In addition to the above, three nos. of Tie Transformers, five nos. of Auto
Transformers and two nos. of Shunt Reactors are provided as shown in the
switchyard line diagram.
5.4AUTO TRANSFORMERS
Five Auto Transformers with on Load Tap Changers are provided to interconnect
the 400 Kv system of NTPC and 220/132 Kv system of ATransco, Malyalapally
substation situated 1.8 Km away from the RSTPS switchyard.
Four nos. of Tie Transformers are provided for feeding power to station
auxiliaries like Cooling water & Raw water pumps, Coal Handling & water
treatment Plants, Ash & Fuel Handling pumps, Cooling towers and lighting
requirements of station & colony.
5.6SHUNT REACTORS
Long lines when lightly loaded, the receiving end voltage raises, due to Ferranti
effect. Shunt Reactors produce lagging MVAR there by control the receiving
end voltages during lightly loaded conditions. Shunt reactors also limit the
short circuit fault levels. Therefore, Shunt reactors are provided on both the
ends of Nagarjunasagar lines 1 & 2, the length of these lines being about 267
km
7. SWITCHYARD EQUIPMENT
Transformers
Switch Gears
Circuit Breaker
Isolators
Earth Switches
Surge Arrestors
Wave Traps
Reactive Power compensating device
BUS Bars
Conductors / Auxiliary Items
Post Insulators and supporting structures