FOR SINGLE PHASE CIRCUITS: 11. ROUTE ALL EXTERIOR LIGHTING CIRCUITS VIA LIGHTING CONTROL PANEL VIA LCP. J HD JUNCTION BOX, DEDICATED FOR HAND DRYER CB CIRCUIT BREAKER OC ON CENTER
PHASE – RED ELECTRICAL CONTRACTOR TO PROVIDE LIGHTING CONTROL PANEL WITH
GROUND – GREEN/BARE DISCONNECT SWITCH, RATING AS NOTED CCTV CLOSED CIRCUIT TELEVISION OL OVERLOAD
ASTRONOMICAL TIME CLOCK, LCD DISPLAY AND PHOTO CELL SWITCHING. VERIFY
NEUTRAL – WHITE LOCATION WITH THE OWNER PRIOR TO INSTALLATION.
DISTRIBUTION BOARD
IG ISOLATED GROUND
18. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE ELECTRICAL LOAD BALANCING
POE SWITCH
AND LABELLING OF ALL EQUIPMENT AND SWITCHBOARDS THROUGHOUT THE INSTALLATION. ISC SHORT-CIRCUIT CURRENT
19. THE ELECTRICAL CONTRACTOR TO PROVIDE GROUNDING ELECTRODE SYSTEM. GROUND KAIC KILO AMPERE INTERRUPTING CAPACITY
ELECTRODE RESISTANCE SHALL COMPLY WITH THE LATEST EDITION OF PHILIPPINE ELECTRICAL CCTV RACK
CODE. KV KILO VOLT
20. ALL DISCHARGE LIGHTING FIXTURE SHALL BE COMPLETED WITH BUILT-IN CONTROL GEAR, LAMP, IP BASED CEILING MOUNTED CCTV CAMERA
KVA KILO VOLT AMPERE
LOW-LSS BALLAST, ETC.
IP BASED WALL MOUNTED CCTV CAMERA KVAR KILO VAR
21. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING OF ALL CABLE/RACEWAY
PENETRATION WITH APPROVED FIRE RATING MATERIAL/SEALANT. KW KILO WATT
SWITCHING
22. THE ELECTRICAL CONTRACTOR TO PROVIDE GROUND FAULT AND OVERCURRENT TRIPPING Sa SINGLE POLE SWITCH 15A, 230VAC, "a" INDICATES CONTROL
DISCRIMINATION BETWEEN THE SWITCHBOARD AND THE INCOMING FEEDER TO COMPLY WITH
THE LOCAL POWER UTILITY COMPANY REQUIREMENTS. S3Wa THREE-WAY SWITCH 15A, 230VAC, "a" INDICATES CONTROL
23. THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL NECESSARY LABOR MATERIALS AND
EQUIPMENT FOR SATISFACTORY COMPLETION OF ALL ELECTRICAL INSTALLATION AS GENERALLY
DESCRIBED IN THE SPECIFICATION AND/OR AS SHOWN IN THE DRAWINGS.
24. ALL SWITCHBOARDS AND PANELBOARDS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE
LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE.
25. EACH CIRCUIT SHALL UNDERGO INSULATION RESISTANCE TESTING BY APPLYING A VOLTAGE OF
NOT LESS THAN 1000V D.C. UPON CIRCUIT UNDER TEST.
26. ALL INSULATION RESISTANCE TEST SHALL BE CARRIED OUT WITH A 1000V MEGGER TEST
INSTRUMENT AND IN ACCORDANCE WITH THE LATEST PHILIPPINE ELECTRICAL CODE
REQUIREMENTS.
27. LIGHTNING PROTECTION SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST
EDITION OF THE PHILIPPINE ELECTRICAL CODE.