HRSG MANUAL
1) HRSG alarm
Under any circumstances, request control system alarm to attract the attention of the operators and
timely take measures to control:
HP steam drum water level is higher than the alarm value
HP steam drum water level is lower than the alarm value
IP steam drum water level is higher than the alarm value
IP steam drum water level is lower than the alarm value
LP steam drum water level is higher than the alarm value
LP steam drum water level is lower than the alarm value
HP main steam temperature H
RH temperature H
HP/IP feed water pump inlet filter DP high
HP/IP feed water pump outlet pressure low, HP drum water level lower than normal value
GT trip
HRSG fuel gas inlet smoke pressure high
HRSG fuel gas outlet smoke pressure high
6) Interlock
A One plus one HRSG trip - if HRSG bypass flue gas damper to quickly shut down, the corresponding
combustion engine trip, turbine trip - turbine generator tripping
B One plus one the combustion engine trip - HRSG trip, turbine trip - turbine generator trip (one to
one correspondence)
C Two plus one ,one combustion engine trip and corresponding HRSG trip
D Two plus one ,Turbine trip→ turbine generator trip
E Two plus one Turbine generator trip - turbine trip - if the bypass quick opening failure (# 1HRSG
corresponding # 1 bypass flue gas damper), fast close beside the two HRSGs and flue gas damper - if
HRSG bypass flue gas damper to quickly shut down, the corresponding combustion engine trip
HP/IP emergency discharge valves: when HP/IP drum water level more than HH(+102mm),
interlocking open the emergency discharge valve, HP/IP drum water level is lower than H value (-
102mm) interlock close the emergency discharge valve. Spray water main valve: when turbine
trip, interlocking close spray water valve. LP drum emergency discharge valve: when LP drum
water level HH (+102mm) and LP heater vent valve not open, interlocking, open LP emergency
discharge valve, LP drum water level is lower than the H (-102mm), interlocking close LP
emergency discharge valve.
HP:
When HRSG feed water open, close the valve when it is started. System startup high pressure steam
bypass into the cold and hot reheat, the temperature rise rate of high pressure system through the
bypass cannot control, through high pressure air exhaust valve to control.
IP:
When HRSG feed water open, can through IP air exhaust valve to adjust IP system temperature rise
rate, when IP superheat steam meet paralleling steam conditions, shut down the air exhaust valve.
LP:
When HRSG feed water open, close the valve when it is started. Go low pressure steam by-pass
system startup, the temperature rise rate of low pressure system through the bypass can't control,
can be adjusted by the lower pressure of air exhaust valve
Feed water heater recirculation control
Is the function of feed water heater recycling in order to improve feed water heater inlet water
temperature, to prevent condensation of tube fin surface and Settings. HRSG startup can be put into
recycle control, the design of the recirculation system in rated running under the steady condition,
the variable load and low load condition, should be controlled recirculation flow to protect the safe
operation of pump.
Adopt one set in a case of circulating pump, recirculation control valve according to feed water
heater 1 entry to automatically adjust the water temperature, the opening shall be limited to, the
lower limit on, the purpose is to protect the safe operation of the pump.
Feed water heater bypass control
Feed water heater bypass control system is the HRSG feed water to the water heater and/or feed
water heater around the line, the main work can be: (1) to make all of the HRSG give water to the
water heater, (2) all of the HRSG water flows through the feed water heater bypass, and (3) any part
of the flow to the water heater or bypass around the water heater. The three-way valve position can
be made of DCS root according to automatically adjust the HRSG operation form.
In the normal operation of HRSG, recirculation flow, the largest cannot meet the inlet water
temperature of feed water heater, the feed water heater import and export of differential pressure is
greater than the set value, can be part of the bypass feed water heater.