SPECIAL SPECIFICATION
2. STRUCTURE DESIGN OUTLINE
KETERANGAN UMUM PERSYARATAN KHUSUS
OUTLINE PERENCANAAN STRUKTUR
1-1. BUILDING OUTLINE 3-1. CONCRETE / BETON
2-1. STRUCTURAL FRAME DESIGN
GARIS BESAR BANGUNAN 3-1-1. CONCRETE QUALITY / MUTU BETON
PERENCANAAN RANGKA STRUKTUR
NAME OF PROJECT
TACI (PT. TD AUTOMOTIVE COMPRESSOR INDONESIA) - TRAINING CENTER
NAMA PROYEK G DIRECTION
ARAH MEMANJANG
SPECIAL MOMENT FRAME, CANTILEVER COLUMN R 8 (SMF), 2.5 (CC) THE QUALITY SHALL CONFORM TO SNI 2847 : 2013
CONSTRUCTION
PELAKSANAAN
NEW BUILDING
B DIRECTION
MUTU HARUS MEMENUHI SNI 2847 : 2013
SPECIAL MOMENT FRAME R 8 (SMF)
ARAH MELINTANG
CONSTRUCTION SITE
KAWASAN BEKASI FAJAR INDUSTRIAL ESTATE, BLOCK L3 - BEKASI WEST JAVA
LOKASI
2-2. SEISMIC LOADING / BEBAN GEMPA
BUILDING USE
TRAINING CENTRE 3-1-2. SPECIFIED CONCRETE STRENGTH / SYARAT KEKUATAN BETON
PENGGUNAAN BANGUNAN SHALL CONFORM TO SNI 1726 : 2012
PLACE OF WORK EXECUTION CYLINDER STRENGTH (fc') AIR - DRIED SPECIFIC GRAVITY SLUMP
BASEMENT STOREY SEISMIC CATEGORY IMPORTANCE BASIC SEISMIC ACCELERATION Sds = 0.580 g TEMPAT PENGGUNAAN KUAT TEKAN SILINDER (kg/cm²) BERAT JENIS ( cm )
SRC RC S No. D 1
BANGUNAN BAWAH TANAH KATEGORI GEMPA FACTOR PERCEPATAN GEMPA DASAR Sd1 = 0.360 g GENERAL SLAB ON GRADE
FOUNDATION K-250 2.2 ~ 2.3 12 ± 2
ABOVE GROUND STOREY
SRC RC S
BANGUNAN DI ATAS LANTAI DASAR 2-3. RAIN LOAD / BEBAN HUJAN COLUMN, SLAB, BEAM K-300 2.2 ~ 2.3 12 ± 2
PENTHOUSE STOREY
SRC RC S No. ROOF
BANGUNAN PENTHOUSE
ATAP - kg/m 2
BUILDING AREA
540 m2
LUAS BANGUNAN GUTTER
- kg/m 1 3-2. STRUCTURE MATERIAL / BAHAN STUKTUR
TALANG
TOTAL AREA 3-2-1. REINFORCING BARS / BESI BETON
42.314 m2
LUAS TOTAL 2-4. WIND LOAD / BEBAN ANGIN
USED TYPE MARK PLACE OF USE NOTE
EAVES HEIGHT SNI 1727 : 2013 article 28.4.4
1FL +4.200 mm PILIHAN JENIS TANDA TEMPAT PENGGUNAAN CATATAN
TINGGI ATAP
BASIC WIND SPEED / KECEPATAN ANGIN DASAR -- BJTP 24 Ø PRACTICAL COLUMN & BEAM -
HIGHEST BUILDING POINT
1FL +4.750 mm
TITIK TERTINGGI BANGUNAN BJTS 42 D GENERAL -
VELOCITY PRESSURE / TEKANAN ANGIN DASAR --
EXTENSION
YES NO 3-2-2. STRUCTURAL STEEL / BAJA STRUKTUR
PERLUASAN
MINIMUM PRESSURE ROOF : 38 kg/m2 WALL : 77 kg/m 2
USED TYPE MARK PLACE OF USE NOTE
PILIHAN JENIS TANDA TEMPAT PENGGUNAAN CATATAN
1-2. STRUCTURAL SPECIFICATIONS 2-5. EARTH PRESSURE COEFFICIENT / KOEFISIEN TEKANAN TANAH
SPESIFIKASI STRUKTUR SS 400 H , CT GENERAL -

Ka -- SSC 400 C PURLIN , FURRING STRIP -


ROOF METAL ROOF EXTERIOR WALL
ALC BLOCK t=150, TINTED GLASS
ATAP DINDING LUAR
3-2-3. COLD FORMED STRUCTURE / STRUKTUR BAJA RINGAN
SLAB
RC
INTERIOR WALL
ALC BLOCK t=150, GYPSUM PARTITION 2-6. LOAD / BEBAN ( kg/m² )
PLAT LANTAI DINDING DALAM
USED TYPE MARK PLACE OF USE NOTE
SUB BEAM 1FL SLAB DESIGN PILIHAN JENIS TANDA TEMPAT PENGGUNAAN CATATAN
RC SLAB ON GRADE FLOOR LEVEL AREA SDL LL Lr FLOOR LEVEL AREA SDL LL Lr
BALOK ANAK RENCANA SLAB LANTAI 1
G 550 C,Z LIGHT TRUSS , PURLIN -
GIRDER FOUNDATION ALL
RC PILE FOUNDATION, FOOTING FOUNDATION GF - 500 -
BALOK PONDASI

COLUMN
RC
GROUND WORK
LEAN CONCRETE, COMP. RED SOIL
2F ALL (FUTURE 2F TOILET) 150 (500) 500 - 3-2-3. ANTI RUST PAINT / CAT ANTI KARAT
KOLOM PEKERJAAN TANAH
PARTS OF MEMBERS WHERE RUSTPROOFING SHALL NOT BE APPLIED :
BAGIAN DARI BATANG YG TIDAK BOLEH DICAT ANTI KARAT
1. AREA IN CLOSE CONTAC WITH, OR COVERED WITH CONCRETE.
BAGIAN YG BERHUBUNGAN DAN DICOR DALAM BETON
2. INNER SU1FLACE OF BOX-SHAPED OR TUBULAR MATERIALS.
1-3. SOIL INVESTIGATION BAGIAN DALAM DARI BOX DAN TABUNG

PENYELIDIKAN TANAH 2-7. SPECIAL LOAD / BEBAN KHUSUS 3. FRICTION SU1FLACE OF HIGH STRENGTH BOLT JOINTS.
PERMUKAAN GESEKAN DARI SAMBUNGAN DENGAN BAUT MUTU TINGGI

LOAD TYPE CAPACITY LOAD DETAIL


DATE OF INVESTIGATION : NOVEMBER 2013 TIPE BEBAN KAPASITAS DETAIL BEBAN
3-3. PAINTING SPECIFICATION / SPESIFIKASI PENGECATAN
INVESTIGATED BY : PT. PONDASI KISOCON RAYA -- -- -- PLACE OF WORK EXECUTION SU1FLACE PREPARATION PAINT COATING THICKNESS PAINTING METHOD
TEMPAT PENGGUNAAN PERSIAPAN PERMUKAAN CAT TEBAL LAPISAN CARA MENGECAT
NUMBER OF BORING : TOTAL 25 BORING
-- -- --
GWL (GROUND WATER LEVEL) : GL-0.90 INDOOR / COVERED AREA WIRE BRUSH RED LEAD PRIMER, ZINC ( 35 µ ) AIRLESS SPRAY / HAND PAINTING
-- -- -- CHROMATE OR EQUIVALENT

-- -- --
N-VALUE

0 10 20 30 40 50 2-8. SOIL BEARING CAPACITY / DAYA DUKUNG TANAH ( T / m² )


0 3-4. JOINTS / SAMBUNGAN
LOCATION FOUNDATION TYPE FOUNDATION DEPTH BEARING CAPACITY NOTE
REINFORCING BARS STEEL FRAME
TEMPAT JENIS PONDASI KEDALAMAN PONDASI DAYA DUKUNG CATATAN
5 BESI BETON KERANGKA BAJA
GENERAL FOOTING GL - 1.000 7 -
USED SITE JOINT SECTION SHOP JOINT SECTION SITE JOINT
10 PILIHAN SAMBUNGAN LAPANGAN PILIHAN SAMBUNGAN PABRIK PILIHAN SAMBUNGAN LAPANGAN

GAS PRESSURE JOINT WELDING WELDING


SAMBUNGAN GAS TEKAN LAS LAS
15
LAPPED JOINT HIGH TENSION BOLT HIGH TENSION BOLT
2-9. PILE CAPACITY / DAYA DUKUNG PILE SAMBUNGAN LEWATAN BAUT MUTU TINGGI BAUT MUTU TINGGI
20
WELDING MILD BOLT MILD BOLT
SIZE PILE LENGTH DEPTH OF PILE TIP ( * ) PILE CAPACITY LAS BAUT BIASA BAUT BIASA
DEPTH
25 UKURAN PANJANG PILE KEDALAMAN UJUNG TIANG DAYA DUKUNG PILE NOTE : BUTT WELDING SHOULD BE VERIFIED WITH UT TEST 100%
KEDALAMAN CLASSIFICATION
( ton ) ALL WELDING SHOULD BE COMPLY WITH AWS STANDARD
mm m GL- m
30 3-5. BOLT / BAUT
CIRCULAR PILE Ø 300 8 ~ 10 ~ 40
USED MARK TYPE PLACE OF USED JOINT SU1FLACE PREPARATION
35 PILIHAN TANDA JENIS TEMPAT PENGGUNAAN PERSIAPAN PERMUKAAN SAMBUNGAN

S10T, A490 HIGH STRENGTH BOLT GIRDER , TRUSS SAND BLAST


40
F8T, A325 HIGH STRENGTH BOLT SUB TRUS, SUB BEAM SAND BLAST
45
SS400 MILD BOLT PURLIN, FURING STRIP, ANCHOR BOLT

50
BH-10
( * ) MAY VARY DEPEND ON ACTUAL SITE CONDITION.
DAPAT BERUBAH SESUAI KEADAAN TANAH 3-6. SPECIAL ATTENTION IN EXECUTION OF WORK
NEED APPROVAL FROM STRUCTURE ENGINEER ALL CONSTRUCTION SHOULD BE PE1FLORMED BY TAKENAKA INDONESIA CONSTRUCTION PROCESS CONTROL

CATATAN
NOTE : IF THERE ARE HARD LENSES, PILE DRIVING SHALL BE PRECEDED WITH PREDRILLING

DATE DATE DATE DATE STATUS DATE DRAWN APPROVED PROJECT TITLE TACI (PT. TD AUTOMOTIVE COMPRESSOR INDONESIA) PROJECT NO. DRAWING NO.
11-06-2019 T. YUKI T.SADAMOTO TRAINING CENTER A-XXX
REVISION PROPOSAL DATE ISSUED PROJECT LEADER SUB DRAWN DRAWING TITLE - SCALE : 1 : 500 (a1) REVISION NO. S-0A
1 : 1.000 (a3)
21-06-2019 Ir. EKA W RIDWAN ST. wYn STRUCTURAL DESIGN OUTLINE R-0