You are on page 1of 5

STATUS OF SYSTEM INSPECTION AS ON 03.01.

20

Sr. No. Project Name of Work Agency & PO/WO

M/s. KALPATARU POWER TRANSMISSION


LTD
Plot No.- 101, Part-III, G.I.D.C. Estate, Sector-
28,
Supply, erection, Testing and Gandhinagar-328 028,
Commissioning of 220KV D/C Gujrat, India
Transmission Line from Parulia S/s to
1 System Burdwan S/s of DVC in the state of PO No.- DVC/Tender/Head
West Bengal, having approximate Quarter/SPE/CMM/Works and
route length of 94KM Service/00001/552778 dtd, 09.05.18.

W.O. No.- DVC/Tender/ Head


Quarter/SPE/CMM/Works and
Service/00001/552779 dtd, 09.05.2018

2 -Do- -Do- -Do-

Supply of Materials and Structures in M/s. ECI-SEW-JV,


connection with Erection, Testing & 6-3-871, Snehalata,
Commissioning of 220KV D/C, 3 Greenlands Road,
phase proposed GOLA Substation of
3 -Do- Begumpet, Hyderabad-500 016
DVC to Ranchi (400/220 KV sub- PO No.- EDCON/EHV/L-40/1160 dtd,
station of POWER GRID) Line, vide 30.08.2013.
Tender specification No.
EDCON/EHV/L-40.
M/s. GE T&D India Limited,
DLF IT Park, Plot No.- 08,
Project for Renovation & up Major Arterial Road, Block-AF,
gradation of Control & Protection Tower-C, 8th Floor, Rajarhat, New Town,
System and replacement of
Substation equipment of 220/132/33 Kolkata-700 156
4 Trans Composite Order No.- DVC/Tender/Head
KV Ramgarh Substation of Damodar Quarter/SPE/CMM/Works
Valley Corporation (Scheme approved Service/00005/552772 dtd,and
under PSDF) 16.04.2018
INSPECTION AS ON 03.01.2019 (Civil Part)
Status
Insp for Inspection Call

●2mm & 4mm packing plates are not ready.


● DVC vide mail dtd 18.12.18 informed to call for
inspectn of packing plates which were excluded in
last DI-78 dtd, 20.11.2018 & furnish the status of
KP/Raipur/331/DV p/plt in the current offered lot.
●KPTL vide mail dtd, 19.12.18 confirmed that
C/FM/IC-05 dtd, procurement of 2mm & 4mm plt from DVC
Galv. Str Tower 06.12.2018 approved vendors is yet under process and offered
materials- reached QC&I for separate inspection of the p/plts.
509.844MT from SPE vide Dy. ●DVC vide mail dtd, 26.12.18 questioned the
No.- 7 dtd, usability of the material (erection completion)
13.12.2018 without the packing plates & added that as the plts
are integral part of the tower str, it would be
prudent to inspect the whole material at a single
go.
Response from the vendor is yet awaited.

●DVC vide mail dtd, 18.12.18 requested KPTL for


HDG B&N- SEC/BI/KPTL/WO- submission of:
48.674MT for stubs 331/DVC/03 dtd, i) co-related MTC's of raw materials.
& Towers, 9Kg spw 10.12.18 received Ii) manufacturer's internal test certificates
and 138Kg B&N for vide Dy. No. 529 iii) packing list of the offered lot
accessories. dtd, 11.12.18 Response from the vendor is yet awaited.

●After obtaining the approved BOM dtd,


ECI-SEW-
JV/DVC/2018- 08.11.2018 & the MTCs of materials vide letter dtd,
11.12.18, the accessories were inspected & DI
Hardware 19/Counter poise, issued vide No.- 115 dtd, 28.12.18.
accessories & D-shackles, U Bolt ●Due to procurement of ground wire from Non-
earthing materials & Ex. approved vendors DVC vide mail dtd 19.12.18
Link/Inspection advised the vendor to prepare the earthing
call dtd, 07.08.18 materials in line with DVC Technical specification.
DVC/R&M/GE/PM ● DVC vide mail dtd, 18.12.18 raised some
/DC/155 dtd, observations, the clarification regarding which has
Str materials for 11.12.18 & yet not been addressed.
inserts, cable trays DVC/R&M/GE/PM ●GE officials came to DVC's office on 28.12.18. The
etc /PC/160 dtd, observations were noted to them.
17.12.18 Response from the vendor is yet pending.
Annexure for Observation to your submitted documents against letter No.-
DVC/R&M/GE/PM/PC/155 dtd, 11.12.18 & DVC/R&M/GE/PM/PC/160 dtd,
17.12.2018

Reqd Qty
Sr. No. Material MTC Observation
(Kg)

SAIL MTC-303081 dtd, 16.06.18 for


1 6thk Plate 1191.689 Material should conform IS:2062.
cheqd coil (IS:3502)

Parasnath Re-rolling Mills Ltd, TC-


2017/SPRM/HRM & HTSS/03137 dtd, MTC Qty less than reqd qty
31.07.18 for 3.010MT

2 ISA50X50X6 6420.78
Parasnath Re-rolling Mills Ltd, TC-
2017/SPRM/HRM & HTSS/02731 dtd,
12.07.18 for 0.690MT. No co-relation of TC with your vendor,
namely Premier Power Prod.(Cal) (P)
MTC issued to NEHA POWER TECH (I) Ltd, Jangalpur, PO.- Domjur, Howrah-
PVT. LTD, Gate No.-1, 1st Right Lane, 711 411
Jalan Industries, Near NH-6, PO-
Biprannapara, Domjur-711411

3 ISMC125 141.48 -Do-, for Qty-1.02MT -Do-

4 Flat-6thk 227.394 No MTC provided for flat

SAIL TC-267232 dtd, 19.11.17 for


1.255MT issued to NEHA POWER No co-relation of TC with your vendor,
10mm thk TECH (I) PVT. LTD, Gate No.-1, 1st namely Premier Power Prod.(Cal) (P)
5 29.438
Plate Right Lane, Jalan Industries, Near Ltd, Jangalpur, PO.- Domjur, Howrah-
NH-6, PO-Biprannapara, Domjur- 711 411
711411

Parasnath Re-rolling Mills Ltd, TC-


2017/SPRM/HRM & HTSS/02731 dtd, No co-relation of TC with your vendor,
12.07.18 for 1.590MT. namely Premier Power Prod.(Cal) (P)
6 ISMC75 9586.936 MTC issued to NEHA POWER TECH (I) Ltd, Jangalpur, PO.- Domjur, Howrah-
PVT. LTD, Gate No.-1, 1st Right Lane, 711 411 as well TC qty less than reqd
Jalan Industries, Near NH-6, PO- qty
Biprannapara, Domjur-711411