According to ISO 12354-1:2017 Building acoustics — Estimation of acoustic performance of buildings from the performance of
elements — Part 1: Airborne sound insulation between rooms
Final assessment
R'w = Rw,1+2 +Rw,2 – c R'w,standard
c – correction coefficient (noise flanking correction)
c = 2 dB for heavy load-nearing structures of reinforced concrete or heavy solid component masonry
c = 3 – 5 dB for masonry infills in skeleton load-bearing systems
c = 4 – 8 dB for lightweight constructions of wooden or gypsum plasterboard slabs in skeleton or
steel or wooden load-bearing structures
Estimation of impact sound insulation of a floor structure
According to ISO 12354-2:2017 Building acoustics — Estimation of acoustic performance of buildings from the performance of
elements — Part 2: Impact sound insulation between rooms
L'nw,standard (dB)
Floor finishing
Where
Equivalent normalized sound pressure level of the floor structure:
d (kg/m3 )
m'o
m'1 = d. (kg/m2 ) planar density of the floor structure, d (m) - thickness, . (kg/m3 ) - density Floor structure
m'o = 1 kg/m2
Weighted reduction of the sound pressure level due to the floor finishing: Concrete screed
m'2 = d2.2 (kg/m2)
(dB) - value from the following graphs
A - Weighted reduction of the sound pressure level due to the floor finishing Lnw,po (dB)
A - weighted reduction of the sound pressure level due to the floor finishing Lnw,po (dB)
TASK
Estimate R'w and L'nw of the following floor structure and compare with
standard requirements R'w,standard = 53 dB and L'nw,standard = 55 dB.
concrete floor screed, = 2100 kg/m3
50 mm
150 mm