You are on page 1of 16

HORING LIH

BATTERY DISABLE TELEPHONE


DELAY AUX-1 AUX-2
FIRE FAULT
CALL POINT AUX-3 AUX-4
VOLTAMETER

Fire Alarm Control Panel


H N L

5-QA12
OUTPUT DELAY BELL BUZZER TEST BAT. TSET RESET

ZONE LED

ZONE NAME

QA12 / 5-QA12
ZONE SW

TEL.

Operating Manual
AC POWER ALARM DELAY AUX-1 FAULT

FIRE POWER HIGH CALL POINT AUX-2 AC FAU

QA12
POWER LOW TELEPHONE AUX-3 BATTERY FA

BATTERY DISABLE AUX-4 PCB FA

BUZZER RELAY TEST AUTO RES

SOUNDER DELAY BAT. TEST RESET


TEL.

HORING LIH INDUSTRIAL CO., LTD


2011 Ver.1
www.horinglih.com
CONTENTS
QA12 / 5-QA12

CONTENTS :

QA 12 System Characteristics ................................................................................................ 1

QA 12 Indicators and Switches Description ..................................................................... 2

QA 12 Wiring Diagram Description .................................................................................... 5

QA 12 Location of Fuse .............................................................................................................. 6

5-QA 12 Indicators and Switches Description ................................................................. 7

5-QA 12 Wiring Diagram Description .................................................................................10

5-QA 12 Location of Fuse ........................................................................................................ 11

Trouble Shooting ........................................................................................................................ 12

Housing Specifications and Main Specifications ........................................................... 13


QA12 System Characteristics
QA12

QA12 System Characteristics :

Alarm verification up to 7 seconds for real fire confirmation and avoid false alarm
from environment interference.

Zone test mode to perform alarm and fault functional test.

Each zone has a separate disable function.

Fault indications for wire disconnection, unstable AC power, battery short circuit
or disconnection and internal PCB unplug.

QA12 could up to 80 zones, 5-QA12 ups to 5 zones.

1
QA12 Indicators and Switches Description
QA12

QA12 Indicators and Switches Description :

1
2 3 4

37
5 9 13 17

6 10 14 18

QA12 7 11 15 19

8 12 16 20

38
21 22 25 26 29 30 33 34

23 24 27 28 31 32 35 36

1 Zone Label 10 Call Point LED 22 Buzzer switch 31 Battery Test LED
2 Zone Fire Indicator 11 Telephone LED 23 Sounder LED 32 Battery Test switch
3 Zone Fault Indicator 12 Disable LED 24 Sounder switch 33 Auto Reset LED
4 Zone switch 13 14 15 16 Aux1~4 LED 25 Relay LED 34 Auto Reset switch
5 AC Power LED 17 Fault LED 26 Relay switch 35 Reset LED
6 Power High LED 18 AC Fault LED 27 Delay LED 36 Reset switch
7 Power Low LED 19 Battery Fault LED 28 Delay switch 37 FIRE indicator
8 Battery LED 20 PCB Fault LED 29 Test LED 38 Telephone jack
9 Alarm Delay LED 21 Buzzer LED 30 Test switch

2
QA12 Indicators and Switches Description
QA12

QA12 Indicator and Switches Description :


1 Zone Label : To show the name of covered area.
2 Zone Fire Indicator : Steady light ON means Fire status, flash light ON means
Disable status.
3 Zone Fault Indicator : Light ON means that circuit has trouble.
4 Zone switch : 1. To disable zone output function when Fire is detected.
2. To perform Zone Fire Test and Zone Fault Test.
5 AC Power LED : Light ON means panel working voltage is normal.
6 Power High LED : Light ON means panel working voltage is 10% higher than the
nominal voltage. Meantime the Fault LED will light ON and panel
buzzer will sound.
7 Power Low LED : Light ON means panel working voltage is 10% lower than the
nominal voltage. Meantime the Fault LED will light ON and panel
buzzer will sound.
8 Battery LED : Light ON means panel working voltage is supplied by battery only.
Meantime the Fault LED will light ON and panel buzzer will sound.
9 Alarm Delay LED : Light ON means panel is reconfirming the alarm signal from
detector, LED light will OFF after 7 seconds confirmation.
The panel will activate Fire condition if signal is confirmed.
10 Call Point LED : When panel receives signal from manual call point, this LED and
Delay LED will both light ON. Panel will active without delay.
11 Telephone LED : When panel receives incoming call signal, LED will ON and buzzer
will active.
12 Disable LED : Indicates any zone output is disabled.
13 14 15 16 Aux1~4 LED : When panel receives external monitoring signal, LED will ON and
buzzer will active.
17 Fault LED : When loop has short, open or terminal trouble, LED will light ON and
flash.
18 AC Fault LED : A yellow light indicates the a break in the AC power supply.
19 Battery Fault LED : A yellow light indicates short circuit or wire-break in the Panel‘s
battery wires.
20 PCB Fault LED : A yellow light indicates a circuit board has become disconnected.
21 Buzzer LED : 1. (temporary silence – LED steady ON)
22 Buzzer switch : When press switch once, LED ON and disable the sounder
output, any new incoming fire or fault signal will enable the
buzzer and LED will OFF.
2. (long silence – LED flash)
When press switch twice, LED flash and disable the buzzer
output, any new incoming fire or fault signal will not enable the
buzzer .
3. (normal)
When press switch three times, panel will back to normal status.
23 Sounder LED : 1. (silence)
24 Sounder switch : When press switch once, LED ON and disable the sounder
output.

3
QA12 Indicators and Switches Description
QA12

2. (normal)
When press switch twice, panel will back to normal status.
25 Relay LED : LED ON indicates relay output from panel is disabled.
26 Relay switch : Pressing this switch will disable the fire and fault relay output.
27 Delay LED : LED ON indicates the alarm delay feature is disabled.
28 Delay switch : Pressing this switch will disable any alarm delay.
29 Test LED : 1. (fault test- LED flash)
30 Test switch : When panel is under manual test mode, press the switch twice to lit the
LED and into Zone Fault test, press each zone switch to show the fault
indication and related output.
2. (fire test- LED steady ON)
When panel is under manual test mode, press the switch once to light
the LED into Zone fire test. Press each Zone switch, both Zone Fire
Indicator and Alarm Delay LED will be lit on 7 seconds and then the
Reset LED flashed 5 seconds. Following press each Zone switch again
to show the fire indication and related output.
3. (normal)
When press the switch three times, panel will back to normal status.
**Note: Any Fire happen during test period, system will automatically
into [Fire mode].
31 Battery Test LED : LED ON indicates panel is under battery test status.
32 Battery Test switch : Pressing this switch to test the back-up battery.
33 Auto Reset LED : LED ON indicates it is under auto reset mode, this feature is for one
man walk test.
34 Auto Reset switch : Pressing this switch will display auto reset mode.
35 Reset LED : LED ON indicates it is under reset mode.
36 Reset switch : Pressing this switch resets the panel, LED lights ON for 5 seconds and
then returns to normal status.
37 FIRE indicator : When the panel has received a fire signal, the LED will light ON and flash.
38 Telephone Jack

1 2 3

1 Zone PCB Connect Fault : LED ON indicates Zone module is disconnect.


2 Ground Fault : LED ON indicates terminal is short to ground.
3 AUX Fault : LED ON indicates the 06112-9A load output is fault.

4
QA12 Wiring Diagram Description
QA12

Zone Module Zone Output Module

COM 10kΩ COM


To Output Device
ZONE 1 N.C.
E1
ZONE 2 N.O.
Zone Output
ZONE 3 N.C.
E2 To Output Device
N.O.

ZONE 10

Power Module -
+ P
-
Indicator LAMP AH-0217
+
or
-
Sounder SND
+ Lc
A
L P
Load Output -
AUX AH-9717
(Non-resettable) +

Load Output RES -


(Resettable) AUX +

Transmitting A

- TL
Phone Contact TEL To Phone device
+ TC

COM

Fault Output FAULT N.C. To Output device


N.O.

COM

Alarm Output FIRE N.C. To Output device


N.O.

COM
Dry Contact
U1

Aux. Output

Dry Contact
X2

5
QA12 Location of Fuse
QA12

06112-9A Terminal Board

Load Power (RES AUX)


F4 F1 F3 F2
Load Power (AUX)
Sounder
Indicating Lamp

06112-2C Power Board


F5

OFF
ON

SW2

Battery Power

06112-5C Relay Output Board

F1

DC Power

06212-4A AC Power Board

F1
FUSE

AC Power

OFF
ON

6
5-QA12 Indicators and Switches Description
5-QA12

5-QA12 Indicators and Switches Description :

4 BATTERY 7 DISABLE 8 TELEPHONE


1 2
5 DELAY 9 AUX-1 10 AUX-2
FIRE FAULT
6 CALL POINT11 AUX-3 12 AUX-4
13 14 15 16 17 18 19
3
H N L

5-Q A12
OUTPUT DELAY BELL BUZZER TEST BAT. TEST RESET
21 ZONE LED

22 ZONE NAME
20

23 ZONE SW
TEL

1 FIRE Indicator 8 Telephone LED 17 Test switch

2 FAULT Indicator 9 18 Battery Test switch


10 11 12 Aux-1~4 LED
3 Voltameter Indicator 19 Reset switch
13 Output switch
4 Battery LED 20 Telephone jack
14 Delay switch
5 Delay LED 21 ZONE LED

6 Call point LED 15 Bell switch 22 ZONE NAME

7 Disable LED 16 Buzzer switch 23 ZONE switch

7
5-QA12 Indicators and Switches Description
5-QA12
5-QA12 Indicators and Switches Description :

1 FIRE Indicator : When the panel has received a fire signal, LED lights ON and flash.
2 FAULT Indicator : When loop has short, open or terminal trouble, LED will light ON
and flash.
3 Voltameter Indicator : When the working voltage is too high or too low, the H or L
will light ON. Meantime, the FAULT LED will ON and buzzer will
active.
4 Battery LED : When working voltage is supplied only by battery, the LED will light ON.
5 Delay LED : Light ON means panel is reconfirming the alarm signal from detector, LED
light will OFF after 7 seconds confirmation. The panel will activate Fire
condition if signal is confirmed.
6 Call Point LED : When panel receives signal from manual call point, this LED and
Delay LED will both light ON. Panel will active without delay.
7 Disable LED : Indicates any zone output is disabled.
8 Telephone LED : When panel receives incoming call signal, LED will ON and buzzer
will active.
9 10 11 12 Aux-1~4 LED : When panel receives external monitoring signal, LED will ON and
buzzer will active.
13 Output switch : LED ON indicates relay output from panel is disabled.
14 Delay switch : LED ON indicates the alarm delay feature is disabled.
15 Bell switch : 1. (temporary silence – LED steady ON)
When press switch once, LED ON and disable the sounder output, any
new incoming fire or fault signal will enable the sounder output and
LED will OFF.
2. (long silence – LED flash)
When press switch twice, LED flash and disable the sounder output,
any new incoming fire or fault signal will not enable the sounder
output .
3. (normal)
When press switch three times, panel will back to normal status.
16 Buzzer switch : 1. (temporary silence – LED steady ON)
When press switch once, LED ON and disable the buzzer output,
any new incoming fire or fault signal will enable the buzzer and
LED will OFF.
2. (long silence – LED flash)
When press switch twice, LED flash and disable the buzzer output,
any new incoming fire or fault signal will not enable the buzzer .
3. (normal)
When press switch three times, panel will back to normal status.
17 Test switch : 1. (fault test- LED flash)
When panel is under manual test mode, press the switch twice to lit
the LED and into Zone Fault test, press each zone switch to show the
fault indication and related output.

8
5-QA12 Indicators and Switches Description
5-QA12

2. (fire test- LED steady ON)


When panel is under manual test mode, press the switch once to
light the LED into Zone fire test. Press each Zone switch, both Zone
Fire Indicator and Alarm Delay LED will be lit on 7 seconds and then
the Reset LED flashed 5 seconds. Following press each Zone switch
again to show the fire indication and related output.
3. (normal)
When press the switch three times, panel will back to normal status.
**Note: Any Fire happen during test period, system will automatically
into [Fire mode].
18 Battery Test switch : LED ON indicates panel is under battery test status.
19 Reset switch : Press switch once, LED will ON for 5 seconds and then back to normal
status.
20 Telephone jack : To communicate with the manual call point ’ s plugged phone.
21 ZONE LED : 1. When LED steady ON indicates zone fault.
2. When LED flash ON indicates that zone alarm output is disabled.
22 ZONE NAME : To show the name of covered area.
23 ZONE switch : 1. To disable zone output when there is an alarm.
2. To perform alarm or fault test during manual test mode.

Note : Dip switch description on PCB no. 06212-1

1
1 2

ON

2
1 2

ON

1 1. Test mode switch:


a. Switch to ’
ON’position is under Manual test mode
b. Switch to ’
1’position is under Auto test mode
2 2. Zone indication switch:
a. Switch to ’
ON’ position is under Auto revert mode
b. Switch to ’
2’position is under Auto latching mode

9
5-QA12 Wiring Diagram Description
5-QA12

Level 1
LC
10kΩ EOL resistor
L1
L2 -
Zone + P
L3
L4
AH-0217
L5
or
COM
Lc
Aux 1A A
L P
Aux Aux 1B
AH-9717
Aux 2A
Aux 2B

Level 2

Manual call point PUSH A

AL EC1
To output device
AL EA1
Alarm Output
AL EC2
AL EA2

TC
Phone Contact
TL Telphone

LAMP -
Indicator
LAMP+

Sounder-
Sounder
Sounder+

Relay Output Module


COM
To output device
E1
E2
Relay output E3
To output device
E4
E5
B-

10
5-QA12 Location of Fuse
5-QA12

06212-2C Power Board


F4
+24V
Sounder
F1

F5 OFF
ON

Battery Power

06212-3A Relay Output Board

F1

DC Power

06212-4A AC Power Board

F1
FUSE

AC Power

OFF
ON

11
Trouble Shooting

Trouble Symptom Solution and Suggestion


Zone LED fault The system consists variety devices, any fault or incorrect
use on detector wiring , bell, and manual call point will
affect panel.
a. Use multi-meter measure AC power terminal, normally
you should get 220 V.
b. Check the voltage display whether the Normal LED is
ON.
c. Check fuse whether it is good.
d. Check external facility and wiring is meet requirement.
Fuse function Each fuse used in panel has individual protection function,
it must not be replaced with incorrect specification and
bad quality one. Burnt fuses are probably caused by wiring
error, short circuit or faulty external devices.
AC power fuse burnt Check the input power and fuse if they are comply to the
specification.
Standby power fuse burnt Check the wiring for polarity correctness.
Sounder fault Disconnect the sounder wire, then use multi-meter to
measure the sounder terminal and should read 24 VDC.
If not, please check the external wiring.
Zone fault Most zone fault caused by incorrect wiring.
Zone fault LED ON a. Check the panel if there is any non-connected zone and
EOL resistor.
b. Disconnect the wire of faulty zone and replaced with
10KΩ, the fault signal should disappear.
c. If above steps released fault means the panel is normal,
please check the external wiring before connect back
to panel.
d. Check wiring for open and short condition, detector
head and base is well connected, EOL resistor is well
connected.
e. Use multi-meter to measure the faulty zone
resistance, normally it should read 10KΩ.

Zone Fault LED ON a. Check any voltage existed between L and C after zone
wire is disconnected, normally it should be 0.
b. Check detector if it is normal.
Zone LED and Fire LED ON a. Disconnect the wire of faulty zone and measure the
faulty zone resistance, normally it should read 10KΩ.
b. Disconnect the faulty zone wire and then reset the
panel, replaced by 10KΩ and fix the trouble before
reconnect the wire.

12
Housing Specifications and Main Specifications

Housing Specifications :
W D

AC POWER ALARM DELAY AUX-1 FAULT

FIRE POWER HIGH CALL POINT AUX-2 AC FAULT

QA12
POWER LOW TELEPHONE AUX-3 BATTERY FAULT

BATTERY DISABLE AUX-4 PCB FAULT

TEL.
BUZZER

SOUNDER
RELAY

DELAY
TEST

BAT. TEST
AUTO RESET

RESET
H

Zones Height/mm Width/mm Depth/mm Remark


5-QA12 320 250 100
QA12 10L 450 330 130
20L 550 330 130
30L 680 380 150
40L 950 420 150
50L 950 420 150
60L 1300 420 170
70L 1300 420 170
80L 1300 420 170

Main Specifications :
Description
Power 220 VAC 50/60Hz (Others also available)
Battery Capacity 24 VDC/4A
Charging voltage & current 28 VDC 100mA~400mA
Loop voltage & current 24 VDC; short circuit under 5V
External resistance Max. 50Ω
# of detector connected (Heat) Mechanical – up to design
Electronic – max. 30 per zone (Horing Lih product)
# of detector connected (Smoke) Max. 30 per zone (Horing Lih product)
# of fire indicating lamp connected # of zone x 1.5
# of bell connected # of zone x 1.5
Relay output Contact rating (24 VDC 3A)
End of line resistor 10KΩ (One for each zone)
Housing 1.2 m/m steel plate

13
QA12 / 5-QA12 Fire Alarm Control Panel

2011 VER.001 HORING LIH INDUSTRIAL CO., LTD

You might also like