Transformers  Problem  Set  
 
Ideal  Transformer  @  No  load  
1) Two  transformers  of  the  same  type,  using  the  same  grade  of  Iron  and  
Conductor  materials  are  designed  to  work  at  the  same  flux  and  current  
densities;  but  the  linear  dimensions  of  one  are  two  times  those  of  the  other  in  
all  respects.  The  ratio  KVA  of  the  two  transformers  closely  equals    
a)16   b)8   c)4   d)2    
2) A  400v/200v,  50Hz  transformer  operates  at  a  flux  density  of  1.2T.  When  
energized  from  HV  side  for  this  transformer.  For  this  transformer  if  the  linear  
dimensions  of  core  are  doubled  while  number  of  turns  halved  on  both  of  its  
HV  and  LV  sides.  If  the  transformer  is  now  connected  to  800V,  50Hz  on  its  HV  
side,  the  its  flux  density  would  be   a)0.6T  b)1.2T  c)2.4T  d)4T  
3)  
a) Find  the  operating  flux  and  Energy  Stored  for  given  magnetic  circuit  with  
No.  of  turns=100,  length  of  core=2000Cm,  Area  of  cross  section  of  
core=25Cm2,  Current  injected=1A.  Relative  permeability=2500  
b) Repeat  above  problem  to  calculate  current  to  be  injected  for  operating  
flux  of  section  a)  if  magnetic  core  has  now  2  mm  airgap  and  also  
determine  energy  stored  in  airgap.  
4) The  low  voltage  winding  of  a  400/230V  single  phase  50Hz  transformer  is  to  
be  connected  to  a  25Hz.  The  supply  voltage  should  be   a)230V
  b)460V   c)115V   d)65V  
5) A  4KVA,  230/115V,  400Hz  single  phase  transformer  originally  designed  for  
use  in  aircraft  is  available  in  laboratory  for  obtaining  115V  from  230V  supply,  
50Hz  mains.  If  over  loading  of  devise  is  not  permitted  then  the  net  kva  output  
of  the  transformer  in  the  laboratory  cannot  exceed__  a)32   b)16   c)4
  d)0.5      
6) A  single-­‐phase  10KVA,  50Hz  transformer  with  1kv  primary  winding  draws  
0.5A  and  55W,  at  rated  voltage  and  frequency  on  no  load.  The  second  
transformer  has  a  core  with  all  its  linear  dimensions  √2  times  the  
corresponding  dimensions  of  first  transformer.  The  core  material  and  
lamination  thickness  are  same  in  both  transformers.  The  primary  winding  of  
both  the  transformers  have  same  number  of  turns.  If  a  rated  voltage  of  2kv  at  
50Hz  is  applied  to  the  primary  of  second  transformer  then  the  noload  current  
and  power  respectively  are     a)0.7A,  77.8W   b)0.7A,  155.6W  
  c)1A,110W   d)1A,  220W  
7) Estimate  reduction  of  volume,  expressed  as  a  percentage  of  the  original  
volume  of  a)  Core  Iron  b)  Copper  in  a  transformer  when  original  steel  plates  
worked  at  a  flux  density  of  0.8  Tesla  are  replaced  by  others  of  Silicon  steel  
worked  at  flux  density  of  1.2  Tesla  assuming  the  total  flux  to  remain  same.  
Assume  square  core.  
8) A  transformer  with  toroidal  core  of  permeability  μ  is  shown  in  the  figure.  
Assuming  uniform  flux  density  across  the  circular  core  cross  section  of  radius  
r<<R,  and  neglecting  any  leakage  flux,  the  best  estimate  for  the  mean  radius  R  
!"#! ! !!!
is   a)__   b)__   c)__       d)   !!
   

_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  

 
 
Ideal  Transformer  @  Load  
9) Consider  a  simple  power  system  consisting  of  an  ideal  voltage  source,  an  
ideal  step  up  transformer,  a  transmission  line,  an  ideal  step  down  
transformer  and  a  load.  The  voltage  of  source  is  480  |0  V,  the  impedance  of  
transmission  line  is  (3+j4)  Ω,  impedance  of  load  is  (30+j40)  Ω.  What  turns  
ratio  would  be  required  to  reduce  transmission  line  loss  to  1%  of  total  active  
power  produced  by  generator.  
10)A  three  phase,  three  winding  Delta/Delta/Star  transformer  
(1.1kV/6.6kV/400V)  transformer  is  energized  from  AC  mains  at  1.1  kV  side.  
It  supplies  900kVA  load  at  0.8pf  lag  from  6.6kV  winding  and  300kVA  load  at  
0.6  pf  lag  from  400V  winding.  The  rms  line  current  in  Amps  drawn  by  the  
1.1kV  winding  from  mains  is  ____    
11)A  balanced  star  connected  and  purely  resistive  load  is  connected  at  the  
secondary  of  a  star/Delta  transformer  as  shown  in  fig.  The  line  to  line  voltage  
rating  of  transformer  is  110v/220v.  Neglect  the  non-­‐idealities  of  transformer,  
the  impedance  Z  of  the  equivalent  star  connected  load  referred  to  the  
primary  side  of  transformer  is____      

 
 
12)The  following  arrangement  consist  of  an  ideal  transformer  and  an  attenuator  
which  attenuates  by  a  factor  of  0.8  An  AC  voltage  𝑉!"! =100V  is  applied  across  
WX  to  get  an  open  circuit  voltage  𝑉!"!  across  YZ.  Next,  an  ac  voltage  

_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
𝑉!"! =100V  is  applied  across  YZ  to  get  an  open  circuit  voltage  𝑉!"!  across  WX.  
Then  𝑉!"! /𝑉!"! ,  𝑉!"! /𝑉!"!  are  respectively.        a)___  b)100/100  and  80/100    
c)__        (d)___    

 
 
13)Figure  shows  an  ideal  3  winding  transformer.  Windings  are  wound  on  the  
same  core  as  shown.  The  turns  ratio  𝑁! :  𝑁! : 𝑁!  is  4:2:1  A  resistor  of  10  ohm  is  
connected  across  winding  2.  A  capacitor  of  reactance  2.5  ohm  is  connected  
across  winding  3.  Winding  1  is  connected  across  400V  AC  supply.  If  the  
supply  voltage  phasor  𝑉! =400  V    the  supply  current  phasor  𝐼!  is  given  by
  a)__   b)__   c)(10+j10)A   d)__  

 
14)Three  single  phase  transformers  are  connected  to  form  delta-­‐star  three  phase  
transformer  of  110kv/11kv.  The  transformer  supplies  at  11kv  a  load  of  8Mw  
at  0.8pf  lag  to  nearby  plant.  Neglect  the  transformer  losses.  The  ratio  of  phase  
currents  from  delta  side  to  star  side  is  ___  ans)  1:10 3    
15)If  the  primary  line  voltage  rating  is  3.3kv  star  side  of  a  25kva,  Y-­‐D  
transformer  (The  per  phase  turns  ratio  is  5:1),  then  the  line  current  rating  of  
the  secondary  side  (in  Ampere  is)____    
16)The  load  shown  in  the  figure  absorbs  4kW  at  pf  of  0.89  lag.  Assuming  the  
transformer  to  be  ideal  the  value  of  reactance  X  to  improve  the  input  power  
factor  to  unity  is  ___  

 
 
_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
 
 
Core  Losses  of  Transformer  
17)A  transformer  has  hysteresis  loss  of  30W  at  240V,60Hz  supply.  The  
hysteresis  loss  at  200V,  50Hz  supply  is?  
18)A  transformer  has  Iron  loss  of  90W  at  60Hz  supply  and  52W  a  40Hz  supply.  
Both  losses  being  measured  at  same  peak  flux  density.  The  total  iron  losses  in  
the  transformer  at  50Hz  supply  will  be  ?  
19)A  230V,  50Hz  single  phase  transformer  has  eddy  current  loss  of  30W.  If  this  
transformer  is  excited  with  DC  source  of  same  magnitude  eddy  current  losses  
will  be  _______     a)30W     b)25W     c)0W     d)None  of  
the  above  
20)A  voltage  of  (200  wt-­‐50  sin  3wt)  is  applied  to  a  250  turn  transformer  winding  
having  negligible  resistance  and  leakage.  Find  the  instantaneous,  Max  value  
of  flux  and  also  find  by  what  percentage  will  the  eddy  current  loss  in  the  iron  
be  reduced  if  the  applied  voltage  is  altered  to  200  sin  wt?  Given  w=100π  
21)A  5kV,  25Hz  single  phase  transformer  has  copper  loss  of  1.4%,  hysteresis  loss  
of  0.6%  and  eddy  current  loss  of  0.5%  of  full  load  output.  If  this  transformer  
is  operated  on  10kV,  50Hz  supply  system,  what  will  be  these  losses  if  the  
current  in  the  windings  remain  same  
22)A  50Hz  transformer  having  equal  hysteresis  and  eddy  current  losses  at  rated  
excitation  is  operated  at  45Hz  at  90%  of  its  rated  voltage.  Compared  to  rated  
operating  point,  the  core  loss  under  this  condition   a)___   b)___   c)reduced  
by  14.5%   d)___  
23)A  single  phase  400V,  50Hz  transformer  has  an  iron  loss  of  5000W  at  the  rated  
condition.  When  operated  at  200V,  25Hz,  the  iron  loss  is  2000W.  When  
operated  at  416V,  52Hz  the  value  of  hysteresis  loss  divided  by  the  eddy  
current  loss  is  ____    (Ans:  1.44)  
24)Am  open  circuit  test  is  performed  on  50Hz  transformer,  using  variable  
frequency  source  and  keeping  v/f  ratio  constant,  to  separate  its  eddy  current  
and  hysteresis  losses.  The  variation  of  core  loss  /  frequency  as  function  of  
frequency  is  shown  in  fig.  The  hysteresis  and  eddy  current  loss  of  
transformer  at  25  Hz  respectively  are___  (Ans:  250W  and  62.5W)      

 
25)A  50Hz,  220/400V,  50kva  single  phase  transformer  operates  on  220V,  40Hz  
supply  with  secondary  winding  open  then,     a)the  eddy  current  loss  and  
hysteresis  loss  of  transformer  decreases   b)  the  eddy  current  loss  and  
hysteresis  loss  of  transformer  increases   c)  the  hysteresis  loss  of  

_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
transformer  increases  while  eddy  current  loss  remain  same  d)  the  hysteresis  
loss  of  transformer  remain  the  same  while  eddy  current  loss  decreases    
26)Two  transformers  X  and  Y  with  identical  ratings  and  dimensions  have  0.8mm  
and  1.2mm  thick  laminations  respectively  .If  𝑅!  and  𝑋!  are  the  magnetizing  
branch  parameters  in  the  equivalent  circuit,  then  
(a) 𝑅!  values  in  both  are  likely  to  be  equal,  but  𝑋! of  X  is  likely  to  
higher  than  𝑅!  of  Y.  
(b) 𝑋!   values  in  both  are  likely  to  be  equal,but  𝑅!   of  X  is  likely  to  
higher  than  𝑅!   of  Y  
(c) 𝑋!   values  in  both  are  likely  to  be  equal,but  𝑅!   of  X  is  likely  to  
be  lower  than  𝑅!   of  Y  
(d) 𝑅!  values  in  both  are  likely  to  be  equal,  but  𝑋! of  X  is  likely  to  
be  lower  than  𝑋!  of  Y.  
27)A  transformer  designed  for  operation  on  60  Hz  supply  is  worked  on  50  Hz  
supply  system  without  changing  its  voltage  and  current  ratings.  When  
compared  with  full  load  efficiency  at  60  Hz,  the  transformer  efficiency  on  full  
load  at  50Hz  will  
(a) increase  marginally  
(b) increase  by  a  factor  of  1.2  
(c) remain  unaltered  
(d) decrease  marginally  
28)If  a  saw-­‐cut  is  made  in  the  iron  core  of  a  single  phase  transformer  as  shown  
in  the  given  figure,  with  secondary  terminals  open,  it  will  result  in  

 
(a) no  voltage  across  secondary  terminals  due  to  discontinuity.  
(b) Excessively  large  current  drawn  by  primary  
(c) No  appreciable  change  in  the  operation  of  the  transformer.  
(d) No  transformer  action  and  the  primary  current  will  be  greatly  
reduced    
29)A  220/110V,50Hz  single  phase  transformer  having  a  negligible  winding  
resistance  operates  from  a  variable  voltage,  variable  frequency  supply  such  
that  𝑉! /𝑓(𝑉! =  primary  applied  voltage,  f=  source  frequency)is  constant.  This  
will  bring  in,  in  the  given  range  of  frequencies  
(a) variation  in  both  eddy  current  loss  and  hysteresis  loss  
(b) variation  only  in  the  eddy  current  loss,  hysteresis  loss  
remaining  constant.  
(c) Variation  only  in  hysteresis  loss,  eddy  current  loss  remaining  
constant.  
(d) No  change  either  in  the  eddy  current  loss  or  the  hysteresis  loss  
_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
30)The  given  fig  represents  a  transformer  with  two  windings  1  &  2  on  the  core  
as  shown.  By  applying  voltage  across  𝑉!  across  winding  1  and  𝑉!  is  induced  
across  winding  2.  In  an  idealized  condition  𝑉!  would  lag  𝑉!  by  (Ans:  180  Deg)  

 
31)The  fig  given  below  shows  a  two  winding  core  type  transformer.  The  
instantaneous  directions  of  primary  current  I1  ,the  mutual  flux  Φm and the
primary leakage flux Φ1 are as indicated in the figure. The
corresponding directions, at the same instant, of the secondary
current I2, and secondary leakage flux Φ2 would be  

 
32)Two  windings  of  a  transformer  are  indicated  by  terminals  AB  and  CD  as  
shown  in  figure.    When  a  voltage  of  100V  applied  across  AB  with  BD  short  
circuited,  a  voltage  of  200V  appears  across  AC.  The  turns  ratio  from  CD  to  AB    

is____  
33) A  1000VA,  230/115V,  transformer  has  been  tested  to  determine  its  equivalent  circuit.  The  
results  are  given  as   O.C:  115V,0.11A,3.9W  and  S.C.:17.1V,8.7A,38.1W.  Find  equivalent  
circuit  of  this  transformer  referred  to  LV  side.  
34) A  50Hz,  single  phase  transformer  draws  short  circuit  current  of  30A  at  0.25pf  when  
connected  to  16V,50Hz  source.  What  will  be  the  power  factor  if  it  is  energized  from  
16V,75Hz  source.  
35)It  is  desired  to  measure  parameters  of  230V/115  V,2kVA,  single  phase  
transformer.  The  following  watt  meters  are  available  in  the  laboratory:  
W1:  250V,  10  A,  low  power  factor  
               W2:  250  V  ,  5A  ,low  power  factor  
W3:  150V,  10  A  ,High  power  factor  
               W4:  150  V  ,  5A  ,High  power  factor  
_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
The  wattmeter’s  used  in  open  circuit  test  and  short  circuit  test  of  the  
transformer  will  be                                                                                                                        (Ans:  W2  and  W3)  
 
36)  The  percentage  impedance  of  a  100  kVA,  11  kV/400  V,  delta  /wye,  50  Hz  
transformer  is  4.5%.  For  the  circulation  of  half  the  full  load  current  during  short  
circuit  test,  with  low  voltage  terminals  shorted,  the  applied  voltage  on  the  
voltage  side  will  be                                                                                                                          (Ans:  247.5  V)  
                   
37)  A  3-­‐Phase  transformer  has  rating  of  20  MVA,  220  kV  (Star)/33  kV  (Delta)  
with  leakage  reactance  12%.  The  transformer  reactance  (in  ohms)  referred  to  
each  phase  of  the  L.V.  delta  connected  side  is                          (Ans:  19.6)  
 
38)  The  resistance  and  reactance  of  a  100  kVA,  11000/400  V,  delta/star  
distribution  transformer  are  0.02  and  0.07  pu  respectively.  The  phase  impedance  
of  the  transformer  referred  to  the  primary  is                                  (Ans:  (72.6  +  j254.1)Ω)    
 
39)  The  core  flux  of  a  practical  transformer  with  a  resistive  load  
     a)  Is  strictly  constant  with  load  changes    
     b)  Increases  linearly  with  load    
     c)  Increases  as  the  square  root  of  the  load  
     d)  Decreases  with  increased  load                                                                            (Ans:  d)  
 
40)  
 
41)  A  20  kVA  2000/200V  single-­‐phase  transformer  has  (0.02  +  j0.06)  pu  
impedance.  To  maintain  load  side  voltage  at  200V  at  full  load  0.8pf  lag,  the  
voltage  required  to  be  applied  on  primary  side  of  transformer  is  -­‐-­‐-­‐-­‐-­‐-­‐-­‐.  
       
42)  A  transformer  has  400/200V  rating  and  it  has  a  pf  of  0.8  lag  on  secondary  
side  when  it  is  loaded.  About  40V  is  required  to  circulate  rated  current  on  short  
circuit,  at  pf  of  0.2.  The  voltage  regulation  of  transformer  at  full  load  0.8  pf  lag  is  -­‐
-­‐-­‐-­‐-­‐-­‐-­‐  
43)  A  10kVA,  400V/200V,  singe  phase  transformer  with  a  percentage  resistance  
of  3%  and  percentage  reactance  of  6%  is  supplying  a  current  of  50A  to  a  resistive  
load.  The  value  of  the  load  voltage  is                                                                            (Ans:  194  V)  
 
44)  A  3-­‐phase  delta/star  transformer  is  supplied  6000  V  on  delta  connected  side.  
The  terminal  voltage  on  the  secondary  side  when  supplying  full  load  at  0.8  
lagging  power  factor  is  415  V.  The  equivalent  resistance  and  reactance  drops  for  
the  transformer  are  1%  and  5%  respectively.  The  turns  ratio  of  the  transformer  
is                                                                                                                                                                                                                  (Ans:  24)  
 
45)  A  single-­‐phase  transformer  has  no-­‐load  loss  of  64W,  as  obtained  from  an  
open-­‐circuit  test.  When  a  short  circuit  test  is  performed  on  it  with  90%  of  the  
rated  currents  flowing  in  its  both  LV  and  HV  windings,  the  measured  loss  is  81W.  
The  transformer  has  maximum  efficiency  when  operated  at    
       a)  50.0%  of  the  rated  current  
       b)  64.0%  of  the  rated  current  
       c)  80.0%  of  the  rated  current  
_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
       d)  88.8%  of  the  rated  current                                                                                                  (Ans:  C)  
46)  A  single  phase  transformer  has  a  maximum  efficiency  of  90%  at  full  load  and  
upf.  Efficiency  at  half  load,  at  the  same  power  factor  is  
  a)  86.7%  
  b)  88.26%  
  c)  88.9%  
  d)  87.8%  
47)  20  kVA  single  phase  transformer  has  efficiency  of  98%  at  full  load  and  also  at  
half  full  load.  The  power  factor  is  unity  in  both  the  cases.  The  efficiency  of  
transformer  at  ¾th  full  load  at  upf  is  ____  
           a)  98.1%                      b)  98%                      c)  97.8%                      d)  97.5%                            (Ans:  a)  
 
 Data  for  Questions  (48  and  49)  
A  300kVA  transformer  has  95%  efficiency  at  full  load  0.8  pf  lagging  and  96%  
efficiency  at  half  load,  unity  pf.  
48)  The  iron  loss  (Pi)  and  copper  loss  (Pc)  in  kW,  under  full  load  operation  are  
                           a)  Pc  =  4.12,      Pi  =  8.51  
  b)  Pc  =  6.59,      Pi  =  9.21  
  c)  Pc  =  8.51,        Pi  =  4.12  
  d)  Pc  =  12.72,  Pi  =  3.07                                                                                                                                  (Ans:  C)  
49)  What  is  the  maximum  efficiency  (in  %)  at  unity  pf  load?  
                 a)  95.1                      b)  96.2                            c)  96.4                              d)  98.1                                      (Ans:  b)    
 
50)  The  percentage  resistance  and  percentage  reactance  of  a  10kVA,  400V/200V,  
3-­‐Phase  transformer  are  2%  and  10%  respectively.  If  the  constant  losses  in  the  
machine  are1%,  the  maximum  possible  percentage  efficiency  of  the  transformer  
is    
                   a)  98.32                  b)  97.25                    c)  96.85                        d)  96.12                                      (Ans:  b)  
 
 
51)  A  500  kVA,  3-­‐phase  transformer  has  iron  losses  of  300  W  and  full  load  
copper  losses  of  600  W.  The  percentage  load  at  which  the  transformer  is  
expected  to  have  maximum  efficiency  is  
               a)  50.0%                    b)  70.7%                            c)  141.4%                    d)  200.0%              (Ans:  b)  
 
52)  The  efficiency  of  a  100kVA  transformer  is  0.98  at  full  as  well  as  at  half  load.  
For  this  transformer  at  full  load  the  copper  loss  
                   a)  is  less  than  core  loss  
                   b)  is  equal  to  core  loss  
                   c)  is  more  than  core  loss    
                   d)  none  of  the  above                                                                                                                                                        (Ans:  c)  
 
 
53)  A  10  kVA,  250  V/2500  V,  1-­‐phase,  two  winding  transformer  has  95%  
efficiency  at  full  load,  upf.  Calculate  efficiency  if  this  two  winding  transformer  is  
used  as  auto  transformer  for  different  configuration.                                                        
 
 

_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
54)  A  400V/200V  transformer  has  full  load  voltage  regulation  of  Xpu  at  0.8pf  lag.  
If  this  transformer  is  used  as  an  auto  transformer  with  voltage  ratings  of  
400V/600V  or  200V/600V,  then  its  voltage  regulation  would  be  
             a)  x/3,  x/3                          b)2x/3,  x/3                          c)2x/3,2x/3                          d)x/3,2x/3              (Ans:  b)  
 
55)  Derive  an  expression  for  the  approximate  relative  weights  of  the  Cu  in  an  
auto  transformer  and  a  two  winding  transformer,  the  primary  voltage  being  V1  
and  the  secondary  voltage  V2.  Compare  the  weights  of  Cu  when  the  
transformation  ratio  is  3.  Ignore  magnetizing  current.                                                                  (Ans:  2/3)  
 
56)  A  single-­‐phase,  50  kVA,  1000  V/  100  V  two  winding  transformer  is  
connected  as  an  autotransformer  as  shown  in  the  figure.  

                                                       
The  kVA  rating  of  the  autotransformer  is  ____________                                                                        (Ans:  550)  
 
57)  A  200/400  V,  50  Hz,  two-­‐winding  transformer  is  rated  at  20  kVA.  Its  
windings  are  connected  as  an  auto-­‐transformer  of  rating  200/600  V.  A  resistive  
load  of  12Ω  is  connected  to  the  high  voltage  (600  V)  side  of  the  auto-­‐transformer.  
The    value  of  equivalent  load  resistance  (in  ohms)  as  seen  from  low  voltage  side  
is                                                                                                                                                                                                                                                                  (Ans:  1.33)  
58)  A  single  phase  2kva  100/200V  transformer  is  reconnected  as  an  auto  
transformer  such  that  its  kVA  rating  is  max.  The  new  rating,  in  kVA  is  ____  (Ans:  
6)  
 
59)  A  single  phase  22kva  2200/220V  50Hz,  distribution  transformer  is  to  be  
connected  as  an  auto  transformer  to  get  an  output  voltage  of  2420V.  Its  max  kVA  
rating  as  an  auto  transformer  is  ____                                                                                                                              (Ans:  242)  
 
60)  A  50kva  3300/230V  single  phase  transformer  is  connected  as  an  auto  
transformer  as  shown  in  fig.  The  nominal  rating  of  the  auto  transformer  will  be  
___                                                                                                                                                                                                                                                                (Ans:  767.4)  
                   
 
 
 
 
 
 
 
 
 
_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
 
Statement  for  Linked  answer  questions  (61  &  62)  

                       
The  figure  above  shows  coils  1  and  2  with  dot  markings  as  shown,  having  4000  
and  6000  turns  respectively.  Both  the  coils  have  a  rated  current  of  25A.  Coil  1  is  
excited  with  single  phase,  400V,  50Hz  supply.  
 
61)  The  coils  are  to  be  connected  to  obtain  a  single  phase  400/1000V  auto  
transformer  to  drive  a  load  of  10kva.  Which  of  the  options  given  should  be  
exercised  to  realize  the  required  auto  transformer?  
a)  Connect  A  and  D;  Common  B  
b)  Connect  B  and  D;  Common  C  
c)  Connect  A  and  C;  Common  B  
d)  Connect  A  and  C;  Common  D                                                                                                                                                    (Ans:  a)  
62)  In  the  auto  transformer  obtained  in  above  question  the  current  in  each  coil  is  
___                                                                                                                                   (Ans:  Coil-­‐1  is  15A  and  Coil  2  is  10A)  
 
 
Synchronous  Machines  
 
• Two  magnetic  poles  revolve  around  a  stationary  armature  carrying  two  
coil  (C1  –  𝐶!! ,  C2  -­‐  𝐶!! )  as  shown  in  the  figure.  Consider  the  instant  when  the  
poles  are  in  a  position  as  shown.  Identify  the  correct  statement  regarding  
the  polarity  of  the  induced  emf  at  this  instant  in  coil  sides  C1  and  C2.  

_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
                                                                                       

   
 a)  ʘ  in  C1,  no  emf  in  C2  
 b)  ⊗  in  C1,  no  emf  in  C2  
 c)  ʘ  in  C2,  no  emf  in  C1  
 d)  ⊗  in  C2,  no  emf  in  C1                                                                                                                                    (Ans:  a)  
2)  When  Stator  and  Rotor  windings  of  a  2-­‐Pole  rotating  electrical  machine  are  
excited,  each  would  produce  a  sinusoidal  mmf  distribution  in  the  airgap  with  
peak  values  Fs  and  Fr  respectively.  The  rotor  mmf  lags  stator  mmf  by  a  space  
angle    at  any  instant  as  shown  in  figure.  Thus,  half  of  stator  and  rotor  surfaces  
will  form  one  pole  with  the  other  half  forming  the  second  pole.  Further,  the  
direction  of  torque  acting  on  the  rotor  can  be  clockwise  or  counter-­‐clockwise.  
                                               

 
 
The  following  table  gives  four  sets  of  statements  as  regards  poles  and  torque.  
Select  the  correct  set  corresponding  to  the  mmf  axis  as  shown  in  figure.  
                                                       

_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
  Stator   Stator   Rotor   Rotor   Torque  
surface   surface   surface  abc   surface  cda   Surface  
ABC  forms   CDA  forms   forms   forms    
(a)   North  Pole   South  Pole  
Clockwise   North  Pole   South  Pole  
(b)   South  Pole   North  Pole  
Counter   North  Pole   South  Pole  
Clockwise  
(c)   North  Pole   South  Pole   South  Pole   North  Pole   Counter  
Clockwise  
(d)   South  Pole   North  Pole   South  Pole   North  Pole   Clockwise  
   
3)  Find  the  highest  speeds  and  the  corresponding  number  of  poles  for  two  direct  
coupled  alternators  required  to  give  frequencies  of  a)  15  &  42    b)  42  &  50  Hz.  
 
4)  A  50  Hz  synchronous  clock  is  correct  at  7AM.  From  7AM  to  1PM  the  average  
frequency  is  49.95  Hz  from  1PM  to  6PM  is  49.90Hz.  What  must  be  the  average  
frequency  for  the  remainder  of  the  24  Hrs  in  order  that  the  clock  be  correct  again  
at  7AM?.  By  how  much  is  the  clock  incorrect  at  6PM?  
 
5)  A  three-­‐phase  10  pole  star  connected  alternator  runs  at  600rpm.  It  has  120  
slots  with  8  conductors  per  slot  and  the  conductors  of  each  phase  are  connected  
in  series.  Determine  the  phase  and  line  emfs  if  the  flux  per  pole  is  56mWb.  What  
harmonics  due  to  slots  might  occur  in  the  phase  and  line  voltages?  
 
6)  Determine  the  root  mean  square  value  of  the  individual  harmonic  components  
and  of  the  total  induced  emf  per  phase  and  line  of  a  50Hz,  3phase  alternator  from  
the  following  data:  No  of  poles  =  10,  slots  per  pole  per  phase  =  2,  conductors  per  
slot  (2layers)  =4,  coil  span  =1500,  flux  per  pole,  fundemental=  0.12Wb,  The  
analysis  of  the  air  gap  flux  density  shows  a  20%  third  harmonic.  All  the  coils  are  
connected  in  series.  
 
7)  The  armature  of  a  single  phase  alternator  is  completely  wound  with  T  single  
turn  coils  distributed  uniformly.  The  induced  voltage  in  each  turn  is  2Volts(rms).  
The  emf  of  the  whole  winding  is  
             a)  2  T  Volt              b)  1.11  T  Volt                c)  1.414  T  Volt          d)  1.273  T  Volt                (Ans:  d)  
 
8)  A  20  pole  alternator  is  having  180  identical  stator  slots  with  6  conductors  in  
each  slot.  All  the  coils  of  a  phase  are  in  series.  If  the  coils  are  connected  to  realize  
single-­‐phase  winding,  the  generated  voltge  is  V1.  If  the  coils  are  reconnected  to  
realize  three-­‐phase  star  connected  winding,  the  generated  phase  voltage  is  V2.  
Assuming  full  pitch,  single-­‐layer  winding,  the  ratio  V1/V2  is    
! !
       a)   !                                  b)  !                                  c)   3                                d)2                                                        (Ans:  d)  
 
9)  It  is  desirable  to  eliminate  5th  harmonic  voltage  from  the  phase  voltage  of  an  
alternator.  The  coils  should  be  short-­‐pitched  by  an  electrical  angle  of    
 
a) 300                    b)  360                          c)  720                              d)  180                                            (Ans:  b)  
 

_____________________________________________________________________________________________  
YouTube  Channel  Play  List  for  Machines:  www.bit.ly/knraomcs  
YouTube  Channel  Play  List  for  Power  Systems:  www.bit.ly/knraops  
For  doubts/clarifications  E-­‐mail:  gate.knrao@gmail.com  
For  regular  Updates  Telegram  Channel:  GATE  lectures  by  KN  Rao      https://t.me/knrao123  
_____________________________________________________________________________________________  
10)  The  distribution  factor  for  a  36  slot  stator  with  3-­‐phase,  8-­‐pole  winding,  
having  1200  phase  spread,  is  ___________  
 
Data  for  Questions(39,41)  
A  4  pole,  50Hz,  synchronous  generator  has  48  slots  in  which  a  double  layer  
winding  is  used.  Each  coil  has  10  turns  and  is  short  pitched  by  an  angle  to  360  
electrical.  The  fundamental  flux  per  pole  is  0.025  Wb.  
 
11)  The  line-­‐to-­‐line  induced  emf  (in  volts),  for  a  three  phase  star  connection  is  
approximately  
             a)  808                        b)  888                      c)  1400                        d)  1538                                            (Ans:  c)    
 
12)  The  fifth  harmonic  component  of  phase  emf  (in  volts),  for  a  three  phase  star  
connection  is    
               a)  0                                b)  269                          c)  281                            d)  808                                                (Ans:  a)  
 
13)  A  three  phase  alternator  is  wound  with  a  60  degree  phase-­‐spread  armature  
windings  and  develops  300  kVA.  If  the  armature  is  reconnected  utilizing  all  the  
coils  for  single-­‐phase  operation  with  a  phase  spread  of  180  degrees,  the  new  
rating  for  the  machine  is  
                 a)  100  kVA      b)  200  kVA              c)  250  kVA              d)  300  kVA                  (Ans:  b)  
   
14)  A  3-­‐ ,  4  pole,  60  slot  alternator,  if    
               a)  Coil  span  =  one  to  12  then  pitch  factor  is    
               b)  The  winding  is  short  pitched  by  five  slots  then  the  pitch  factor  is    
!!!!
               c)  If  coil  span  =   !"  of  pole  pitch  then  coil  span  factor  is  
 
15)  A  4-­‐pole,  3-­‐phase,  double  layer  winding  is  housed  in  a  36-­‐slot  stator  for  an  ac  
machine  with  600  phase  spread.  Coil  span  is  7  short  pitched.  Number  of  slots  in  
which  top  and  bottom  layers  belong  to  different  phases  is    
               a)  24                          b)  18                          c)  12                                  d)  0                                                                    (Ans:  a)  
 
16)  The  flux  per  pole  in  a  synchronous  motor  with  the  field  circuit  ON  and  the  
stator  disconneted  from  the  supply  is  found  to  be  25  mWb.  When  the  stator  is  
connected  to  the  rated  supply  with  the  field  excitaion  unchanged,  the  flux  per  
pole  in  the  machine  is  found  to  be  20  mWb  while  the  motor  is  running  on  no-­‐
load.  Assuming  no-­‐load  losses  to  be  zero,  the  no-­‐load  current  drawn  by  the  
motor  from  the  supply  
a)  lags  the  supply  voltage  
b)  leads  the  supply  voltage  
c)  is  in  phase  with  the  supply  voltage  
d)  Is  zero                                                                                                                                                                                                                    (Ans:  b)  
 
 