STRUCTURAL ENGINEERING DIVISION

Test Floor Laboratory


Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Jamani-Shorkot,
Section 2B

Reference # CED/TFL 31935 (Dr. M Rizwan Riaz) Dated: 29-10-2018


Reference of the request letter # RE/M-4/2B/2018/437 Dated: 25-10-2018

Tension Test Report (Page – 1/4)


Date of Test 12-11-2018
Gauge length 2 inches
Description W-Section Steel Strip Tensile and Bend Test
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

------ (cm) (cm2) (kg) (kg) (kg/cm2) (kg/cm2) (in)


1 W-Section 2.36x0.275 0.65 2400 3200 3698.00 4930.66 0.60 30.00
2 W-Section 2.30x0.275 0.63 2500 3200 3952.57 5059.29 0.60 30.00
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
Only Four Samples for Tensile and Four Samples for Bend Test

Bend Test
Strip Taken from W-Section Bend Test Through 180º is Satisfactory
Strip Taken from W-Section Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Jamani-Shorkot,
Section 2B

Reference # CED/TFL 31935 (Dr. M Rizwan Riaz) Dated: 29-10-2018


Reference of the request letter # RE/M-4/2B/2018/440 Dated: 25-10-2018

Tension Test Report (Page – 2/4)


Date of Test 12-11-2018
Gauge length 2 inches
Description W-Section Steel Strip Tensile and Bend Test
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

------ (cm) (cm2) (kg) (kg) (kg/cm2) (kg/cm2) (in)


1 W-Section 2.36x0.275 0.65 2600 3200 4006.16 4930.66 0.60 30.00
2 W-Section 2.30x0.275 0.63 2500 3100 3952.57 4901.19 0.60 30.00
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
Only Four Samples for Tensile and Four Samples for Bend Test

Bend Test
Strip Taken from W-Section Bend Test Through 180º is Satisfactory
Strip Taken from W-Section Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Jamani-Shorkot,
Section 2B

Reference # CED/TFL 31935 (Dr. M Rizwan Riaz) Dated: 29-10-2018


Reference of the request letter # RE/M-4/2B/2018/439 Dated: 25-10-2018

Tension Test Report (Page – 3/4)


Date of Test 12-11-2018
Gauge length 2 inches
Description W-Section Steel Strip Tensile and Bend Test
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

------ (cm) (cm2) (kg) (kg) (kg/cm2) (kg/cm2) (in)


1 W-Section 2.36x0.275 0.65 2400 3000 3698.00 4622.50 0.60 30.00
2 W-Section 2.36x0.275 0.65 2400 3200 3698.00 4930.66 0.60 30.00
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
Only Four Samples for Tensile and Four Samples for Bend Test

Bend Test
Strip Taken from W-Section Bend Test Through 180º is Satisfactory
Strip Taken from W-Section Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Jamani-Shorkot,
Section 2B

Reference # CED/TFL 31935 (Dr. M Rizwan Riaz) Dated: 29-10-2018


Reference of the request letter # RE/M-4/2B/2018/438 Dated: 25-10-2018

Tension Test Report (Page – 4/4)


Date of Test 12-11-2018
Gauge length 2 inches
Description W-Section Steel Strip Tensile and Bend Test
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

------ (cm) (cm2) (kg) (kg) (kg/cm2) (kg/cm2) (in)


1 W-Section 2.10x0.275 0.58 2100 2900 3636.36 5021.65 0.50 25.00
2 W-Section 2.10x0.275 0.58 2200 3000 3809.52 5194.81 0.60 30.00
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
Only Four Samples for Tensile and Four Samples for Bend Test

Bend Test
Strip Taken from W-Section Bend Test Through 180º is Satisfactory
Strip Taken from W-Section Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Jamani-Shorkot,
Section 2B (km 114+800 – 117+500 L/S)

Reference # CED/TFL 31936 (Dr. M Rizwan Riaz) Dated: 29-10-2018


Reference of the request letter # RE/M-4/2B/2018/445 Dated: 29-10-2018

Tension Test Report (Page – 1/4)


Date of Test 12-11-2018
Gauge length 2 inches
Description W-Section Steel Strip Tensile and Bend Test
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

------ (cm) (cm2) (kg) (kg) (kg/cm2) (kg/cm2) (in)


1 W-Section 2.36x0.275 0.65 2600 3200 4006.16 4930.66 0.65 32.50
2 W-Section 2.36x0.275 0.65 2600 3200 4006.16 4930.66 0.60 30.00
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
Only Four Samples for Tensile and Four Samples for Bend Test

Bend Test
Strip Taken from W-Section Bend Test Through 180º is Satisfactory
Strip Taken from W-Section Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Jamani-Shorkot,
Section 2B (km 117+000 – 119+150 R/S)

Reference # CED/TFL 31936 (Dr. M Rizwan Riaz) Dated: 29-10-2018


Reference of the request letter # RE/M-4/2B/2018/444 Dated: 29-10-2018

Tension Test Report (Page – 2/4)


Date of Test 12-11-2018
Gauge length 2 inches
Description W-Section Steel Strip Tensile and Bend Test
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

------ (cm) (cm2) (kg) (kg) (kg/cm2) (kg/cm2) (in)


1 W-Section 2.36x0.275 0.65 2600 3200 4006.16 4930.66 0.65 32.50
2 W-Section 2.36x0.275 0.65 2600 3000 4006.16 4622.50 0.70 35.00
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
Only Four Samples for Tensile and Four Samples for Bend Test

Bend Test
Strip Taken from W-Section Bend Test Through 180º is Satisfactory
Strip Taken from W-Section Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Jamani-Shorkot,
Section 2B (km 117+500 – 119+150 L/S)

Reference # CED/TFL 31936 (Dr. M Rizwan Riaz) Dated: 29-10-2018


Reference of the request letter # RE/M-4/2B/2018/443 Dated: 29-10-2018

Tension Test Report (Page – 3/4)


Date of Test 12-11-2018
Gauge length 2 inches
Description W-Section Steel Strip Tensile and Bend Test
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

------ (cm) (cm2) (kg) (kg) (kg/cm2) (kg/cm2) (in)


1 W-Section 2.30x0.275 0.63 2500 3100 3952.57 4901.19 0.60 30.00
2 W-Section 2.36x0.275 0.65 2600 3200 4006.16 4930.66 0.60 30.00
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
Only Four Samples for Tensile and Four Samples for Bend Test

Bend Test
Strip Taken from W-Section Bend Test Through 180º is Satisfactory
Strip Taken from W-Section Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Jamani-Shorkot,
Section 2B

Reference # CED/TFL 31936 (Dr. M Rizwan Riaz) Dated: 29-10-2018


Reference of the request letter # RE/M-4/2B/2018/441 Dated: 25-10-2018

Tension Test Report (Page – 4/4)


Date of Test 12-11-2018
Gauge length 2 inches
Description W-Section Steel Strip Tensile and Bend Test
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

------ (cm) (cm2) (kg) (kg) (kg/cm2) (kg/cm2) (in)


1 W-Section 2.36x0.275 0.65 2600 3200 4006.16 4930.66 0.60 30.00
2 W-Section 2.36x0.275 0.65 2500 3200 3852.08 4930.66 0.70 35.00
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
Only Four Samples for Tensile and Four Samples for Bend Test

Bend Test
Strip Taken from W-Section Bend Test Through 180º is Satisfactory
Strip Taken from W-Section Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Jamani-Shorkot,
Section 2B

Reference # CED/TFL 31937 (Dr. M Rizwan Riaz) Dated: 29-10-2018


Reference of the request letter # RE/M-4/2B/2018/433 Dated: 25-10-2018

Tension Test Report (Page – 1/1)


Date of Test 12-11-2018
Gauge length 2 inches
Description Plate Steel Strip Tensile Test as per ASTM A36
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

------ (mm) (mm2) (kN) (kN) (MPa) (MPa) (in)


1 Plate 14.20x5.90 83.78 27.00 40.20 322.27 479.83 0.70 35.00
2 Plate 14.20x9.80 139.16 47.00 65.50 337.74 470.68 0.70 35.00
3 Plate 14.40x21.60 311.04 130.00 158.20 417.95 508.62 0.90 45.00
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - - - - - - - - -
Only Three Samples for Tensile Test

Bend Test

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
SMEC International Pty Ltd
Peshawar-Karachi Motorway (PKM) Consultants Sukkur – Multan Section (392 km) (Section-6)
( Honto Industrial (Private) Limited)
Reference # CED/TFL 31954 (Dr. M Rizwan Riaz) Dated: 31-10-2018
Reference of the request letter # 5065057/6/6/375 Dated: 29-10-2018
Tension Test Report (Page – 1/1)
Date of Test 12-11-2018
Gauge length 2 inches
Description G.I Pipe Steel Strip Tensile and Bend Test as per ASTM A53
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

-------- (mm) (mm2) (kg) (kg) (MPa) (MPa) (in)


1 DN65 27.20x4.00 108.80 4000 5000 360.66 450.83 0.40 20.00
2 DN65 27.20x4.00 108.80 4000 5000 360.66 450.83 0.40 20.00
3 DN80 27.20x4.10 111.52 4300 5100 378.26 448.63 0.50 25.00
4 DN80 27.20x4.10 111.52 4600 5100 404.64 448.63 0.60 30.00
5 DN100 27.00x4.00 108.00 4300 4900 390.58 445.08 0.60 30.00
6 DN100 27.00x4.00 108.00 4200 4900 381.50 445.08 0.50 25.00
7 DN150 27.20x4.40 119.68 3700 4800 303.28 393.45 0.50 25.00
8 DN150 26.80x4.40 117.92 4000 4900 332.77 407.64 0.50 25.00
9 DN200 27.00x6.40 172.80 6500 8200 369.01 465.52 0.60 30.00
10 DN200 27.00x6.40 172.80 7000 8300 397.40 471.20 0.60 30.00
11 DN250 27.00x6.30 170.10 7000 8400 403.70 484.44 0.50 25.00
12 DN250 27.00x6.30 170.10 7000 8400 403.70 484.44 0.55 27.50
Only Twelve Samples for Tensile and Six Samples for Bend Test
Bend Test
Strip Taken from G.I Pipe (DN65) Bend Test Through 180º is Satisfactory
Strip Taken from G.I Pipe (DN80) Bend Test Through 180º is Satisfactory
Strip Taken from G.I Pipe (DN100) Bend Test Through 180º is Satisfactory
Strip Taken from G.I Pipe (DN150) Bend Test Through 180º is Satisfactory
Strip Taken from G.I Pipe (DN200) Bend Test Through 180º is Satisfactory
Strip Taken from G.I Pipe (DN250) Bend Test Through 180º is Satisfactory
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Assistant Enginee/Bridges
Pakistan Railways, Multan
Fabrication and Erection of Steel Ground Storeage Tank 750000 Ltr Capacity at Multan
Reference # CED/TFL 31971 (Dr. M Rizwan Riaz) Dated: 06-11-2018
Reference of the request letter # 640-W/1/M Dated: 25-10-2018

Tension Test Report (Page – 1/1)


Date of Test 12-11-2018
Gauge length 2 inches
Description MS Plate & Angle Steel Strip Tensile and Bend Test
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

(mm) (mm) (mm2) (kg) (kg) (MPa) (MPa) (in)

1 MS Plate 610x100x8 27.90x7.75 216.23 7000 9800 317.59 444.62 0.50 25.00

2 MS Plate 610x100x8 27.90x7.75 216.23 7000 9800 317.59 444.62 0.40 20.00

3 MS Plate 610x100x6 28.00x6.00 168.00 5000 7500 291.96 437.95 0.70 35.00

4 MS Plate 610x100x6 28.00x6.00 168.00 5100 7400 297.80 432.11 0.70 35.00

5 MS Plate 610x10x4 28.20x3.90 109.98 4000 5400 356.79 481.67 0.70 35.00

6 MS Plate 610x10x4 28.20x3.90 109.98 4000 5400 356.79 481.67 0.65 32.50

7 MS Angle 915x76/76x9.5 28.00x8.75 245.00 11500 13700 460.47 548.56 0.60 30.00

8 MS Angle 915x76/76x9.5 28.00x8.75 245.00 10400 14000 416.42 560.57 0.60 30.00
Only Eight Samples for Tensile and Four Samples for Bend Test

Bend Test
Strip Taken from MS Plate610x100x8mm Bend Test Through 180º is Satisfactory
Strip Taken from MS Plate610x100x6mm Bend Test Through 180º is Satisfactory
Strip Taken from MS Plate610x10x4mm Bend Test Through 180º is Satisfactory
Strip Taken from MS Angle 915x76/76x9.5mm Bend Test Through 180º is Satisfactory
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S Defence Housing Authority.
Lahore Cantt
(Execution of OHWT, Tube Well & Allied Facilities in Sector-H, DHA Ph-V (M/s Raza Zaman
& Coy)(Jamal)
Reference # CED/TFL 32002 (Dr. M Rizwan Riaz) Dated: 08-11-2018
Reference of the request letter # 408/241/E/Lab/343/283 Dated: 07-11-2018

Tension Test Report (Page – 1/1)


Date of Test 12-11-2018
Gauge length 2 inches
Description MS Pipe Steel Strip Tensile and Bend Test as per ASTM A53
Size of Strip

Yield Stress
Designation

Elongation
Yield load
X Section

Breaking

Ultimate

% Elongation
Stress
Load
Area

Remarks
Sr. No.

(inch) (mm) (mm2) (kg) (kg) (MPa) (MPa) (in)

1 MS Pipe 12 28.00x5.80 162.40 5400 7400 326.19 447.01 0.70 35.00

2 MS Pipe 12 28.00x5.80 162.40 5300 7200 320.15 434.93 0.60 30.00

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -
Only Two Samples for Tensile and One Sample for Bend Test

Bend Test
Strip Taken from MS Pipe (12") Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S Ittefaq Building Solution Pvt Ltd
Lahore
(Project : Pakages Factory Lahore)

Reference # CED/TFL 32006 (Dr. M Rizwan Riaz) Dated: 09-11-2018


Reference of the request letter # IBS/PKG/01 Dated: 09-11-2018

Tension Test Report (Page -1/2)


Date of Test 12-11-2018
Gauge length 8 inches
Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Elongation
Yield load

Breaking
Weight

Load
Diameter/ Area Yield Stress Ultimate Stress

% Elongation
Size (in2) (psi) (psi)

Remarks
Sr. No.

Nominal

Nominal

Nominal

Nominal
(lbs/ft)

Actual

Actual

Actual

Actual
(inch)

(inch)
(#)

(kg) (kg)

1 0.388 3 0.381 0.11 0.114 4500 5400 90200 87050 108200 104500 0.80 10.0

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -
Note: only one sample for tensile and one sample for bend test

Bend Test
#3 Bar Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S Ittefaq Building Solution Pvt Ltd
Lahore
(Project : Broad Way Heights Bahria Orchard, Lahore)

Reference # CED/TFL 32006 (Dr. M Rizwan Riaz) Dated: 09-11-2018


Reference of the request letter # IBS/BH-2 Dated: 09-11-2018

Tension Test Report (Page -2/2)


Date of Test 12-11-2018
Gauge length 8 inches
Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Elongation
Yield load

Breaking
Weight

Load
Diameter/ Area Yield Stress Ultimate Stress

% Elongation
Size (in2) (psi) (psi)

Remarks
Sr. No.

Nominal

Nominal

Nominal

Nominal
(lbs/ft)

Actual

Actual

Actual

Actual
(inch)

(inch)
(#)

(kg) (kg)

1 0.376 3 0.375 0.11 0.111 4300 5400 86200 85720 108200 107700 0.80 10.0

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -
Note: only one sample for tensile and one sample for bend test

Bend Test
#3 Bar Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Gojra-Jamani,
Section 2A (km 76+952 – 78+476 R/S)

Reference # CED/TFL 32007 (Dr. M Rizwan Riaz) Dated: 09-11-2018


Reference of the request letter # RE/M-4/2A/2018/420 Dated: 08-11-2018

Tension Test Report (Page – 1/3)


Date of Test 12-11-2018
Gauge length -------
Description Chain Link Fence Wire Tensile Test as per AASHTO-M-181

Diameter of
Breaking Load
Sr. No. Single Wire Remarks
(mm) (kg) (kN)

1 3.15 500 4.91

2 3.15 500 4.91

- - - -

- - - -

- - - -

- - - -

- - - -

Only Two Samples for Test

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Gojra-Jamani,
Section 2A (km 58+200 – 59+724 L/S)

Reference # CED/TFL 32007 (Dr. M Rizwan Riaz) Dated: 09-11-2018


Reference of the request letter # RE/M-4/2A/2018/419 Dated: 08-11-2018

Tension Test Report (Page – 2/3)


Date of Test 12-11-2018
Gauge length -------
Description Chain Link Fence Wire Tensile Test as per AASHTO-M-181

Diameter of
Breaking Load
Sr. No. Single Wire Remarks
(mm) (kg) (kN)

1 3.20 500 4.91

2 3.15 550 5.40

- - - -

- - - -

- - - -

- - - -

- - - -

Only Two Samples for Test

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer
RENARDET S.A ((M-4), Package-II)
Construction of Faisalabad-Khanewal Motorway (M-4) Project, Package-II, Gojra-Jamani,
Section 2A (km 86+476 – 88+000 R/S)

Reference # CED/TFL 32007 (Dr. M Rizwan Riaz) Dated: 09-11-2018


Reference of the request letter # RE/M-4/2A/2018/418 Dated: 08-11-2018

Tension Test Report (Page – 3/3)


Date of Test 12-11-2018
Gauge length -------
Description Chain Link Fence Wire Tensile Test as per AASHTO-M-181

Diameter of
Breaking Load
Sr. No. Wire Remarks
(mm) (kg) (kN)

1 3.15 500 4.91

2 3.20 450 4.41

- - - -

- - - -

- - - -

- - - -

- - - -

Only Two Samples for Test

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S CM Engineering (Pvt) Ltd
Lahore
(CM PAK Project Site ID : 40674, 41107, 42497, 42504, 42423, 42464, 41639, 42498, 41616,
41082)

Reference # CED/TFL 32011 (Dr. M Rizwan Riaz) Dated: 09-11-2018


Reference of the request letter # CME/Steel/CMPAK/321 Dated: 25-10-2018

Tension Test Report (Page -1/5)


Date of Test 12-11-2018
Gauge length 8 inches
Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Elongation
Yield load

Breaking
Weight

Diameter/
Load

Area Yield Stress Ultimate Stress

% Elongation
Size
(in2) (psi) (psi)

Remarks
(mm)
Sr. No.

Nominal

Nominal

Nominal

Nominal
(lbs/ft)

Actual

Actual

Actual

Actual

(inch)
(kg) (kg)

1 0.369 10 9.44 0.11 0.108 3200 4900 64200 65070 98200 99700 1.20 15.0

2 0.368 10 9.43 0.11 0.108 3200 4800 64200 65150 96200 97800 1.00 12.5

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test

Bend Test
10mm Dia Bar Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S CM Engineering (Pvt) Ltd
Lahore
(CM PAK Phase-9B Project Site ID : 51139)

Reference # CED/TFL 32011 (Dr. M Rizwan Riaz) Dated: 09-11-2018


Reference of the request letter # CME/Steel/CMPAK/Phase-9B/320 Dated: 01-11-2018

Tension Test Report (Page -2/5)


Date of Test 12-11-2018
Gauge length 8 inches
Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Elongation
Yield load

Breaking
Weight

Diameter/
Load
Area Yield Stress Ultimate Stress

% Elongation
Size
(in2) (psi) (psi)

Remarks
(mm)
Sr. No.

Nominal

Nominal

Nominal

Nominal
(lbs/ft)

Actual

Actual

Actual

Actual

(inch)
(kg) (kg)

1 0.370 10 9.45 0.11 0.109 3400 5000 68200 68930 100200 101400 1.20 15.0

2 0.368 10 9.42 0.11 0.108 3200 4800 64200 65250 96200 97900 1.20 15.0

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test

Bend Test
10mm Dia Bar Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S CM Engineering (Pvt) Ltd
Lahore
(CM PAK Project Phase-9B Site ID : 51082)

Reference # CED/TFL 32011 (Dr. M Rizwan Riaz) Dated: 09-11-2018


Reference of the request letter # CME/Steel/CMPAK/Phase-9B/319 Dated: 29-10-2018

Tension Test Report (Page -3/5)


Date of Test 12-11-2018
Gauge length 8 inches
Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Elongation
Yield load

Breaking
Weight

Diameter/
Load
Area Yield Stress Ultimate Stress

% Elongation
Size
(in2) (psi) (psi)

Remarks
(mm)
Sr. No.

Nominal

Nominal

Nominal

Nominal
(lbs/ft)

Actual

Actual

Actual

Actual

(inch)
(kg) (kg)

1 0.371 10 9.47 0.11 0.109 3300 4900 66200 66690 98200 99100 1.20 15.0

2 0.370 10 9.45 0.11 0.109 3200 4900 64200 64850 98200 99300 1.50 18.8

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test

Bend Test
10mm Dia Bar Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S CM Engineering (Pvt) Ltd
Lahore
(CM PAK Phase-9B Project Site ID : 51221)

Reference # CED/TFL 32011 (Dr. M Rizwan Riaz) Dated: 09-11-2018


Reference of the request letter # CME/Steel/CMPAK/Phade-9B/318 Dated: 26-10-2018

Tension Test Report (Page -4/5)


Date of Test 12-11-2018
Gauge length 8 inches
Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Elongation
Yield load

Breaking
Weight

Diameter/
Load
Area Yield Stress Ultimate Stress

% Elongation
Size
(in2) (psi) (psi)

Remarks
(mm)
Sr. No.

Nominal

Nominal

Nominal

Nominal
(lbs/ft)

Actual

Actual

Actual

Actual

(inch)
(kg) (kg)

1 0.354 10 9.24 0.11 0.104 4100 4800 82200 86900 96200 101800 0.90 11.3

2 0.354 10 9.25 0.11 0.104 4000 4900 80200 84630 98200 103700 0.90 11.3

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test

Bend Test
10mm Dia Bar Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S CM Engineering (Pvt) Ltd
Lahore
(Edot Co Project Site ID : MPPR02, MMCR02, FFD146., MDKR02, LSY002, LQDR06,
LSFR04, LDHI01, LTBI01, FFBR11)

Reference # CED/TFL 32011 (Dr. M Rizwan Riaz) Dated: 09-11-2018


Reference of the request letter # CME/Steel/Edot Co/317 Dated: 23-10-2018

Tension Test Report (Page -5/5)


Date of Test 12-11-2018
Gauge length 8 inches
Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Elongation
Yield load

Breaking
Weight

Diameter/
Load

Area Yield Stress Ultimate Stress

% Elongation
Size
(in2) (psi) (psi)

Remarks
(mm)
Sr. No.

Nominal

Nominal

Nominal

Nominal
(lbs/ft)

Actual

Actual

Actual

Actual

(inch)
(kg) (kg)

1 0.410 10 9.94 0.11 0.120 3600 5400 72200 65910 108200 98900 1.40 17.5

2 0.413 10 9.99 0.11 0.121 3800 5400 76200 68970 108200 98100 1.10 13.8

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -
Note: only two samples for tensile and one sample for bend test

Bend Test
10mm Dia Bar Bend Test Through 180º is Satisfactory

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires


UET Lahore, Pakistan.
Note:
1- You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3- Sealed sample / Unsealed sample / Marked sample/Signed Samples