You are on page 1of 28

LOAD CALCULATION

Page 3 of 127
Owner Medford Water Comission Computed By AVS
Plant WQIP_Chemical building Unit Date Jan 31, 2020
Project No. 402845 File No. Verified By
Title Big Butte WTP Date
BLACK & VEATCH Page of

Calculation of Seismic Base Shear based on IBC 2018, ASCE 7-16


INPUT: ASCE 7 Ref. IBC Ref.
Risk Category III Table 1.5-1 Table 1604.5

Site Soil Classification D 11.4.3, Geo Rpt, Section 1613.2.2


or Table 20.3-1
SS = Mapped Spectral Acceleration for (MCE R) 62.2 %g 0.622 g Figs 22-1 Section 1613.2.1
at 0.2-sec Short Period Response Fig 1613.2.1(1)
thru
thru
S1 = Mapped Spectral Acceleration for (MCE R) 30.1 %g 0.301 g Fig 22-8 Fig 1613.2.1(8)
at 1.0-sec Period Response or USGS website
Description of Seismic Force Resisting System
R = Response Modification Coefficient 3.0 Table 12.2-1 Masonry building is resting on
RC wall below. It is a dual
Ω0 = Omega, System Overstrength Factor 2.5 Table 12.2-1 system. For RC wall, R=3 hence
as per ASCE 7-10, Cl. 12.2.3 to
Cd = Deflection Amplification Factor 3.5 Table 12.2-1 get more stringent structural
system, R=3 is considered for
hn = Building Height: 24.00 ft Masonry building as well. But
detailing requirement is still
TL = Long Period Transition Period: 16.0 sec 11.4.6 & Figs 22-14 to followed
22-17 as a Special
Reinforcement Shear Wall
Structure Type (From Table 12.8-2): 5) All Other Structural Systems Section 12.8.2.1
Ct = Building Period Coefficient: 0.020 Table 12.8-2
x = Coefficient used for Building Period calc 0.75 Table 12.8-2

CALCULATIONS:
Ie = Importance Factor 1.25 Section 11.5.1 &
Table 1.5-2
Site Coefficients:
Fa = Site Coefficient based on 0.2-sec Short Period 1.302 Table 11.4-1 Table 1613.2.3(1)
Fv = Site Coefficient based on 1-sec Period 1.999 Table 11.4-2 Table 1613.2.3(2)
Maximum Considered Earthquake Response Acceleration:
SMS = Fa*SS/100 = 0.810 (Eqn 11.4-1) (Eqn 16-37)
SM1 = Fv*S1/100 = 0.602 (Eqn 11.4-2) (Eqn 16-38)
Design Spectral Response Accelerations:
SDS = (2/3)SMS SDS = 0.540 (Eqn 11.4-3) (Eqn 16-38)
SD1 = (2/3)SM1 SD1 = 0.401 (Eqn 11.4-4) (Eqn 16-39)
Determine Seismic Design Category
Seismic Design Category,0.2-sec Period D Table 11.6-1 Table 1613.2.5(1)
Seismic Design Category, 1-Sec Period N/A Exclude < Use or Exclude? Table 11.6-2 Table 1613.2.5(2)
Determine Periods (Time) for Response Spectra Curve:
Ta = Approximate Fundamental Period of the Structure
= Ct*hnx 0.020*(24.00)^0.75 = 0.217 sec (Eqn 12.8-7)
T0 = 0.2*(SD1/SDS) = 0.20*0.401/0.540 = 0.149 sec Section 11.4.6
TS = (SD1/SDS) = 0.401/0.540 = 0.743 sec Section 11.4.6

Calculation of Seismic Response Coefficient, C S for Equivalent Lateral Force Procedure:


CS = (For SDC 'A') = N/A Section 11.7 & (Eqn 1.4-1)
CS = SDS / (R/Ie) = Cs = 0.225 << Controls (Eqn 12.8-2)
If Ta < TL, CS_MAX < SD1 / {T*(R/Ie)} Cs <= 0.771 (Eqn 12.8-3)
If Ta > TL, CS_MAX < (SD1*TL) / {T2*(R/Ie)} N/A (Eqn 12.8-4)
CS_MIN = 0.044*SDS*Ie > 0.01 Cs => 0.030 (Eqn 12.8-5)
If S1 > 0.6g, CS_MIN > 0.5*S1 / (R/Ie) N/A (Eqn 12.8-6)

SUMMARY: (Equivalent Lateral Force Procedure)


Seismic Design Category SDC = D << See 11.8.2 & 11.8.3 for add'l requirements of the Geotech Report
Seismic Load Effect Including Overstrength Factor,
W o .for Structures with Irregularities
Base Shear (LFD) VLFD = CS*W = 0.225 *W VLFD*W0 = 0.563 *W (Eqn 12.8-1)

Base Shear (ASD) VASD = 0.7*VLFD = 0.158 *W VASD*W0 = 0.394 *W Section 2.4 ASD Load Combinations

Black & Veatch Proprietary and Confidential


WTR-AM-FM-EN-1820-2018, dtd 8/27/2019 Page 1 of 1 UNCONTROLLED when printed
Client Name: Medford Water Comission Prepared By: AVS
Project Name: Water Quality Improvement Projects Date: Jan 31, 2020
Project No. : 402845.0000 Rev No. 2 Verified By: NVN
Calculation Title: Load calculation for Grating design-Big Butte Springs Date: Jan 31, 2020
Calculation No./File No.: Page: of 0

Load Calculations for Grating Design:


Reference image from Foundaton and Grating plan

Grating supporting member 1

10.5 ft

Grating supporting member 2

Max.5.0 ft

INPUT
Type of Grating = Hot Dipped Galvanized Steel
Weight of grating 7.4 psf = 0.0074 ksf 7.4/1000
Maximum span of grating for design = 5.0 ft
Thickness of grating = 1.25 in
Grating supporting member (1) = W 10 X 45
Maximum length of grating supporting member = 10.5 ft

Grating supporting member (2) = L 2.5X2.5X0.25 refer standard drawing


Maximum length of grating supporting member = 2.0 ft

A DEAD LOAD
Self weight of grating supporting member = as calculated in STAAD
Self weight of Grating = 0.0074 ksf
Load transferred on supporting member = 0.0185 kip/ft 0.0074*5/2

B LIVE LOAD
Live load on Operating floor 150 psf = 0.15 ksf 150/1000
Load transferred on supporting member = 0.375 kip/ft 0.15*5/2

C SEISMIC LOAD
SDS = 0.540
Max. Base shear coefficient of Superstructure Cs = 0.225 W refer sesimic base shear calculation
Self weight multiplied by the coefficient = as calculated in STAAD
Load due to grating = 0.00416 kip/ft 0.225*0.0185

LOAD COMBINATIONS AS PER ASCE 7-16


Strength Load Combinations
1) 1.4DL Ev = 0.2 SDs x D
2) 1.2DL + 1.6LL = 0.108 D
3) (1.2+0.108)D + Eh + L
4) (0.9-0.108)D + Eh

Service Load Combinations


1) 1.0DL
2) 1.0DL +1.0LL
3) (1+0.525 x 0.108)D + 0.525Eh + 0.75LL
4) (0.6-0.7 x 0.108)D + 0.7Eh
ANALYSIS AND DESIGN OF
GRATING SUPPORTING MEMBER

Page 3 of 127
Job No Sheet No Rev
402845 1 0

Software licensed to HPE Part Big


CONNECTED User: Amey Sawant Butte
Job Title MWC WQ Improvements Ref

By AVS Date28-Jan-20 Chd NV


Client Medford Water Comission File Grating member design.stdDate/Time 29-Jan-2020 11:31

Geometry of structure-

Grating supporting member 1


(W10 X 45)

Grating supporting member 2


(L 2.5 X 2.5 X 0.25)

Rendered view -

Print Time/Date: 29/01/2020 12:03 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Job No Sheet No Rev
402845 1 0

Software licensed to HPE Part Big


CONNECTED User: Amey Sawant Butte
Job Title MWC WQ Improvements Ref

By AVS Date28-Jan-20 Chd NV


Client Medford Water Comission File Grating member design.stdDate/Time 29-Jan-2020 11:31

Dead load on members -


Self weight &
Grating load

Live load on members -

Print Time/Date: 29/01/2020 12:03 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Job No Sheet No Rev
402845 1 0

Software licensed to HPE Part Big


CONNECTED User: Amey Sawant Butte
Job Title MWC WQ Improvements Ref

By AVS Date28-Jan-20 Chd NV


Client Medford Water Comission File Grating member design.stdDate/Time 29-Jan-2020 11:31

Seismic load on members -


Self weight with factor 0.225
Grating load x 0.225

Print Time/Date: 29/01/2020 12:03 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Job No Sheet No Rev
402845 1 0

Software licensed to HPE Part Big


CONNECTED User: Amey Sawant Butte
Job Title MWC WQ Improvements Ref

By AVS Date28-Jan-20 Chd NV


Client Medford Water Comission File Grating member design.stdDate/Time 29-Jan-2020 11:31

Load combinations used for design -


+++++++++++++++++++++++++++++++++++++++++++++++++++++++++
----- LOAD COMBINATION ULS -----
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++
LOAD 200 (1.40 DL)
REPEAT LOAD
1 1.4
*********************************************
LOAD 201 (1.2 DL + 1.6 LL)
REPEAT LOAD
1 1.2 2 1.6
*********************************************
LOAD 202 (1.20 DL + 1.0 EV + 1.0 EH + 1.0 LL)
REPEAT LOAD
1 1.308 3 1.0 2 1.0
*********************************************
LOAD 203 (0.9 DL - 1.0 EV + 1.0 EH)
REPEAT LOAD
1 0.792 3 1.0
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++
----- LOAD COMBINATION SLS -----
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
LOAD 100 (1.0 DL)
REPEAT LOAD
1 1.0
*********************************************
LOAD 101 (1.0 DL + 1.0 LL)
REPEAT LOAD
1 1.0 2 1.0
*********************************************
LOAD 102 (1.0 DL + 0.7 EV + 0.7 EH)
REPEAT LOAD
1 1.0756 3 0.7
*********************************************
LOAD 103 (1.0 DL + 0.525 EV + 0.525 EH + 0.75 LL)
REPEAT LOAD
1 1.0562 3 0.525 2 0.75
*********************************************
LOAD 104 (0.6 DL - 0.7 EV + 0.7 EH)
REPEAT LOAD
1 0.5244 3 0.7

Print Time/Date: 29/01/2020 12:03 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Job No Sheet No Rev
402845 1 0

Software licensed to HPE Part Big


CONNECTED User: Amey Sawant Butte
Job Title MWC WQ Improvements Ref

By AVS Date28-Jan-20 Chd NV


Client Medford Water Comission File Grating member design.stdDate/Time 29-Jan-2020 11:31

Maximum deflection of members -

0.017 inch

0.013 inch

1) Allowable deflection for W10X45 member = Span/200


= 10.5 X 12/200
= 0.63 inch > 0.017 inch, hence ok

2) Allowable deflection for angle = Span/200


= 2 X 12/200
= 0.12 inch > 0.013 inch, hence ok

Print Time/Date: 29/01/2020 12:03 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Job No Sheet No Rev
402845 1 0

Software licensed to HPE Part Big


CONNECTED User: Amey Sawant Butte
Job Title MWC WQ Improvements Ref

By AVS Date28-Jan-20 Chd NV


Client Medford Water Comission File Grating member design.stdDate/Time 29-Jan-2020 11:31

Unity ratio check of members -

Print Time/Date: 29/01/2020 12:03 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
CONNECTION DESIGN FOR
ANGLE

Page 3 of 127
Job No Sheet No Rev
402845 1 0

Software licensed to HPE Part Big


CONNECTED User: Amey Sawant Butte
Job Title MWC WQ Improvements Ref

By AVS Date28-Jan-20 Chd NV


Client Medford Water Comission File Grating member design.stdDate/Time 29-Jan-2020 11:31

Maximum Shear and Tension for design of connection -

Shear and Tension = 0.445 kip = 445 lb


On each anchor load will be from both sides, hence total = 2 x 445 = 890 lb say 1000 lb

Print Time/Date: 29/01/2020 12:03 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 1
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 200 + HAS-R 316 1/2
Effective embedment depth: hef,act = 6.000 in. (hef,limit = - in.)
Material: ASTM F 593
Evaluation Service Report: ESR-3187
Issued I Valid: 11/1/2016 | 3/1/2018
Proof: Design method ACI 318-14 / Chem
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.250 in.
Anchor plate: lx x ly x t = 24.000 in. x 2.500 in. x 0.250 in.; (Recommended plate thickness: not calculated
Profile: Rectangular plates and bars (AISC); (L x W x T) = 0.250 in. x 0.188 in. x 0.000 in.
Base material: cracked concrete, 4000, fc' = 4000 psi; h = 10.000 in., Temp. short/long: 32/32 °F
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar

Geometry [in.] & Loading [lb, in.lb]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 2
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads

Anchor reactions [lb]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 1000 1000 0 1000
max. concrete compressive strain: - [‰] 1 x
max. concrete compressive stress: - [psi] Tension
resulting tension force in (x/y)=(0.000/0.000): 1000 [lb]
resulting compression force in (x/y)=(0.000/0.000): 0 [lb]

3 Tension load
Load Nua [lb] Capacity f Nn [lb] Utilization bN = Nua/f Nn Status
Steel Strength* 1000 9223 11 OK
Bond Strength** 1000 3887 26 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 1000 5140 20 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


Nsa = ESR value refer to ICC-ES ESR-3187
f Nsa ≥ Nua ACI 318-14 Table 17.3.1.1

Variables
Ase,N [in.2] futa [psi]
0.14 100000
Calculations
Nsa [lb]
14190
Results
Nsa [lb] f steel f Nsa [lb] Nua [lb]
14190 0.650 9223 1000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 3
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

3.2 Bond Strength

Na = (AA ) y
Na
Na0
ed,Na y cp,Na Nba ACI 318-14 Eq. (17.4.5.1a)
f Na ≥ Nua ACI 318-14 Table 17.3.1.1
ANa = see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
ANa0 = (2 cNa)2 ACI 318-14 Eq. (17.4.5.1c)
cNa = 10 da √
t uncr
1100
ACI 318-14 Eq. (17.4.5.1d)

( )
1
y ec,Na = e' ≤ 1.0 ACI 318-14 Eq. (17.4.5.3)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( )
ca,min
cNa
≤ 1.0 ACI 318-14 Eq. (17.4.5.4b)

y cp,Na = MAX ( ,)
ca,min cNa
cac cac
≤ 1.0 ACI 318-14 Eq. (17.4.5.5b)
Nba = l a · t k,c · p · da · hef ACI 318-14 Eq. (17.4.5.2)

Variables
t k,c,uncr [psi] da [in.] hef [in.] ca,min [in.] t k,c [psi]
2327 0.500 6.000 2.500 1174
ec1,N [in.] ec2,N [in.] cac [in.] la
0.000 0.000 15.324 1.000
Calculations
cNa [in.] ANa [in.2] ANa0 [in.2] y ed,Na
7.239 141.01 209.62 0.804
y ec1,Na y ec2,Na y cp,Na Nba [lb]
1.000 1.000 1.000 11064
Results
Na [lb] f bond f Na [lb] Nua [lb]
5981 0.650 3887 1000

3.3 Concrete Breakout Strength

Ncb = (AA ) y
Nc
Nc0
ed,N y c,N y cp,N Nb ACI 318-14 Eq. (17.4.2.1a)
f Ncb ≥ Nua ACI 318-14 Table 17.3.1.1
ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
ANc0 = 9 h2ef ACI 318-14 Eq. (17.4.2.1c)

( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-14 Eq. (17.4.2.4)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef
≤ 1.0 ) ACI 318-14 Eq. (17.4.2.5b)

y cp,N = MAX (
ca,min 1.5hef
cac
,
cac
≤ 1.0 ) ACI 318-14 Eq. (17.4.2.7b)
1.5
Nb = kc l a √fc hef
'
ACI 318-14 Eq. (17.4.2.2a)

Variables
hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] y c,N
6.000 0.000 0.000 2.500 1.000

cac [in.] kc la f'c [psi]


15.324 17 1.000 4000

Calculations
ANc [in.2] ANc0 [in.2] y ec1,N y ec2,N y ed,N y cp,N Nb [lb]
207.00 324.00 1.000 1.000 0.783 1.000 15802
Results
Ncb [lb] f concrete f Ncb [lb] Nua [lb]
7908 0.650 5140 1000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 4
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

4 Shear load
Load Vua [lb] Capacity f Vn [lb] Utilization bV = Vua/f Vn Status
Steel Strength* 1000 5109 20 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength 1000 8373 12 OK
controls)**
Concrete edge failure in direction y+** 1000 6861 15 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength


Vsa = (0.6 Ase,V futa) refer to ICC-ES ESR-3187
f Vsteel ≥ Vua ACI 318-14 Table 17.3.1.1

Variables
Ase,V [in.2] futa [psi] (0.6 Ase,V futa) [lb]
0.14 100000 8515
Calculations
Vsa [lb]
8515
Results
Vsa [lb] f steel f Vsa [lb] Vua [lb]
8515 0.600 5109 1000

4.2 Pryout Strength (Bond Strength controls)

Vcp =kcp [(AA ) y


Na
Na0
ed,Na y cp,Na Nba ] ACI 318-14 Eq. (17.5.3.1a)
f Vcp ≥ Vua ACI 318-14 Table 17.3.1.1
ANa see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
ANa0 = (2 cNa)2 ACI 318-14 Eq. (17.4.5.1c)
cNa = 10 da √t uncr
1100
ACI 318-14 Eq. (17.4.5.1d)

( )
1
y ec,Na = e' ≤ 1.0 ACI 318-14 Eq. (17.4.5.3)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( ) ca,min
cNa
≤ 1.0 ACI 318-14 Eq. (17.4.5.4b)

y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-14 Eq. (17.4.5.5b)
Nba = l a · t k,c · p · da · hef ACI 318-14 Eq. (17.4.5.2)

Variables
kcp t k,c,uncr [psi] da [in.] hef [in.] ca,min [in.] t k,c [psi]
2 2327 0.500 6.000 2.500 1174
ec1,N [in.] ec2,N [in.] cac [in.] la
0.000 0.000 15.324 1.000
Calculations
cNa [in.] ANa [in.2] ANa0 [in.2] y ed,Na
7.239 141.01 209.62 0.804
y ec1,Na y ec2,Na y cp,Na Nba [lb]
1.000 1.000 1.000 11064
Results
Vcp [lb] f concrete f Vcp [lb] Vua [lb]
11961 0.700 8373 1000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 5
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

4.3 Concrete edge failure in direction y+

Vcb = (AA ) y
Vc
Vc0
ed,V y c,V y h,V y parallel,V Vb ACI 318-14 Eq. (17.5.2.1a
f Vcb ≥ Vua ACI 318-14 Table 17.3.1.1
AVc see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b)
AVc0 = 4.5 c2a1 ACI 318-14 Eq. (17.5.2.1c)

( )
1
y ec,V = 2e'v ≤ 1.0 ACI 318-14 Eq. (17.5.2.5)
1+
3ca1
y ed,V = 0.7 + 0.3 ( ca2
1.5ca1 )
≤ 1.0 ACI 318-14 Eq. (17.5.2.6b)

y h,V = √1.5ca1
ha
≥ 1.0 ACI 318-14 Eq. (17.5.2.8)

(( ) )
0.2
l 1.5
Vb = 7 e √da l a √f'c ca1 ACI 318-14 Eq. (17.5.2.2a)
da

Variables
ca1 [in.] ca2 [in.] ecV [in.] y c,V ha [in.]
8.000 12.000 0.000 1.000 10.000

le [in.] la da [in.] f'c [psi] y parallel,V


4.000 1.000 0.500 4000 1.000

Calculations
AVc [in.2] AVc0 [in.2] y ec,V y ed,V y h,V Vb [lb]
240.00 288.00 1.000 1.000 1.095 10737
Results
Vcb [lb] f concrete f Vcb [lb] Vua [lb]
9801 0.700 6861 1000

5 Combined tension and shear loads


bN bV z Utilization bN,V [%] Status
0.257 0.196 5/3 18 OK
bNV = bzN + bzV <= 1

6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility! 
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-14,
Section 17.8.1.

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 6
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200 + HAS-R 316 1/2
Profile: Rectangular plates and bars (AISC); 0.250 x 0.188 x 0.000 in. Installation torque: 360.001 in.lb
Hole diameter in the fixture: df = 0.563 in. Hole diameter in the base material: 0.563 in.
Plate thickness (input): 0.250 in. Hole depth in the base material: 6.000 in.
Recommended plate thickness: not calculated Minimum thickness of the base material: 7.250 in.
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required

7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required • Dispenser including cassette and mixer
• Properly sized drill bit accessories to blow from the bottom of • Torque wrench
the hole
• Proper diameter wire brush

12.000 12.000
1.250 1.250

1.250 1.250

1 x

12.000 12.000

Coordinates Anchor in.


Anchor x y c-x c+x c-y c+y
1 0.000 0.000 12.000 12.000 2.500 48.000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 7
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
CONNECTION DESIGN FOR
W10X45

Page 3 of 127
Typical Shear
connection with RCC

End plate 0.5 inch thk

1 1/4" thk galvanized steel grating


12" THK WALL 3/16"

W10X45

4-No 3/4" dia anchor bolts


with 6" embedment
Job No Sheet No Rev
402845 1 0

Software licensed to HPE Part Big


CONNECTED User: Amey Sawant Butte
Job Title MWC WQ Improvements Ref

By AVS Date28-Jan-20 Chd NV


Client Medford Water Comission File Grating member design.stdDate/Time 29-Jan-2020 11:31

Maximum Shear for design of connection -

Shear = 3.561 kip say 3.6 kip = 3600 lb

Maximum transverse force for design of connection -

Transverse force = 0.075 kip say 0.1 kip = 100 lb

Print Time/Date: 29/01/2020 12:03 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 1
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 200 + HAS-R 316 3/4
Effective embedment depth: hef,act = 6.000 in. (hef,limit = - in.)
Material: ASTM F 593
Evaluation Service Report: ESR-3187
Issued I Valid: 11/1/2016 | 3/1/2018
Proof: Design method ACI 318-14 / Chem
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.500 in.
Anchor plate: lx x ly x t = 14.000 in. x 11.000 in. x 0.500 in.; (Recommended plate thickness: not calculated
Profile: W shape (AISC); (L x W x T x FT) = 10.100 in. x 8.020 in. x 0.350 in. x 0.620 in.
Base material: cracked concrete, 4000, fc' = 4000 psi; h = 12.000 in., Temp. short/long: 32/32 °F
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar

Geometry [in.] & Loading [lb, in.lb]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 2
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads

Anchor reactions [lb]


Tension force: (+Tension, -Compression) 3 4
Anchor Tension force Shear force Shear force x Shear force y
1 0 900 900 25
2 0 900 900 25 x
3 0 900 900 25
4 0 900 900 25
max. concrete compressive strain: - [‰] 1 2
max. concrete compressive stress: - [psi]
resulting tension force in (x/y)=(0.000/0.000): 0 [lb]
resulting compression force in (x/y)=(0.000/0.000): 0 [lb]

3 Tension load
Load Nua [lb] Capacity f Nn [lb] Utilization bN = Nua/f Nn Status
Steel Strength* N/A N/A N/A N/A
Bond Strength** N/A N/A N/A N/A
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 3
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

4 Shear load
Load Vua [lb] Capacity f Vn [lb] Utilization bV = Vua/f Vn Status
Steel Strength* 900 10236 9 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength 3601 14349 26 OK
controls)**
Concrete edge failure in direction x+** 3601 4649 78 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength


Vsa = (0.6 Ase,V futa) refer to ICC-ES ESR-3187
f Vsteel ≥ Vua ACI 318-14 Table 17.3.1.1

Variables
Ase,V [in.2] futa [psi] (0.6 Ase,V futa) [lb]
0.33 85000 17060
Calculations
Vsa [lb]
17060
Results
Vsa [lb] f steel f Vsa [lb] Vua [lb]
17060 0.600 10236 900

4.2 Pryout Strength (Bond Strength controls)

Vcpg =kcp [(AA ) y


Na
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ] ACI 318-14 Eq. (17.5.3.1b)
f Vcpg ≥ Vua ACI 318-14 Table 17.3.1.1
ANa see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
ANa0 = (2 cNa)2 ACI 318-14 Eq. (17.4.5.1c)
cNa = 10 da √t uncr
1100
ACI 318-14 Eq. (17.4.5.1d)

( )
1
y ec,Na = e' ≤ 1.0 ACI 318-14 Eq. (17.4.5.3)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( )ca,min
cNa
≤ 1.0 ACI 318-14 Eq. (17.4.5.4b)

y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-14 Eq. (17.4.5.5b)
Nba = l a · t k,c · p · da · hef ACI 318-14 Eq. (17.4.5.2)

Variables
kcp t k,c,uncr [psi] da [in.] hef [in.] ca,min [in.] t k,c [psi]
2 2327 0.750 6.000 5.000 1273
ec1,N [in.] ec2,N [in.] cac [in.] la
0.000 0.000 11.536 1.000
Calculations
cNa [in.] ANa [in.2] ANa0 [in.2] y ed,Na
10.859 320.38 471.66 0.838
y ec1,Na y ec2,Na y cp,Na Nba [lb]
1.000 1.000 1.000 18003
Results
Vcpg [lb] f concrete f Vcpg [lb] Vua [lb]
20499 0.700 14349 3601

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 4
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

4.3 Concrete edge failure in direction x+

Vcbg = (AA ) y
Vc
Vc0
ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-14 Eq. (17.5.2.1b)
f Vcbg ≥ Vua ACI 318-14 Table 17.3.1.1
AVc see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b)
AVc0 = 4.5 c2a1 ACI 318-14 Eq. (17.5.2.1c)

( )
1
y ec,V = 2e'v ≤ 1.0 ACI 318-14 Eq. (17.5.2.5)
1+
3ca1
y ed,V = 0.7 + 0.3 (ca2
1.5ca1 )
≤ 1.0 ACI 318-14 Eq. (17.5.2.6b)

y h,V = √
1.5ca1
ha
≥ 1.0 ACI 318-14 Eq. (17.5.2.8)
' 1.5
Vb = 9 l a √fc ca1 ACI 318-14 Eq. (17.5.2.2b)

Variables
ca1 [in.] ca2 [in.] ecV [in.] y c,V ha [in.]
8.000 5.000 0.000 1.000 12.000

le [in.] la da [in.] f'c [psi] y parallel,V


6.000 1.000 0.750 4000 1.000

Calculations
AVc [in.2] AVc0 [in.2] y ec,V y ed,V y h,V Vb [lb]
180.00 288.00 1.000 0.825 1.000 12880
Results
Vcbg [lb] f concrete f Vcbg [lb] Vua [lb]
6641 0.700 4649 3601

5 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility! 
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-14,
Section 17.8.1.

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 5
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

6 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200 + HAS-R 316 3/4
Profile: W shape (AISC); 10.100 x 8.020 x 0.350 x 0.620 in. Installation torque: 1200.002 in.lb
Hole diameter in the fixture: df = 0.813 in. Hole diameter in the base material: 0.875 in.
Plate thickness (input): 0.500 in. Hole depth in the base material: 6.000 in.
Recommended plate thickness: not calculated Minimum thickness of the base material: 7.750 in.
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required

6.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required • Dispenser including cassette and mixer
• Properly sized drill bit accessories to blow from the bottom of • Torque wrench
the hole
• Proper diameter wire brush
y

7.000 7.000

3.000

5.500
3 4

5.000

x
5.500

1 2
3.000

4.500 5.000 4.500

Coordinates Anchor in.


Anchor x y c-x c+x c-y c+y
1 -2.500 -2.500 5.500 17.000 5.000 10.000
2 2.500 -2.500 10.500 12.000 5.000 10.000
3 -2.500 2.500 5.500 17.000 10.000 5.000
4 2.500 2.500 10.500 12.000 10.000 5.000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.3
Company: B&V Page: 6
Specifier: AVS Project: MWC WQIP
Address: Sub-Project I Pos. No.: Chemical Building BB
Phone I Fax: | Date: 1/31/2020
E-Mail:

7 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

You might also like