Shri S. R. Bhat, Member Secretary i/c, SRPC welcomed the Members and the Participants
to the 32nd Meeting of the Protection Coordination Sub-Committee.
MS i/c briefed the members about the communication addressed to Hon'ble CERC in
respect of Phase-I of implementing recommendations of Protection Audit; based on
inputs received from the utilities. He also reminded the Members about the time line for
implementation of activities relating to Phase-II of the same i.e. 1st Sep, 2014. Bimonthly
report in this regard needed to be submitted to Hon'ble CERC. He urged the constituents
to kindly submit the inputs at the earliest, for further necessary action.
MS i/c also informed the Members about the completion of "Transmission line patrolling
guidelines" that had been prepared in consultation with the stake holders. The same had
been submitted to Hon'ble CERC and also posted in the SRPC website for compliance.
He observed that the load relief under UFR was lower than actually desired as observed
through average values visible through SCADA. Members were kindly requested to make
arrangements to ensure the desired load relief under UFR schemes, enabling the grid in a
secure manner.
MS i/c also informed the forum regarding the Sub Group meeting held on 28th May 2014
at SRPC to discuss issues raised by KSEB on account of SPS modifications of Sholapur-
Raichur 765 kV line proposed by NLDC. Many issues had been discussed and resolved
after deliberations. He proposed a Sub Committee to study and review the existing df/dt
settings – rate of decay, quantum of relief, contingency to be considered etc. Members
were informed about the Task Force report on "Power System Analysis under
Contingencies”. The issues addressed in the report needed to be deliberated in the next
PCSC meeting so as to decide the road map to accomplish the tasks given in the report.
MS i/c informed about the two Sub Group meetings of PCSC held in the month of May
2014. One meeting was held at NTECL-Vallur on 19th May 2014 in respect of pollution
related trippings of the lines in Vallur area (North Chennai); another meeting at MAPS-
Kalpakkam in respect of Unit-1 hunting observed on 20th May2014.
2 Confirmation of the Minutes of the 31st PCSC Meeting held on 29th April 2014
The Minutes of the 31st PCSC meeting were confirmed since no comments had been received
from the constituents.
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 2
Single Line Diagram
Deliberations:
• The following were noted about the trip event:
o Krishnapatnam – Nellore 1 (AP-Manubolu) line tripped in Zone-2 E/F at
Manubolu end only; carrier aided trip did not operate.
o At SEPL end, back up e/f protection operated and running units 1, 2, 3 tripped.
• SRLDC explained that as the generating units at Krishnapatnam are not in service there
is no source (i.e. V and I signals) to drive the distance relays at Krishnapatnam end
hence the tripping at one end only i.e. Manubolu; SRLDC informed that similar event
had taken place on 25th May2014 @ 17:03 hrs.
• KPCTL suggested for using "weak-infeed" logic for the line.
• SRLDC suggested that at SEPL, it is better to have IDMT characteristics for DEFR than
DMT and the relay has to be coordinated with zone-2 settings of the other lines.
• In the Meeting, it was agreed that AP may consider implementing "weak-infeed" or
other suitable logic in respect of Krishnapatnam-Nellore (AP - Manubolu) lines.
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 3
3.2 Grid Disturbance at BTPS Substation on 01-05-2014
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 4
Single Line Diagram
Deliberations:
KPCL:
• B-phase bushing of GT of unit-1 got flashover and resulted in heavy neutral current
flowing in unit-2.
• Due to blast over the bushing, the lines were hand-tripped by the operator.
• On JSW line carrier was received from Jindal end.
JSW:
• BTPS-JSW line is a LILO line of 11 km length.
• Line auto reclosed at JSW end and normal carrier was sent to other end.
• Existing line settings are provided by KPTCL.
SRLDC:
• SRLDC agreed that the B-phase fault was cleared in time.
• Due to the fact that the line is short, POR (permissible over reach) scheme could be
implemented for distance protection.
• JSW end of BTPS-JSW line should have tripped in Zone-2 instead of Zone-1 and this
aspect needed review.
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 5
• KPCL informed that no zone-4 tripping though the same had been mentioned in FIR.
Due to this contradiction, KPCL was requested to submit a detailed report pertaining to
the incident.
KPTCL:
• The time settings of PD (Pole Discrepancy) relay and A/R relay had to be checked and
reviewed at BTPS.
Recommendations
• KPCL was requested to submit the detailed analysis report of the incident within a
week's time.
• KPCL was requested to check & review the time settings of PD (Pole Discrepancy)
relay and A/R relay and the same shall be informed to PCSC forum.
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 6
• From the FIR, it was noted that there was operation of bus bar protection of both buses
1 & 2 due to failure of string insulators that caused the quadruple bus conductors to fall
on the tubular bus bars of Pugalur-2 line and TS-2 tie line bay.
• The operation had also resulted in tripping of Pugalur-2 line, TS-2 tie line, GT1, and
GT2.
• There was also a tripping of TS-2 Expn – Trichy line due to suspected power swing
phenomenon.
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 7
Single Line Diagram
Deliberations:
SRLDC:
• Though the fault was cleared in time, tripping of TS2 – Trichy line on account of power
swing is not a desired operation.
• The programme for disc insulator replacement needed to be given to the forum.
• Disc insulators had to be replaced positively before COD of the generating unit.
NLC:
• NLC displayed photographs of the switchyard with the affected component.
• Line between TS2 Expn. and TS2 is a very small line of 1.3 km length.
• Around 5,200 disc insulators have arrived for replacement in the yard.
• Disc insulator replacement programme would be finalized after discussing with M/s
BHEL.
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 8
SRPC:
• BHEL could be impressed upon for expeditious replacement of disc insulators in the
affected area for early restoration.
Recommendations
• NLC was requested to take up the replacement of the disc insulators issue with M/s
BHEL expeditiously.
O : 20.02.2014
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 9
Petition No. On this issue, we direct SR 01.06.2014
146/MP/2013 all RPCs to formulate Constituents
with I.A. patrolling
36/2013 protocol/guidelines by
1.6.2014.
O : 20.02.2014
Deliberations:
• In the PCSC meeting, timely compliance of the above was highlighted. Periodicity of
Reporting was also discussed and the constituents were requested to submit the progress of
implementation to SRPC and SRLDC as specified in the Hon'ble CERC Order dated 20th
February, 2014.
• Issue regarding non-furnishing of FIR/Trip Analysis Report, EL, DR, etc. was highlighted.
SRPC had taken up the issue under Clause 1.5 of IEGC vide letter dated 05.05.14 and
21.05.14. It was pointed out that the above reports were to be uploaded on SRLDC web
application within 24 hours as mandated in IEGC/CEA Regulations.
• It was informed to the PCSC forum that the Phase I Compliance status had been submitted to
Hon'ble CERC vide SRPC letter dated 26th May14 (Annexure III).
O : 22.02.2014
Petition No. We direct ISTS licensees PGCIL & To be collected
167/Suo- to submit details of ISTS
Motu/2012 updated distance Licensee
protection relay setting of latest by
O : 22.02.2014 all inter-regional lines 04.04.2014
with POSOCO & RPCs.
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 10
Deliberations:
• In the PCSC meeting the timely compliance of the above was highlighted.
• Periodicity of Reporting was discussed and the constituents were requested to submit the
progress of implementation to SRPC and SRLDC as specified in the Hon'ble CERC Order
dated 22.02.2014.
SRPC/SRLDC shall
submit a compliance
report in this regard
within four months of
issuing this order.
Deliberations:
• In the PCSC meeting the timely compliance of the above was highlighted.
• The periodicity of Reporting was discussed and the constituents were requested to submit the
progress of implementation to SRPC and SRLDC as specified in the Hon'ble CERC Order
dated 19.12.2013.
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 11
6 Implementing / Reviewing the Special Protection Schemes (SPS)
6.1 Review of SPS : 765 KV Raichur Sholapur-Line modified logic- KSEB agenda
The issues raised by KSEB regarding implementing the 765 KV Raichur - Sholapur SPS
modified logic had been discussed in detail in the Sub Group meeting of PCSC held on
28.05.2014. The Minutes of the Sub Group meeting is enclosed as Annexure IV.
Logic:
Contingency: One of 400 kV Kolar-Hosur D/C line trips and
flow on other Circuit > 850 MW
Action: Back down 500 MW import at HVDC Kolar and Shedding load in Tamil
Nadu as per Trip Signal 2.
Deliberations
• It was informed that the SPS had been discussed in the OCC meeting.
• SRTS-II, PGCIL informed that the SPS would be implemented after discussing the financial
issues of SPS in the Commercial Sub Committee.
• KSEB requested SRLDC to furnish the details of Loads identified for tripping while
implementing the SPS.
6.3 SPS for PGCIL 400 KV Mysore and 400 KV Kalavindapattu S/S
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 12
6.4 SPS for Kudankulam Nuclear Power Station
Ø The issue was discussed in detail in the 29th PCSC and in the Special meeting held at SRPC
on 17.03.2014.
Deliberations
• KKNPP informed that instruction had been given to the operators in the control room to
carry out manual ramp down at the rate of 50 MW/minute. It would take around 5 to 6
minutes for 300 MW ramp down.
• SRLDC desired that ramp down be carried out automatically through soft logic.
Recommendation:
PCSC Deliberations
Ø The PCSC forum advised NPCIL, KKNPP to implement the Single Phase Auto Reclose
Scheme at the earliest and the same be communicated to the forum with in a week's
time.
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 13
11 The issue of quantum of df/dt relief in SR
In the 29th PCSC meeting SRLDC informed that the df/dt settings in the Southern Region
would be revised from the month April 2014 due to Synchronization of SR with NEW Grid.
Deliberations
• SRLDC proposed for the following df/dt settings in the SR.
• Stage-1 : 49.9Hz & 0.1 Hz/sec
• Stage-2 : 49.9Hz & 0.2 Hz/sec
• The detail as submitted by SRLDC / POSOCO is enclosed herewith as Annexure VI.
• The PCSC forum decided to discuss the issue in detail in Sub Group meeting / the next
PCSC.
12 Submission of completed dynamic study data
All SLDCs were requested to direct the embedded IPPs connected at 220 kV and above voltage
level to submit completed dynamic study format to SRPC, Secretariat.
Deliberations
• The pending units would be circulated in the agenda of the 33rd PCSC.
*****
Minutes of the 32nd Protection Coordination Sub Committee Meeting held on 29.05.2014 Page 14
ANNEXURE I (1/5)
ANNEXURE I (2/5)
ANNEXURE I (3/5)
ANNEXURE I (4/5
ANNEXURE I (5/5)
ANNEXURE II (1/16)
1
ANNEXURE II (2/16)
But, BFR of Q50 CB of CWD20 dia also operated that led to opening of Q51 CB of CWD20 dia and sending DT to remote Jeypore-I end for
tripping the line.
PGICL:
• Insulators are being cleaned once in six months.
• Even after opening the CBs Q50 and Q51 of CWD 20 dia, current conduction was there for 500 msec due to pollutants in the area, which could
have resulted in LBB operation of the Q50 CB.
SRLDC:
• When was the filter banks of the pole cleaned last time?
• A detailed report from PGCIL is required for analysis of the event.
NTPC:
• LBB (BFR) should also give re-trip command to the breaker.
PCSC Recommendations :
• PGCIL shall submit a detailed report on the tripping incident by 6th June, 2014.
3
ANNEXURE II
APTRANSCO:
• O/C and LBB did not operate at AP end.
• The bus sectionalizer CB is belonging to
AP.
SRLDC:
• Though CB tripped, it could not be
found in the event logger.
• PGCIL is required to revise the zone-2
settings at NPS.
PCSC Recommendation
Ø Both APTRANSCO and PGCIL have
to submit a detailed report by
10.6.2014.
Ø PGCIL is requested to revise the zone-
2 settings at NPS.
400KV 22-04-2014 Tripped at Nellore (A.P) end only SRLDC:
Krishnapatnam- at 5:27 hrs on Y-Phase to Ground fault.
• On the two feeders of Krishnapatnam-
Nellore(A.P) line-1
Manubolu (Nellore(AP)) implementing
5 GI-2
“weak-in feed logic” or energizing both the
feeders would be an appropriate action to
avoid one end tripping.
Tripping of 400kV 02-05-2014 Broken conductor feature in main- KPTCL:
NCTPS-Vallur 2 distance relay operated which
• Broken conductor detection and protection
line-2 resulted in tripping of line
is managed by undercurrent sensing
6 principle by electromagnetic relay or GI-2
negative phase sequence (NPS) sensing
principle by electromagnetic and
numerical relays.
• KPTCL employs only alarm for broken
4
ANNEXURE II
conductor protection.
• For generating stations, instead of line
NPS, generator NPS could be employed for
broken conductor detection.
TANTRANSCO:
• NPS setting is 20% and 5 sec time delay.
NTECL:
• NPS is not enabled at Vallur.
SRLDC:
• The practice of having only alarm for
broken conductor protection has to be
reviewed.
Tripping of 400kV 03-05-2014 Y-B phase fault had occurred in SRLDC:
Raichur(PG)-Gooty at 16:52 hrs 400kVRaichur-Gooty line-2.
• POR scheme is already there.
line-1&2, 400kV Distance protection over-reached
Raichur- • Time stamps of events in SOE sent to
at Raichur TPS end for 400kV
SRLDC is appeared to be incorrect.
Raichur(PG) line-1 Raichur-Raichur (PG) line-1 and
At Gooty end for 400kV Raichur- • SOE of Raichur is not being sent to
Gooty line-1. SRLDC.
• Even after 20 days of issuing notice,
7 PGCIL has not yet replied on testing the GI-2
lines.
PGCIL:
Gooty 1 & 2 lines were tested and corrected
on 11.5.2014 and Raichur lines would also be
tested .
5
ANNEXURE II
400kV 04-05-2014 Line tripped at Krishnapatnam end SRLDC:
Krishnapatnam- at 4:53 hrs only. D.R/ E.L were not furnished
• On the two feeders of Krishnapatnam -
Nellore line-2
Manubolu implementing “weak-infeed
8 GI-2
logic” or energising both the feeders
would be an appropriate action to avoid
one end tripping.
400/220kV ICT-2 05-05-2014 ICT-2 tripped on operation of over SRLDC:
at Satenapalli at 12:25hrs flux protection. D.R and E.L not
• Over flux protection should trigger the DR
furnished
and APTRANSCO should do wiring for
9 GI-2
DR triggering.
• DR and EL reports are to be submitted by
APTRANSCO
Tripping of 400kV 05-05-2014 Y-phase to earth fault had **
Kudankulam- at 23:47 hrs occurred near to Kudankulam. R-
Madurai line and B-Pole of breaker tripped
750ms after tripping of Y-Pole
10 GI-2
breaker at Madurai. The carrier
aided protection at Madurai end
and healthiness of PLCC link
needs to be tested
**
32nd PCSC Deliberations & Recommendations
• It is noted that there was a Y-phase to earth fault near KKNPP end and the line tripped in Zone-1 at KKNPP and Zone-2 in Madurai
end.
• Despite sending carrier from KKNPP, Madurai end did not receive it and without auto reclosing tripped in Zone-2.
NPCIL:
• There was no fault on the Madurai – Kudankulam line.
• After successful implementation of auto reclose for one and half breaker scheme at Rajasthan Atomic Power Plant, the same
would be implemented at KKNPP.
6
ANNEXURE II
PGCIL:
• If pressure in the CB is less than 32 kg/cm2, then there would be a lock out; if it is about 30.5 kg/cm2 then it would give auto
reclose lock out.
• There was a problem with pressure switch of the circuit breaker on the Madurai-Kudankulam line and it has been rectified.
SRLDC:
• Power plant like NLC’s TS2 has implemented auto reclose feature on the evacuating lines.
• The schedule for completing auto reclose feature at Rajasthan Atomic Power Plant and then at KKNPP shall be intimated by
NPCIL before next PCSC meeting.
Recommendations
Ø NPCIL is requested to inform the PCSC forum regarding the implementation schedule of auto reclose feautre at Rajasthan Atomic
Power Plant and KKNPP.
220kV 13-05-2014 Tripped at Chittoor end only on R- • ICT is in radial mode and at the tail end no GI-2
Chittoor - at 15:26 hrs Phase to ground, Zone-3 fault. (LV source to feed the fault.
11 Tiruvalum Rph CT of 100MVA-3 blasted at
Tiruvalum) TANTRANSCO:
220kV 14-05-2014 Reason to be furnished • At 110 kV system at Tiruvalum, there is no GI-2
Chittoor - at 11:23 hrs bus bar protection implemented.
12
Tiruvalum
APTRANSCO:
220kV 16-05-2014 Tripped at Chittoor • O/C setting of the line is 208 MW. GI-2
Chittoor - at 10:45hrs end due to operation
Tiruvalum of Over Load relay SRLDC:
• Delayed clearance of fault needs
13 explanation.
• As CT is on the bus side, the bus bar
protection should have operated.
• On 28.5.2014 there was a lock out of CB at
7
ANNEXURE II
Tiruvalum. Code was issued at 4.00 PM to
trip Chittoor- Tiruvalum line but until 7.00
PM the code was not executed. Without
tripping the line and continuing to feed the
load is not correct operation.
Date &
S. No. Element Reason/ Deliberation
Time
400kV Srisailam-Mamidipally line 20-04-2014 @ 02:36hrs Line tripped on over voltage at Srisailam. No D.R
1 furnished
400kV Kaiga-Guttur line-2 04-05-2014 at 00:05 hrs Overvoltage operated at Guttur. No D.R furnished.
2
PGCIL:
• DR is not there and so events are not validated.
• Wiring to trigger DR for DT from remote end is to be done at KGS end.
KGS:
16 times DT was received from remote end and the line tripped on O/V during the month of May-2014.
KPTCL:
8
ANNEXURE II
The numerical relay on the line is Areva P437. Timing and pickup ratio in the relay would be tested.
3 400kV Srisailam-Mamidapalli-2 04-05-2014 at 00:14 hrs Line tripped on over voltage at Srisailam.
4 400kV Srisailam-Sarenapalli-2 04-05-2014 at 00:14 hrs Line tripped on over voltage at Srisailam.
400kV VTPS-Satenapalli line-2 04-05-2014 at 17:54 hrs Over voltage protection at VTPS end. D.R not
5
furnished
6 400kV Kaiga-Guttur line-1 05-05-2014 at 18:03 hrs Overvoltage operated at Guttur. No D.R furnished.
7 400kV Vijayawada-Gazuwaka line-1 05-05-2014 at 20:29hrs Drop of to pick up ration of relay to be checked
400kV Krishnapatnam-Nellore(AP)-2 06-05-2014 at 11:52 hrs Over voltage protection operated at Krishnapatnam.
8
No D.R furnished
400 kV Kaiga-Guttur- 2 08-05-2014 at 13:55 hrs Over voltage protection operated at Guttur. No D.R
9
furnished
400 kV Kaiga-Guttur-2 08-05-2014 at 17:30 hrs Over voltage protection operated at Guttur. No D.R
10
furnished
400kV Talaguppa-Hassan 09-05-2014 at 1:26 hrs over voltage protection had
11
Operated at Talaguppa end. No D.R furnished
400kV Srisailam-Mamidipally line-1 09-05-2014 at 02:53hrs Line tripped on over voltage at Srisailam. D.R not
12
furnished
220kV Idukki-Udumalpet line 19-04-2014 at 17:32 R-Phase to earth fault. Line auto reclosed at Udumalpet
1
hrs end and failed to reclose at Idukki end
9
ANNEXURE II
2 400kV Krishnapatnam-Nellore line-1 20-04-2014 at 2:40 R-phase to ground fault. Line did not auto reclose.
3 400kVKrishnapatnam-Nellore line-2 20-04-2014 at 3:20 R-phase to ground fault. Line did not auto reclose.
400kV Krishnapatnam-Nellore line- 21-04-2014 at 2:48 R-phase to ground fault. Line did not auto reclose.
4
1&2 hrs
400kV Guttur-Narendra line-1 28-04-2014 at 2:25 Y-phase to ground fault. Line auto reclosed at Narendra
5
hrs but failed to auto reclose at Guttur end
400kV Ramagundam-Chandrapur 28-04-2014 at 14:46 R-phase to earth fault had occurred in line. Line did not
6
line – 1 hrs auto reclose
NTPC:
• Auto reclose feature is not in service on Ramagundam – Chandrapur line due HVDC back-to-back link at
Chandrapur. It was informed that HVDC link faces problem if there is auto-reclose feature.
• It was informed that nowhere in the country, 3-phase auto reclose is implemented for the lines at generating
station.
• NTPC informed that sending DT for the earth fault at Chandrapur end is not a correct operation.
PGCIL:
• Problematic protection coupler is to be replaced for the line.
• 3-phase auto reclose feature is implemented on the Gazuwaka-Jeypore which is having HVDC back-to-back at
Gazuwaka. Synchro check is done and 1-phase auto reclose is converted into 3-phase auto reclose.
SRLDC:
• 3-phase auto reclose feature implemented on Gazuwaka-Jeypore line is not known to SRLDC and it is not clear
under what conditions it was approved. However, SRLDC recommends 1-phase auto reclose
MS i/c:
• PGCIL should come back with a plan for implementing auto reclose feature on Ramagundam – Chandrapur line.
400kVGuttur-Narendra line-2 30-04-2014 at 20:19 R-phase to ground fault. Line auto reclosed at Narendra
7 hrs end
but failed to reclose at Guttur end
10
ANNEXURE II
KPTCL:
• Bays are maintained by PGCIL at Narendra.
PGCIL
• Relays were checked individually but the scheme of auto reclose is not yet checked. It will be done after taking
the line shutdown.
400kV NCTPS-Vallur line-1 02-05-2014 at 22:58 R-phase to ground fault. Line did not auto reclose.
8
hrs
NTECL:
• During the grid disturbance, auto reclose feature was disabled at NCTPS side.
• Protection settings in Main-2 are changed and auto reclose is in service.
SRLDC:
• Within next PCSC meeting, TANTRANSCO and NTECL shall submit the details of auto reclose feature
implementation plan.
400kV Raichur-BTPS line 03-05-2014 at 15:42 B-phase to ground fault. Line did not auto reclose.
9
hrs
400kV NCTPS-Vallur-2 04-5-2014 at 4:53 R-phase to ground fault. Line did not auto reclose.
10
hrs
11 400kV NCTPS-Vallur-1 04-05-2014 4:59hrs R-phase to ground fault. Line did not auto reclose.
400kV Almathy-Vallur line-2 05-05-2014 at B-Phase to earth fault
12
05:33hrs
MAPS,NPCIL had sent the following agenda for discussion in the PCSC forum.
11
ANNEXURE II
There are many line trips during the past which is cause of Concern to them as some of the equipment's are tripping and sometimes AVR of generator
is changing over to manual.
S.No Date & Description
Reason/
time of Deliberation
event
Line-1
1 19.04.2014 Line got tripped at 09:45 hrs with following alarms: Spurious trip as
1) 514-L1 main protection trip, exact reason could
2) 514-L1 trip and lock out, not be found
Relays flagged: 86 RX,YX,BX, 86RZ,YZ,BZ,Y3ZM1,Y3ZM2,186A,186B
MAINS-1 MICOM: R TRI,Y TRIP,B TRIP ZONE-1
Fault Location:1.3Km. Duration:100 milli sec.
MAINS-2 MICOM Y Trip. ZONE-1, distance 1.7Km
Relays flagged at ARNI END: A,B,C phase trip, Zone-1,2.15 Km,Mains-2 Zone-1
Duration:54.98 milli sec.
SP koil end Mains-2 protection operated, R&B phase carrier failure,14 KV dip in grid voltage
was realized at the time of line-1 trip.
1OVRX was flagged in Unit-1 and 2 and the same was reset. 6.6KV BUS E voltage dipped
from 6.59 KV to 6.48KV
During the line-1 trip following alarms appeared/observation/action taken in unit-1/2
1.Line 2 current went to >600amps and line 3 current got increased.
2.Unit-2 generation was lowered from 175 to 170 mW(e) by reducing
Reactor further and further lowered to 158 MW(e) by steam dumping with small steam dumping
for about 5 minutes. LD Chennai was contacted and Line- 4 Acharapakkam end breaker which
was in open condition was closed. Later unit-2 generation was normalized after closing the
steam dump valve and raising the reactor power.
3. EM carried out visual inspection on line-1 at Ist tower and found normal. After getting LD
Chennai clearance, Line-1 was test charged from SP koil end at 11:24hrs. At 11:55hrs line-1
was tied from MAPS end.
2 11.05.2014 At 11:33 hrs 230 kV SP koil line 1 got tripped with Line 1 Main protection trip and trip and Line fault
12
ANNEXURE II
lockout were in. The relays flagged are
Main I : R/Y/B TRIP ZONE 1, started phase C, Fault duration 58.19 millisecond, Relay trip
time 149 milisec,location 3.038 KM 86RX,86YX,86BX,186A,186B,Y3M1,Y3M2,COX-2,
60X-2 in unit 2
MAIN II : B-TRIP,ZONE-1,SOTF,Starter acted were in.
Line 1 was inspected up to first tower and found normal. All relays were reset and it was test
charged from SP koil end found not holding. Declared faulty. Line-1 was taken to service
at 2000 hrs.
Line-2
1 05.04.2014 Line-2 got tripped at 1307hrs on B-phase to ground on zone-1 protection(9.451KM). After Spurious trip as
inspecting S/Y, line-2 was charged back at 1345hrs. exact reason could
not be found
2 15.05.2014 At 12.00hrs 230 KV Line-2 Tripped with following alarms: Spurious trip as
1) 514-L2 main protection trip, exact reason could
2) 514-L2 trip and lock out, not be found
Relays flagged: 186,Y3M2, 85X4
In MAINS 1:
RYB Trip, ZONE -1 fault, started phase C, starter operated, over current. Fault location 32.88
km, fault resistance: 44.29 ohm, Fault duration: 79.97 sec. IA/IB/IC: 285.2A/129.5 A / 3.08 KA.
voltage: 119.3/122.5/97.53kv.
In MAINS 2:
TRIP, B Trip, Distance: 14.3 km.
Line load current: L1/L3: 460/290 amps.
At SP koil end: Mains-I: CGQ, INST, EL, 19.64 km, oc-50
Line was inspected in switchyard and up to first tower and
found normal. Relays were reset and line was taken in to service at 13.05 hrs.
Line load current: L1/l2/L3: 250/230/250 amps.
Line-3
1 12.01.2014 Emergency shut down was taken to attend to glow in R-Phase of the line insulator near Arni end Glow at breaker
breaker. end
2 29.03.2014 Got tripped on Zone-1 R-Phase to earth fault at 0620hrs. As per ADE shift Arni conductor got Conductor
13
ANNEXURE II
snapped at Cheyyur. snapped
3 30.03.2014 Got tripped with alarms 230KV Line-3 Main protn trip Spurious trip as
and 230KV Line-3 trip and lock out. Tripped on Y-phase to earth fault. Zone-1. Distance: 18.43 exact reason could
KM. Line was inspected up to 1st tower and no abnormality was noticed. Line was test charged not be found
from Arani end and found holding. Line was taken to service
4 11.04.2014 Line3 got tripped with following alarms. Spurious trip as
Line 3 tripped and locked out. exact reason could
Line main trip and trip and lock out. not be found
Relays flagged: 186A,B starter operated,Y3Z,M1,M2
86RX,Yx,Bx mains-1: R trip,Y trip, B trip VAN/BN/CN:
123.7/123.7/101.3KV. Zone-1: 9.4 Km. Fault current: 317A/216A/3.56KA
Mains -2:86YZ,86RZ,B trip zone-1 5.5 Km. At 13:06 line was test charged from ARNI end
found holding. It was tied from our end at 13:08 hrs.
5 20.04.2014 As per Arani SS, 230 KV Kalpakkam-Arani line B-Phase wave trap area line glow observed Glow at wave trap
hence 230 KV Kalpakkam-Acharapakkam line-4 breaker at Acharapakkam end closed at 10.30
hrs. 230 KV Kalpakkam-Arani line breaker at both end opened to attend the deficiency
6 01.05.2014 Line-3 which got tripped with 230KV Line-3 main protection trip and 230KV Line-3 trip and Spurious trip as
lock out alarms at 14:07 hrs. 8 KV dip in voltage was noticed. 1OVR relay flagged in both units exact reason could
and was reset. 230 KV Kalpakkam-Arni feeder-3 was checked upto Ist tower and found not be found
normal.230 KV line-3 was test charged from ARNI end found holding. It was tied from our end
at 14:50 hrs
7 03.05.2014 Arni feeder lin3 got tripped at 13.33 hrs on R phase fault, zone1, with 17.3 Km distance. Relays Spurious trip as
were reset and test charge done. As test charge was holding, Line taken back to service at 13.58 exact reason could
hrs not be found
8 06.05.2014 230 KV Line-3 tripped at 0755hrs on B phase to earth fault.Zone-2 distance protection Spurious trip as
(27KM)was operated/Y up to Ist tower was checked and found no abnormality.Line-3 was test exact reason could
charged from Arani end and found line is holding. At 830hrs Line-3 was taken to service. not be found
Line-4
1 04.05.2014 At 08:16 hrs 230 KV Acharapakkam LINE-4 got tripped on main protection. B phase fault at Line conductor got
3.5 Km recorded with 5 KV dip in system. cut
Relays flagged :
14
ANNEXURE II (15/16)
Main 1 : Zone 1, R,Y,B TRIP, Distance 3.524 Km, duration 59.94 milliseconds, Ic 10.5 Kilo
Amps, Vcn : 33.35 KV.
MAIN 2 : B-TRIP, Zone 1 send.
230 KV protection panel :
86RX,86YX,86BX,86RZ,86YZ,86BZ, Starter operated Y3M1,Y3M2.
-Line 4 was inspected in switchyard and up to 1st tower. Test charge was done from
Acharapakkam end, found not holding. Hence line declared faulty and permit given for
inspection by EB. Rain and lightning exists at site during the time. Later CISF reported that line
got cut from the first tower after the road crossing near the first circle. SE LD center, AD shift
Acharapakkam, AD lines SP koil were informed. Line 4 was isolated and Earth switch is kept
close and LC is given.
-During Line4 tripping time, Unit1 AVR got changed over to Manual with alarm "Excitation
protection changeover channel 1-2", House load permissive contact faulty were in. In DVR
panel UN-665(AB 61)
LED 21 - Protection changeover, LED-25 Channel -1 PT fuse failure,
In UN-665(AB-65) for channel 2 LED 25 PT fuse failure were glowing.
Relays 60X1 and 60X2 were found flagged and were reset. House load HS is selected to bypass.
Excitation relay 1 OVR was reset.
-EM checked the Generator PT output MCBs at 110 V side voltage for AVR and protection
channel were found normal at 102 volts. DVR input terminal voltages were checked and found
normal. Alarms were reset from micro tech panel by pressing Release reset and Acknowledge
/reset PBs. Alarms got cleared.
-AVR was changed over to auto channel 1 at 11.05 hrs. The response is checked & found
normal. House load HS is selected to NORMAL.
2 14.05.2014 Acharapakkam line was isolated for attending R phase conductor as it got detached from the R-ph conductor cut
suspension insulator by TNEB personnel. R phase suspension insulator was replaced by TNEB
staff. Acharapakkam end line DS sparking problem being attended by TNEB staff .Line was
taken in to service at 1650hrs on 15.05.2014.
On 22-05-2014, U-1 was operating at 165 MW(E) and U-2 was operating at 168 MW(E) At 13.08hrs both units came on house load operation due
to sudden grid frequency dip from 49.92 to 47.65Hz. 230kV grid supply was found lost. During the units are on house load operation, U-1 PHT
15
ANNEXURE II (16/16)
pump -7 got tripped on protection. In consequence to pump tripping reactor got tripped resulting in unit outage. Unit-2 was synchronized after grid
normalization at 13.36hrs.
Total 8 no of line trips could not be justified & 6 no's of incidents were line faults.
MAPS:
• There were 18 outages recently due to spurious trippings. Arani line alone tripped about 5 times.
• Arani line is tripping frequently without any fault on the line and the fault distance is known.
• On many occasions during the line trip and subsequent voltage dip effect, the AVR of the generating unit is switching over from automatic to
manual mode on its own. When the voltage becomes normal, AVR is taken from manual to automatic mode manually.
• TANTRANSCO was requested to carry out line patrolling for locating any trouble spots, if any.
• On 22.5.2015, two units at Kalpakkam went on house load.
• From MAPS to TANTRANSCO, there are two lines to Singamperumal (SP) Koil, one line each to Arani and Acharapakkam.
• On 22.5.2014, TANTRANSCO lines (i.e. SP Koil lines-1&2) were radially drawing a load of 450 MW while MAPS was generating around 330
MW. Since there is no connectivity to grid for MAPS, momentarily there was an island formation with 330 MW generation and 450 MW load
which could not sustain and the generating units at MAPS went on house load on account of u/f operation at 47.65 hz after opening the GCB of
the units.
• MAPS opined that had Acharapakkam line been there, the incident could have been prevented.
MS i/c:
• If any Line Clearance (LC) is there in that area for maintenance, then further opening of the lines have to be restricted for avoiding undesired
island formation of MAPS generation with TANTRANSCO loads.
• The MAPS islanding issue would be discussed in the next PCSC meeting.
*****
16
ANNEXURE III (1/59)
ANNEXURE III (2/59)
ANNEXURE III (3/59)
Annexure
Phase-1
S. Name of Substation Details of work Status of Implementation of Phase I
N Recommndations
POWERGRID
1 400 KV Arasur Substation Distance protection Zone-2 & Zone-3 timing of 230 complied
KV feeders need review
Electromagnetic back up directional O/C and E/F All Distance protections, ICT Differential
relays to be replaced with numerical relays on ICT- and Reactor B/U protections are
1. provided with Numerical relays.
1
Pld PLCC protection couplers to be replaced with PLCC protection couplers are healthy
new protection couplers and providing trouble free service. In
case of any complaints same shall be
addressed accordingly.
Static bus bar protection relay to be replaced with Replacement of bus bar relays with
numerical relays numerical is not contemplated in the
gazette notification
7 400 kV Kadapa Substation Electromagnetic and static relays for ICTs, All Distance protections, ICT Differential
Reactor, Bus bar,over voltage, distance protection and Reactor B/U protections are
to be replaced with numerical relays. provided with Numerical relays.
However Numerical Busbar protection
is not envisaged as per Gazzett
notifications.
8 400 kV Kalivanthapattu S/S 230 kV feeder distance protection Zone-2 and complied
Zone-3 timings need review
9 400 KV Khammam Substation Old Static line protection (Distance) relays to be complied
replaced with numerical relays
2
11 400 kV Mysore Substation Replacement of static relays (THR, CAG, RADHA complied
etc.) with numerical relays to be looked into.
12 400 KV Narendra Substation Plug setting multiplier setting of back up over complied
current relays of CTs to be reviewed.
13 400 kV Puducherry Substation Zone-2 & Zone-3 time settings of distance complied
protection relays of 230kV feeders need review.
LBB & Bus Bar protection are in-built in the same In built busbar and LBB protection in
Siemens SIPROTEC 75552 Relay for both Main 1 station bus bar protection scheme is a
& 2. Same needs review general practice being followed in all
SAS based substation and this is as per
the latest practice in protection system
3
15 400 kV Salem Substation Static distance protection relays of 400 kV feeders complied
to be replaced with numerical relays
18 400 KV Vijayawada (NUNNA) Old Static line protection (Distance) relays to be complied
Substation replaced with numerical relays.
Monitoring source to be provided for DC earth DC Earth fault relay is already available.
leakage to be provided Complied,
19 400kV Kochi Substation Over voltage protection time setting to be reviewed complied
4
21 400kV N'Sagar (Tallapalli) Old relays to be replaced with numerical relays for complied
Substation feeders, ICTs and Reactors.
NTPC
1 220 kV Kayamkulam Zone-2 and Zone-3 timings of distance protection complied
relays need review.
5
Existing micro mho distant protection (Main I) Relays received at site. Erection will be
relays to be retrofitted with numerical relay. taken up.
2 400 kV NLC TPS-II Expn. O/V protection for stage-II time setting to be Complied
revised for instantaneous trip
NPCIL
1 220 KV Kaiga-Generating The line relays 220 KV side are provided with 01 The settings will be implemented
Station-1&2 primary protection ie. Static Relay, and a back up subsequent to the approval at the
relay is to electro mechanical relay with high set. staion at the earliest oppurtunity.
Blocking of High set protection in the back up relay
needs to be reviewed. NPCIL-Kaiga to review the
same
Instead of Static Relays, Numerical Relays to be Action has been initated for
provided with different make for all lines as Main-I procurement of Numerical relays
and Main-II. NPCIL-Kaiga to review the same (Micom-P442 and Micom -P443 ).
Replacement of existing static type
relay (EE,SHPM101) with numerical
relays as Main -I and Main -II will be
implemented upon receipt of material at
Kaiga site.
6
Tamilnadu - TRANSCO/ GEDCO/ IPP
1 230 kV Arni Substation Static relays are to be replaced with numerical Procurement action initiated. Further
relays tender process could not be carried out
due to Election code of conduct. Time
extension requested upto October
2014.
V/F protection for transformers to be made Will be provided.
available
REF protection to be implemented for Neutral CT is arranged to be provided.
Transformers (Capacity below 100 MVA) Numerical diffl. Relay will be provided.
No Earth fault protection on HV & LV side of E/F settings for AUTOs not being
transformer. Same to be provided adopted in Tantransco.
Separate earthing for DC system (110 V DC) to be Estimte got sanctioned. Work under
provided progress.
Only Bus PT supply is available for Main I & II Line CVT to be provided in all feeders
protection, no line VT supply is available for and will be taken up in second phase.
protection. Same needs review
7
No Capacitor Tripping Devices are kept in service Due to nuisance trippings Capacitor
for Feeders and Transformers. Same needs review trip device is disabled.
Relay settings for feeders and transformers need Being reviewed whenever needed.
review
Time synchronising with GPS to be provided for Time synchronising with GPS provided
230kV protection system and is in service.
3 230 kV Ennore (ETPS) Earth fault relay to be provided on HV & LV sides E/F settings for AUTOs not being
of Auto t/p # 1, 2 and TO # 3 t/f. Over fluxing adopted in Tantransco.
relayto be provided.
OT1 and WT1 indicators suspected for not Defects rectified and indication
working. Same needs to be rectified. available now.
PRV device to be made available on Auto T/f # 1 PRV available in Auto 1. Explosion vent
and 2. available in Auto 2.
Surge counters to be made available on lightening Surge counters available in 110kV
arrestor. LAS.Action is taken for provision in
230kV LAS.
DC earthing in 220V DC system to be rectified Earthing checked and rectified.
Zone-2 timing of distance protection relay of 23kV Zone 2 time delay 350mSec as per
kines need review SRPC recommendation.
4 230 kV Gobi Substation REF protection to be made available. REF protection enabled.
8
Time synchronising with GPS to be provided for
protection relays.
Procurement action initiated. Further
Static distance relay to be replaced with numerical
tender process could not be carried out
relays.
due to Election code of conduct. Time
Diiferent type and Make of distance protection extension requested upto October
relays to be provided for Main-I & Main-II protection 2014.
for 230kV Arasur feeder.
5 230 kV Hi-Tech Carbon Co- Earthing system to be improved. Additional earth pits being provided.
Gen.
Dedicated hot line speech facility to SLDC to be May not be insisted since the
established. connectivity is for 33.7MW and in
110kV level.
6 230 kV Ingur Substation Time synchronising with GPS to be provided for
protection relays.
Static distance relay to be replaced with numerical
relays. Procurement action initiated. Further
Diiferent type and Make of distance protection tender process could not be carried out
relays to be provided for Main-I & Main-II protection due to Election code of conduct. Time
for 230kV Arasur and K.R.Thoppur feeders. extension requested upto October
2014.
7 230 kV Kayathar Substation Earth resistance to be measured and recorded. Earth resistance is measured and
recorded.(0.6 ohms)
No E/L relay protection on ATR 1, 2 & 3 HVs. E/F settings for AUTOs not being
Same to be provided adopted in Tantransco.
9
V/F protection is not available on ATR-1, 2 & 3. Will be enabled.
Same to be provided.
Different type and Make of distance protection Procurement action initiated. Further
relays to be provided for Main-I & Main-II protection tender process could not be carried out
for 230kV feeders due to Election code of conduct. Time
extension requested upto October
2014.
Only Bus PT supply is available for Main I & II Bus PT used for protection in all the
protection. There is no line VT supply available for stations. Procurement action for
protection. Same to be reviewed and rectified. provision for Line CVT is under
process.
No capacitor tripping devices are provided on 230 Due to nuisance trippings Capacitor
kV feeders & ATRs. Provision for the same to be trip device is disabled.
done
Relay settings for feeders and transformers need Reviewed whenever needed
review
Time synchronising with GPS to be provided for Procurement action initiated. Further
230kV protection system tender process could not be carried out
due to Election code of conduct. Time
extension requested upto October
2014.
9 230 kV Madurai Substation Time synchronising with GPS to be provided for Procurement action initiated. Further
(Alandur) protection relays. tender process could not be carried out
due to Election code of conduct. Time
extension requested upto October
Static distance protection relays to be replaced with
2014.
numerical relays.
10
10 230 kV Manali Substation O/C and E/f relay setting on HV & LV sides of both Uniform setting adopted
auto transformers need review.
Diiferent type and Make of distance protection Procurement action initiated. Further
relays for Main-I & Main-II protection to be provided tender process could not be carried out
for 230kV feeders due to Election code of conduct. Time
extension requested upto October
2014.
11 230 kV Mylapore Substation Carrier scheme to be provided for 230kV Basi Fibre laying is under progress
bridge feeder
No Earth fault protection on HV & LV side. Same to E/F settings for AUTOs not being
be reviewed and provided adopted in Tantransco.
Earth leakage monitoring system to be provided Earth leakage monitoring provided
Separate earthing for 220 V & 48V DC system to Work under progress.
be provided
Only Bus PT supply is available for Main I & II Bus PT used for protection in all the
protection, no line VT supply is available for stations.
protection. Same needs review
11
No Capacitor Tripping Devices are kept in service Due to nuisance trippings Capacitor
for Feeders and Transformers. Same needs review trip device is disabled.
12 230 kV North Chennai TPS CTD protection to be provided in all 230KV feeders Due to nuisance trippings Capacitor
and Transformers. trip device is disabled.
Different type and Make of distance protection Procurement action initiated. Further
relays to be provided for Main-I & Main-II protection tender process could not be carried out
for 230kV feeders due to Election code of conduct. Time
extension requested upto October
2014.
12
15 230 kV Singaperumal Koil Trip circuit supervision relay to be provided for both R&M work will be done.
Substation trip coils for 230 kV Veerapuram, 230 kV
Kalpakkam, 230 kV Kalivanthapattu, 230 kV
Oragadam, 230/110 kV Auto 1 HV side
230 kV Singaperumal Koil Provision for supervision of all the trip coils through -
Substation the TSR relay to be examined.
It is found that relays of the same C&R panels are R&M work will be done.
placed in different locations of other C&R panels in
many bays. It is very difficult for the SS operator to
identify the relays during emergency condition.
Hence relays shall be placed on the respective
feeder panel to be examined.
TMS of auto transformers for over currrent relays Uniform setting adopted
(HV/LV) to be reviewed and corrected
Since the length of 230 kV Veerapuram line is Numerical relay available and
around 650 mts, sensitivity of performance of performance satisfactory
distance protection for that shortest line needs to
be examined.
13
Carrier aided protection scheme to be provided for Fibre laying is under progress. Aided
230 kV Oragadam feeder protection will be provided by June
2014.
Provsion for Direct trip transmission signal on complied
operation of Bus bar/LBB relay for all the lines to
remote end to be provided.
Cable Duct near Auto transformer 3 needs to br R&M work will be done.
repaired
Over flux protection to be provided for Auto Procurement action initiated. Further
transformers . tender process could not be carried out
due to Election code of conduct. Time
extension requested upto October
2014.
16 230 kV Thiruvalam Substation Battery earth leakage meters provided for DC Work will be takenup
source I & II are not in working condition. Same
needs to be rectified.
Non Directional Over Current relay with 150% on Uniform setting adopted
both sides of all Auto Transformers are provided.
Earth fault relay on both side are not adopted.
Same needs review.
17 230 kV Tondiarpet Substation Transmission line earth wire not connected to SS Work will be takenup
earth mat at Tondiarpet. Same needs review and
rectification
14
100 MVA, 230/110 kV transformer # 1 &2, back up Uniform setting adopted for O/C. E/F
O/C relays setting need review. Earth fault relays settings for AUTOs not being adopted
to be provided on both HV & LV side of ICT's in Tantransco
18 230kV Mettur Thermal Power Main-I and Main-II protection schemes to be fed Work will be takenup on availing LC
Station from separate DC source. Provision for the same
to be done.
PLCC protection coupler to be made available for Procurement action initiated. Further
MTPS-Stage-III and MTPH feeders. tender process could not be carried out
due to Election code of conduct. Time
extension requested upto October
2014.
Synchronisation cores of Line VT and Bus VT are Reviewed
of different voltage ratios and same needs review
Time synchronising with GPS to be provided for Procurement action initiated. Further
protection relays. tender process could not be carried out
due to Election code of conduct. Time
extension requested upto October
15
Both Main-1& Main-2 distance protection relays of extension requested upto October
230 kV feeders to are be of numerical type. Static 2014.
distance relays to be replaced with numerical
relays.
19 230kV Singarapettai Substation Zone separation for Bus Bar Protection needs to Estimate sent for approval.
be done. .
20 400 kV Alamathy Substation Time synchronising with GPS to be provided for Procurement action initiated. Further
400 & 230kV protection system tender process could not be carried out
due to Election code of conduct. Time
extension requested upto October
2014.
Different type and Make of distance protection
relays to be provided for Main-I & Main-II protection
for 230kV feeders
16
22 400 kV Sunguvarchathiram Separate auxiliary relays for transformer mounted Will be provided.
protection.
Different type and Make of distance protection Procurement action initiated. Further
relays to be provided for Main-I & Main-II protection tender process could not be carried out
for 230kV feeders due to Election code of conduct. Time
extension requested upto October
2014.
The differential protection relay in ICTs has inbuilt As per norms one differential relay
function of differential protection, ref protection, provided.
overflux protection, aux. protection for transformer
mounted relays, breaker failure protection. So
provision for additional differential protection relay
with all the above in built function as a main-II to be
reviewd for improving reliability
Providing of Trip-Neutral-Close (TNC) switch for all TNC switch will be procured and
the bays in C&R panel for emergency operation connected.
17
Providing of "Stub protection" for 400 kV lines Provided for NCTPS 1&2. For SPDR
and Pondy feeders Stub protection will
be enabled during the Annual relay test
during 2014.
18
2 220 kV APGPCL - Stage-II All distance static relays should be retrofitted with -
Vijjeswaram GS latest version Distance Relays for quick and
accurate analysis for the tripping.
19
5 220 kV Chandrayanaghatta Replacement of existing Static Relays provided for
Distance Protection, diff protection with numerical
Indent under preparation
relays
20
6 220 kV Chittoor Substation Auto reclosure function is to be enabled for all 220
On 220KV feeders Auto recloser function
KV feeders.
not used in APTRANSCO system.
21
100MVA PTR-I, O/L Relay settings of HV and LV
side need to be reviewed As communicated recommended settings
are adopted
11 220 kV Jurala Generating Provision of differential protection for Jurala line 1 Fund mobilisation proposal is put up to
Station & 2 (line length-1.45 KM) feeders to be examined. board and procurement action will be
made soon after getting approval
The inbuilt disturbance recorder available in Referred to the OEM and its reply is
numerical relays to be activated awaited.
22
In adopted distance relay setting for Main 1 & Main Adopted as per recommended settings
2 for Jurala Line 1 & 2 one of the settings of piolet
directional protection i.e. PIL - Dis.resist ROZ is
0.24 ohms whereas recommended setting is 18.05
hms which is the major deviation.
PLCC panel is erected but not commissioned It is found that the same are not
suitable for indian system and
procurement is in progress
GPS time synchronisation for 220 kV switch yard Fund mobilisation proposal is put up to
protective relays to be provided board and procurement action will be
made soon after getting approval
12 220 kV KTPS SS A,B,C Unit (1- All Electro Static Relays to be replaced with latest
Relays Procured. It will be replaced in next
8) - Kothagudem version Numerical relays
shut down of the unit.
110V/220V DC source earth to be removed. Removed.
23
The old RAZOA (Electro Static) relays to be Replaced.
replaced with latest version Numerical relays
15 220 kV N'Sagar Station event logger to be made available Fund mobilisation proposal is put up to
board and procurement action will be
made soon after getting approval
No GPS is available. Time sync facility not Purchase order placed for the same
available. Same to be provided and will be commissioned soon after
procurement.
No A/R feature and no O/V feature is available. Provision is available and will be
Same to be provided activated if recommended.
There is only 3-phase tripping. No I-phase tripping. Provision is available and will be
Same to be reviewed and provided activated if recommended.
24
16 220 kV Ongole Substation Provision of additional 220kV battery charger
Provided battery charger
17 220 kV Rayalaseema TPS All static relays on feeders to be replaced with Procurement action will be made soon
nemerical distance relays after getting approval from APGENCO
The static Bus Bar Protection to be replaced with management.action will be made soon
Procurement
numerical relays after getting approval from APGENCO
Station Event logger to be madefunctional management.action will be made soon
Procurement
after getting approval from APGENCO
GPS time synchronisation of relays shall be made management.
Procurement action will be made soon
available. after getting approval from APGENCO
18 220 kV Renigunta Substation The carrier aided tripping not available in 220 kV management.
Indent under preparation
Nagari feeder
Auto reclosure function to be enabled for all
Under procurement and awaiting for budget.
220mkV feeders
Surge monitor for 220 kV C.K. Palli (R-Ph)and On 220KV feeders Auto recloser function
Nagari (B-ph) to be replaced not used in APTRANSCO system.
220 V battery charger to be made functional
Replaced
19 220 kV Samalkot Power Station Distance protection relay settings to be reviewed Reviewed and revised relay settings are
communicated and adopted.
PLCC Inter Tripping Scheme to be made functional
Carrier protection scheme is enabled.
25
Provision for O/V, U/F & df/dt protections for 220kV
feeders to be reviewed. O/V, U/F & df/dt protection features are not
used on 220KV feeders in APTRANSCO
system and O//V, U/F & df/dt relays are
provided on the identified feeders as per the
protection committee meeting directives.
26
100MVA PTR-III Existing LV directional earth fault
relay is to be made functional Made functional.
24 220 kV Srisailam Distance protection relay settings, power swing Settings are adopted as per
block settings to be reviewed for 220 kV lines APTRANSCO recommendations
Disturbance recorder, Station Event logger and Fund mobilisation proposal is put up to
GPS to be made available board and procurement action will be
made soon after getting approval
27
In N.Sagar line (P442) relay configuration of Settings are adopted as per
voltage protecgtion, CB failure and interval auto manufacturer recommendation and
reclose configuration disabled instead of enable APTRANSCO being consulted for
mode. KZ RES component and angle different review.
from approved setting. Same to be reviewed
All static relays like distance relay, differential relay Fund mobilisation proposal is put up to
and Bus-Bar relays to be replaced with latest board and procurement action will be
version numerical relays having inbuilt D.R made soon after getting approval
25 220 kV Srisailam power station The Generator differential protection, GT O/C+ E/F Except GT REF protection all other
(right bank) protection , GT REF Protection, Overflux protection protections were duplicated either in
, UAT O/C + E/F protection settings to be main-2 realy or through separate relay.
duplicated and provided in Main-2 relay for
increasing the reliability.
Older version of unit 4 Main-I & II relay (REG Replaced with REG670 relays
316*4) relay to be replaced with REG 670 or other
similar relay as provided for other units
GPS to be provided for time synchronization of GPS already procured and will be
protection system commissioned along with the
switchyard scada.
26 220 kV Sullurpet Substation Eroded flexible copper earthing provided between
CTs and structure of LV1& LV2 of 220/132kv
Rectified
Transformers to be rectified
28
PLCC equipment on 220kv Gummidipudi feeder to
be replaced/ retrofitted Inter State feeder (to be projected)
27 220 kV Tadikonda Dual earthing for CTs and CVTs 220KV VTS-1
feeder to be done Indent under progress
28 220 kV Vijayawada TPS Earth fault/Strips in 220 KV Switchyard are rusty, to Painting completed.
(Dr NTTPS) be bituminous painted.
29
Provision of overflux protection for transsformers
Provided.
Zone-III setting in Shadnagar feeder to be Zone-III settings are changed as per the
reviewed instructions of Power Systems Wing.
Zone-III Timing setting in Shamshabad-II to be
reviewed. Recommended settings are adopted
30
Distance protection relay setting to be reviewed
Recommended settings are adopted
Procurement of testing kit for testing switchyad Tan delta and universal relay testing kit
equipment . allotted
Replacement of Static differencial protection relays
provided for ICT-1&2 with numerical relays. Indent under preparation
33 400 kV Gajwel/Medak S/S / 400 315 MVA ICT-1 O/L relay setting of HV & LV to be -
kv side of 400/220 kv GAJWEL reviewed
SS
31
All the Numerical Protection relays to be time
synchronized with as the GPS. Provision for GPS Indent under preparation
to be done.
Review of Power swing detection settings Power swing detection settings were
corrected as per approved setting.
Generator Transformer over current & high set
Generator Transformer over current &
settings to be reviewed
highset values was corrected as per
approved settings.
36 400 kV GVK Gautami Power Auto reclose scheme to be eanbled for both 400 kV
feeders. Auto recloser scheme was enabled.
Over voltage stage-1 time setting of line-2 to be Deviation has been corrected as per
reviewed APTRANSCO approved relay setting [refer
to letter CE/IPC/112/F(Tech.Limits)
D.No.30/06 dt.26.04.2006].
Provision for under frequency and df/dt protections U/F & df/dt protection features are not used
to be reviewed on 400KV feeders in APTRANSCO system.
37 400 kV SS only Lanco The relays settings to be reviewed -
Kondapalli Power Ltd. Phase-II
38 400 kV Jegurupadu SS & 220 Auto reclose to be made functional for 400 kV
kV Jegurupadu SS(Gen) feeders Auto recloser scheme is enabled.
32
40 400 kV Konaseema Gas Power Over current relay High. Set value of STGT to be The over current relay high-set value of
Ltd. reviewed STGT has been changed from 9.5 to 7.5.
Over voltage stage-1 time delay settingto be The over voltage stage-1 time delay of
reviewed 400KV line#2 has been changed from 4sec
to 5sec.
Auto reclose to be made functional for 400 kV
To implement auto reclose scheme for
feeders
400KV line-1&2 breakers technical support
is required from OEM which is awaited.
41 400 kV Kothagudam TPP Configuration of SAS to be completed early for Procurement action will be made soon
Quick analysis of trippings. after getting approval from APGENCO
management.
Possibility of separate GPS for 400 KV Switch yard Procurement action will be made soon
control room to be provided after getting approval from APGENCO
management.
42 400 kV KTPS VI Possibility of separate GPS for 400 KV Switch yard Procurement action will be made soon
Switchyard/Paloncha - control room to be provided after getting approval from APGENCO
Kothagudem
management.
Directional Earth Fault settings of Lines may Letter addressed to APTRANSCO. Reply
reviewed on par with GT Back up O/C and Earth
Fault Relay.
awaited.
43 400 kV Kurnool (Nannur) Provision to be made for having different make
Substation distance relays for Main I & Main II protection for
Srisailam 400 kV feeders, 220 kV AP Carbides I & Indent under preparation
II, 220 KV Brahmanakottur feeder, Somayajulapalli
I & II
33
63 MVAR Bus Reactor (TEED-I) Siemens make,
Model 7UT613 the actual settings in "Power
Reviewed and recommended relay settings
System Data 2" is different from approved setting are adopted.
by APTRANSCO.
34
44 400 kV Mamidipally & 220 kV Distance protection relays for 400 kV and 220 kV
Mamidipally substation feeders to be replaced with numerical relays Indent under preparation
protection settings for relays to be reviewed Protection settings are reviewed and
adopted settings are as per APTRANSCO
Station Event logger to be made available protection philosophy. (Already furnished to
Staion E/L made available
35
ABB make distance relay of Type REL 316 to be
replaced Indent under preparation
46 400 kV Srisailam Power setting for excess power condenser mode Setting provided as per practical
relay in unit protection is to be reviewed requirement
Time setting of Dead Machine protection Relay to Setting provided as per practical
be reviewed. requirement
Setting of stub protection function in distance relay Same is informed to APTRANSCO and
to be reviewed the Settings issued by APTRANSCO
are adopted.
Timing of Zone-2 Relay setting for Nunnar, Same is informed to APTRANSCO and
Mamidapally and VTP-S to be re examined the Settings issued by APTRANSCO
are adopted.
Distance protection setting of Main-II Distance Fund mobilisation proposal is put up to
relay to be re-examined. board and procurement action will be
made soon after getting approval
Disturbance recorders (ABB Make Indactic) to be Purchase order placed for new DR
made functional evaluation unit and will be
commissioned soon after procurement.
36
Station Event logger to be time synchronised with Purchase order placed for the same
GPS. Provision for GPS to be made. and will be commissioned soon after
procurement.
Static Bus bar protection relay to e replaced with Purchase order placed for the same
numerical relay Relay. and will be commissioned soon after
procurement.
Generator Protection id displaying only fault data Fund mobilisation proposal is put up to
records, but no graphical representation with time board and procurement action will be
resolution upto milli sec. related to the made soon after getting approval
disturbances. Same to be reviewed
provisions of GPS to be done for time Purchase order placed for the same
synchronizing of protection system and will be commissioned soon after
procurement.
APTRANSCO
37
Karnataka - TRANSCO/ GEDCO/ IPP
1 220 kV Allipura Substation - All 220 kV line and bus coupler C&R panels The old C&R panels are being
BELLARY distance relays are retrofitted with ABB REL511 replaced by new panels. The tendering
relays & REL670 respctively, but the existing process is completed. Purchase order
panels back-up electromechanical relays are very is issued to M/s ER for supply of 220kV
old and sluggish, most of the TS relays are not control panels for Alipur Sub Station.
working properly, announciation not in working
condition. replacement of the relay panels.
For Ragulapadu line carrier inter tripping should be APTRANSCO has to confirm the
restored. availibility of equipments at
Ragalapadu.
For 100MVA-I No REF protection available and The C&R panel is being replaced.
over flux relay should be restored.
38
Main-2 protection is not available for all the 220 kV
lines. 220kV control and relay panels with
main-1 and main-2 distance protection
are being provided under R&M works.
3 220 kV BTPS Dead Earth fault in 220 V DC set 1 & 2. Earth Fault in 220 V DC circuit is traced
and rectified.
A/R Scheme for 220 kV Lines not available for For implementation of A/R scheme in
lines. 220 KV lines,M/s Alsthom is being
contacted. In consultation with the firm
the work of implementating A/R scheme
will be taken up.
4 220 kV BWSSB, CWSS Synchronising facility is not available. M/s BWSSB is insisted to provide the
Pumping Station, TATAGUNI same.
5 220 kV Gerusoppa Dam Power Different type of Numerical Distance Protection is Preparation of tender specification &
House to be provided as Main-II in place of Static Over obtaining administrative approval is
Current and Earth Fault Protection. under progress.
39
6 220 kV HAL Event logger is not available.
9 220 kV HRS Hoody Substation Main-II relays not available in all 220 kV feeders. 220kV control and relay panels with
The same to be provided. main-1 and main-2 distance protection
are being provided under R&M works.
10 220 kV HSR Layout Main-1 protection is Distance Relay and Main-2 Included in the renovation and
protection is Back up relays with OCR & EFR. upgradation of protection system works
Bus Bar protection relay is out of service, the same Included in the renovation and
to be put back to service for protection. upgradation of protection system works
40
On 09.10.2012 for the 220 kV Hoody Line fault, the
transformer-1 HV & LV tripped. The relay setting
Attended
to be reviewed.
12 220 kV JSW ENERGY The over voltage stage - 2 and stub protection
(JINDAL) Substation functions for 400 kV lines to be enabled Attended
13 220 kV Kadakola protection system to be time synchronized with Included in the renovation and
GPS upgradation of protection system works
14 220 kV Kadra (Gen) Carrier protection is out of service for Karwar 1 & 2 Commissioned
feeders
Neutrals of generating transformers and LAs are to Sufficient space for earthing is not
be exclusively earthed. available. Hovever the work will be
taken up at the earliest.
15 220 kV Kodasalli S/S (Gen) Carrier protection is not in service for all feeders Commissioned
(the real time testing is pending).
41
16 220 kV Kolar Synchronisation facility not available Included in the renovation and
upgradation of protection system works
18 220 kV Lingasugur All 220 kV line and bus coupler C&R panels, The work of replacement of old C&R
distance relays are retrofitted with ABB REL511 panels will be taken up upon supply of
relays & REL670 , but the existing panels back up new C&R panels
electromechanical relays are very old and sluggish,
most of the TS Relays are faulty, annunciation not
working, hence it is suggested to replace the
panels at the earliest.
19 220 kV Naganathapura R/S In Bus bar protection relay Master Card is faulty,
sent for repair to M/s. ERL. Attended
42
Main-1: Numerical Distance Protection and Main-2
is Back up protection with OCR & EFR. Included in the renovation and
upgradation of protection system works
20 220 kV Nagjhari Power House The LBB relay time & current are set at 1.5 sec & The LBB time & current is set at 1.5
0.2 A for all feeders and generating transformers. second 0.2 amps are reset to 0.2
seconds and 0.2 amps now.
21 220 kV Narendra SS ICT-1&2 220 KV LA counters are not available.
Attended
22 220 kV NRS Rajajinagar Event logger and DRS not available for Peenya & Included in renovation and upgradation
Vrushabavathi Lines. of protection system works
43
Winding/Oil temperature indicator are not in Attended
working condition. The same to be made in
working condition.
Main II Distance protection Relays for all 220 Kv Included in renovation and upgradation
feeders is not available & the Protection Coupler of protection system works
for Peenya & Vrushabavathi Lines are not
available.
23 220 kV Peenya, Bangalore GPS, Disturbance recorder and event logger are
not available and same to be provided. Control
panel annunciation not in working condition except
transformers
Is being covered under R&M works
Main-II Distance protections were not propvided in under Peenya.
all 220 kV feeders and PLCC/Protection coupler
was not provided except 220 kV Hebbal feeder
24 220 kV Raichur TPS 220 V DC earth fault persisting negative dead Negative dead ground is removed.
grounded Partial ground is present with following
voltages. +ve w.r.t ground voltage is
+140 V -ve w.r.t ground
voltage is –90 V
Old electromagnetic relays can be replaced with Budget proposal is made for the year
numerical relays. 2014-2015 budget. Procurement
process will be initiated after approval
of budget.
44
LBB Relay RAICA RXKL1 setting for ICT-II is kept ICT-2 LBB relay setting: Existing
at 50 mA. RXIB24 module (with 50 mA setting)
was replaced with New RXIB24 module
(200mA setting) on 15-02-2013.
26 220 kV Sharavathi SS (Gen) LBB relay timing is observed to be 0.7 sec which is LBB timing was kept at 200
high, can be reduced to 250 to 300 m.sec in msec.However at present the existing
coordination with pole discrepancy relay of breaker. LBB protection panel is removed and
LBB protection will be enabled in new
Bus bar protection panel which is being
commissioned.
Feeders with same Make & Type relay as Main-I & Tendering work is under progress for
Main-II should be changed with different procurement & commissioning of
Make/Type relays for Main-I & Main-II. different make & type of relays for main
I & Main II.
Feeders having O/C and E/F relays as Main-II to The same will be carried out during
be replaced with distance relays for good implementation of different type & make
protection coordination on 220 kV Grid. relays for main I & Main II.
Carrier protection should be kept in service for the carrier protection is provided for all
feeders having no carrier protection. feeders.Protection panels and
healthiness of the same can be
confirmed after ascertaining healthiness
of PLCC equipment from PLCC division
of KPTCL.
45
DC earth leakage should be arrested on top priority Tender action is under final stage for
to avoid spurious trippings due to DC earth the procurement of online DC earth
leakage. leakage tester.However right now
efforts are being made to isolate DC
earth leakage whenver unit/lines are
shutdown.
28 220 kV Sir M.V. GIS Station In CB two Nos. of trip coils energised from one DC Included in renovation and upgradation
source only. of protection system works
29 220 kV SUBRAMANYAPURA protection system to be time synchronized with Included in renovation and upgradation
GPS of protection system works
30 220 kV T. K. HALLI To provide GPS synchronisation for 220kV Included in renovation and upgradation
protection system. of protection system works
31 220 kV Varahi (VUGPH Electromechanical directional OCR & EFR relays Under Process
Hosangadi) (Gen) are existing as back up protection for 220 kV line
feeders. Different type of numerical distance
relays should be replaced in place of
electromechanical relays.
46
32 220 kV Vrushabavathi 220 kV Lines provided with Main I only, Main II
Substation protection to be provided.
Included in renovation and upgradation
GPS to be procured and installed for time of protection system works
synchronisation of protection system.
33 400 kV BTPS High setting for the bus bar differential protection The settings will be reviewed in
i.e. 325 V. consultation with OEM.
A/R Selection switch is kept in non auto mode for The operation of Auto reclosure relays
all 400 kV lines. of most of the lines are found to be not
satisfactory.OEM of the relays M/s
Alsthom is being contacted for
rectification works.The firm is not
responding positively.However the firm
is being oersued to take up rectification
works of A/R relays immeditely.Once
the relays are rectified,breakers will be
tested for A/R operation and selection
switch will be kept in Auto mode.
Dead 220 V DC Earth fault for both sets i.e. Earth fault in 220 V Dc circuit is traced
Positive to Earth 235 V. and rectified.
GPS time synchronisation for all the relays & DR GPS time synchronization for relays of
not carried. unit 2,Hiriyur1 & 2 & Disturbance
reorder is implemented.The time
synchronization of other unit & lines will
be completed shortly.
47
Pole descripency relay setting kept at 0.1 Sec for A/R scheme is yet to be commissioned
all the lines. for 400 KV lines.Hence A/R selection
switch is kept in non auto mode.The
operation of A/R relays are found to be
inot satisfactory.Action for its
rectification is under progress.On
commissioning of A/R Scheme PD relay
will be kept at 0.1 sec.
35 400 kV Hoody Substation Main-II protection not provided in 220 kV feeders 220kV control and relay panels with
instead Backup protection are provided. main-1 and main-2 distance protection
are being provided under R&M works.
36 400 kV Nelamangala & 220 kV Main II distance protection were not provided in all
Nelamangala 220 kV lines and
Included in renovation and upgradation
of protection system works
48
PLCC/Protection Coupler were not provided except
Nittur & Dabuspet lines
Attended
37 400 kV Raichur TPS SS (IS) 220 V DC earth fault persisting with leakage Located the D/C earth fault by availing
current of 15 mA services of M/S Taurus Powertronics
Ltd,Bangalore.The earth fault found in
ICT -2 DC Source-2 circuit.The same
will be isolated shortly.
PD settings for Munirabad, BTPS and Timers will be replaced & settings will
Mahboobnagar kept at 0.1 sec be changed as per SRPC norms during
line shutdown.
RTPS-Munirabad line Zone-II setting (26.880 Ohm) The relay settings for all the 400 KV
is more than Zone-III (26.44 Ohm) lines at RTPS have been reviewed &set
in the presence of PGCIL & KPTCL
th th
staff on 13 & 14 of March 2014.Now
the existing settings for munirabad line
are,Zone 1=12.76 ohms,Zone 2=21.6
ohms,Zone 3=24.63 ohms & Zone -4
(reverse)=6 ohms.
49
No fault locator working for Munirabad and The process of retrofitting
Mehboobnagar lines electromechanical relays with
Numerical version for both the lines is
under progress.The numerical relays
will be incorporated with fault locator.
50
Bus coupler distance protection to be replaced with
numerical relay -
51
KSEB
52
LBB not in service for SBEM 2, 3 and EMPC 1
-
4 220 kV Idukki HEP Provision for measuring earth resistance to be would be be considered during
explored. renovation period
LBB protection for all Circuit Breakers shall be
included. Under Progress
53
6 220 kV Kaniyambetta S/S The 220 kV line's Main I (Electrostatic
QUADRAMHO) Distance Relays should retrofitted
Under Progress
with latest version Numerical Relays for easy and
quick analysis of faults.
7 220 kV Madakkathara 1 phase auto reclosing to be provided for 220 kV
feeders. Done
8 220 kV New Pallom Switching Resistance reaches to be examined for each zone
Station of protection instead of setting it as a commoin
Done
parameter as in the 220 kV New Pallom-
Kayamkulam 1 & 2.
Load encroachment impedance and the loadability
of the relay to be examined depending upon the
Done
line length and loading nof the feeder.
54
220 kV Idukki-New Pallom feeder has main-1 static
version relay and main-2 has overcurrent relay
which to be considered to be replaced with Under Progress
numerical distance protection relay.
55
ANNEXURE III (58/59)
56
ANNEXURE III (59/59)
57
ANNEXURE IV (1/17)
ANNEXURE IV (2/17)
SPS 1 & 3:
It was explained that proposed load relief from the states could not be solely
based on their demand. Usage of ISTS network was also a very important
parameter. Though demand met could be lower, relative usage of ISTS network
in meeting this demand was also to be borne in mind. Another aspect in viewing
the same would be the ISGS allocation /allocation from Talcher-II station of NTPC
and total import ratios of SR beneficiaries.
It was therefore agreed that the existing scheme of load relief be retained. The
matter would be reexamined after commissioning of second circuit of 765 kV
Raichur-Sholapur link and experience post commissioning of the same.
1
It was noted that the number of SPS operations in Southern Region had reduced
of late.
SPS 2:
It was noted that NLDC had already advised blocking of this scheme.
SPS 3:
The matter had been discussed in the Special Meeting held at Hyderabad on 18 th
January 2014. In that Meeting, the need for SPS operation in Southern Region to
meet eventuality of loss of import due to tripping of 765 kV line had already been
discussed and agreed.
SPS 4
It was observed that SR Grid was presently connected with WR Grid through
single 765 kv line. Hence, all loads in SR were equally sensitive to the flow on 765
kV Raichur-Sholapur line. As regards load aspect, the same has already been
covered under SPS 1 & 3.
SPS 5 & 6
2
SPS 7
After discussions, it was felt that for flow exceeding 1,500 MW from SR to NEW
Grid, need for 765 kV line tripping may need examination. It was felt that NLDC
could be requested to carry out necessary studies to further examine this
suggestion.Ability of SR Grid to absorb the jerk of sudden loss of export of power
greater than 1,500MW could also be referred to NLDC.
SPS 8 & 9
It was explained by SRLDC that choice of loads had already been made
appropriately. The loads had been identified on the downstreamportion of the
lines so as to give proper relief.
SPS 10
It was clarified by SRLDC that signal 3 had been devised on account of the
extended mode of operation of HVDC.(2500 MW for 10 hrs a day)Earlier, there
was uncovered load of about 500 MW not covered in any load relief scheme. This
was expected to be absorbed by the SR Grid since there was no interconnected
AC link with NEW Grid. However, after commissioning of 765 kV line, any pole
outage would result in increased power flow on the AC inter connection. Hence,
the two conditions had been concatenated. In case the same was not done,
there could be operation of other SPS schemes on account of higher flow through
Raichur-Sholapur line and upstream line.
SPS 11
It was noted that separate loads for Kudankulam SPS had already been identified.
3
Other
Constituents desired that a comprehensive list of SPS Schemes along with the
operating logics be made available to them, since number of modifications had
been proposed/ implemented.
***********
4
ANNEXURE IV (16/17)
ANNEXURE IV (17/17)
ANNEXURE V (1/4)
1
ANNEXURE V (2/4)
b. APTRANSCO to
review distance
protection settings of
KPTS- Managuru line-2
as it tripped for fault in
KPTS- Managuru line-1.
c. APGENCO to review
reverse distance
protection settings of
KPTS- Shapur nagar
Line.
d. APGENCO to enable
DEF Back Up protection
in all lines emanating
from KTPS.
e. APGENCO to enable
IDMT characteristics for
GTs and ICTs at KTPS
which is to be
coordinated with primary
protection.
f. APGENCO to review
the Overload settings of
Unit 4
g .DR at Khammam
Substation to be time
synchronized with GPS
2
ANNEXURE V (3/4)
h. APGENCO to review
bus bar protection
settings.
3
ANNEXURE V (4/4)
4
ANNEXURE VI (1/11)
• Proposed setting
– Stage-1 : 49.9Hz & 0.1 Hz/sec
– Stage-2 : 49.9Hz & 0.2 Hz/sec
Mundra disturbance on 12th March 2014
ANNEXURE VI (2/11)
§ Complete black out at CGPL Mundra (UMPP) due to tripping of all evacuating
lines from CGPL Mundra
§ Load loss : 1110 MW was reported during the event out of which
§ Df/dt : 960 MW (Gujarat: 630 MW + Maharashtra: 330 MW)
§ SPS operation : 150 MW
df/dt setting N.R
All India UFR Status
49.2 Hz 49 Hz 48.8 Hz 48.6 Hz Total
Region STATES Remarks
Approved Approved Approved Approved Approved
in RPC Actual in RPC Actual in RPC Actual in RPC Actual in RPC Actual
Punjab 400 435 402 575 406 807 408 415 1616 2232
Delhi 258 297 259 353 262 429 263 1049 1042 2128
UP 551 1393 554 987 559 1368 561 799 2225 4547
NR
Uttarakhand 77 90 77 100 78 0 78 0 310 190
J&K 83 0 84 0 84 0 85 0 336 0
Chandigarh 16 0 16 0 16 0 16 0 64 0
Total 2160 4268.2 2170 4131.8 2190 2604 2200 2341 8720 13345
Gujarat 580 773 580 726 580 1117 580 1025 2320 3641
MP 460 468 460 450 460 460 465 490 1845 1868
Maharashtra 805 1108 810 1200 815 765 820 851 3250 3924
Chattisgarh 150 110 150 114 155 117 155 91 610 432
WR
Goa 25 25 25 25 100 0
UFR under
DD 10 15 15 15 55 0
Procurement
DNH 30 30 35 35 130 0
Total 2060 2459 2070 2490 2085 2459 2095 2457 8310 9865
All India UFR Status
49.2 Hz 49 Hz 48.8 Hz 48.6 Hz Total
Region STATES Remarks
Approved Approved Approved Approved Approved
in RPC Actual in RPC Actual in RPC Actual in RPC Actual in RPC Actual
Andhra Pradesh 809 1064 / 562 812 1172 / 594 822 1120 / 597 825 1130 / 581 3268 4486 / 2334 Max / Average
Karnataka 576 703 / 474 578 821 / 514 586 707 / 451 588 627 / 441 2328 2858 / 1880 Max / Average
Kerala 204 288 / 214 205 263 / 217 208 275 / 218 209 298 / 211 826 1124 / 860 Max / Average
SR
Tamilnadu 740 1098 / 740 744 932 / 745 753 1012 / 756 756 510 / 419 2993 3552 / 2660 Max / Average
WB( Incl CESC) 345.5 350 350 354 1399.5 Full Quantum Implemented
Manipur 5 3 5 0 5 0 5 0 20 3
Meghalaya 15 15 15 15 15 15 15 15 60 60
NER
Mizoram 5 5.09 5 5.31 5 5.1 5 5.2 20 20.7
Nagaland 5 3 5 3 5 3 5 0 20 9
Total 100 95.09 100 94.31 100 96.6 100 89.7 400 375.7
All India df/dt Status
Stage I Stage II Stage III
Total
49.9Hz & 0.1Hz/Sec 49.9Hz & 0.2Hz/Sec 49.9Hz & 0.3Hz/Sec
Region STATES Remarks
Approved Actual Approved Actual Approved Actual Approved Actual
in RPC in RPC in RPC in RPC
HP 50 50 70 70 70 70 190 190
Goa
DD
DNH
Total 2000 2000 2000 2000 2472 2472 6472 6472
Bihar
Jharkhand
DVC
ER
Odisha NIL
Total 0 0 0 0 0 0 0 0
Arunachal Pradesh
Assam
Manipur
Meghalaya
NER
Mizoram
Nagaland
Tripura
Total 0 0 0 0 0 0 0 0
49.5Hz & 0.2 Hz/sec 49.3Hz & 0.3 Hz/sec Total
Region STATES Approved Approved Approved
Remarks
Actual Actual
in RPC in RPC in RPC Actual
Andhra Pradesh 712 714 1767 1635 2479 2349
Partly Implemented -
Rajasthan 1574 3316 Scheme implemented 1070 1070 Fully Implemented
only at 49.2 Hz. & 49.0 Hz.
Partly Implemented -
Maharashtra 3250 3924 Load relief to be added 1853 1853 Fully Implemented
at 48.8HZ
WR Chattisgarh 610 432 Partly Implemented 184 184 Fully Implemented
Goa 100 0
DNH 130 0
Andhra Pradesh 3268 4486 / 2334 Fully Implemented 2479 2349 Partly Implemented
Karnataka 2328 2858 / 1880 Fully Implemented 1510 1345 Partly Implemented
AnnexureVI (11/11)
Summary - All India UFR & df/dt Status
UFR Status df/dt Status
Region STATES
Approved Actual Status Approved Actual Status
Kerala 826 1124 / 860 Fully Implemented 347 356 Fully Implemented
SR Partly Implemented -
Tamilnadu 2993 3552 / 2660 Load relief to be added 1183 617 Partly Implemented
at 48.6HZ
Poducherry 85 112 / 86 Fully Implemented 18 18 Fully Implemented
Total 9500
Bihar 397 Fully Implemented
Total 3320