam, which shall contain the
remainder of the tension steel evenly distributed.
2
Ast required in Zone II = = 2299 mm
2
Area of steel provided = 2513 mm > 2299 OK
2 2
Equi.diameter фeq (n1ф1 +n2ф2 )/(n1ф1+n2ф2) = 32.00 mm
Min. Side face reinf. req 0.01 * 220 * 1795 = 1975 mm2
2
Area of steel provided = 2413 mm
OK
Shear Reinforcement for Service Condition:
2
Max Shear reinforcement = Asw max = 623.84 mm
OK
Max Long. Spacing = = 600
Provide 2L-12mm dia stirrups @ 150mm c/c . OK