Professional Documents
Culture Documents
8kV
SUBSTATION HAWIYAH-2
IN TAIF
Transients Analysis
SUMMARY .................................................................................... 3
APPENDIX A ............................................................................... 19
APPENDIX B ............................................................................... 43
Scope of the study is to verify that transients related with the capacitor
banks and the detuning reactors of the new substation Hawiyah-2 cause
problems neither to the capacitor banks nor to the switchgear. Emphasis
is given to inrush and outrush currents with respect to the detuning
reactor. Surge arrester selection is also verified considering restrike
transients.
Simulation software
CYME’s EMTP-RV (Electromagnetic Transients Program) version 2.2.1
was used for the entire studies described in this report.
Capacitor Banks
3-phase capacitor bank rating: 8904 kVAR.
Capacitor bank voltage rating: 15.93 kV (phase-to-phase).
Nominal frequency: 60 Hz.
Rated capacitor bank capacitance: 93.036 μF.
Connected as double star ungrounded neutral.
Harmonic filter
Tuned frequency: 279.71 Hz (single tuned).
Effective Harmonic Filter Bank Rating: 7002 kVAR at 13.8 kV.
110 kV
13.8 kV
C1 C2
C3 C4
C5 C6
BUS-A BUS-B
BUS-A BUS-B
C7
BUS-A BUS-B
, X 1 R1 X R ,
Z1
Z1 VN I SC _ 3 ph , R1
1 X R
2
Z0
Z 2 Z 1 , Z 0 3 V N I SC _ 1 ph Z 1 Z 2 , R0 , X 0 R0 X R
1 X R
2
Current
Frequency
CASE maximum Ipeak x f
(f- Hz)
(Ipeak - kA)
Current
Frequency
CASE maximum Ipeak x f
(f- Hz)
(Ipeak - kA)
Note that the detuning reactor reduces significantly the outrush current.
Assuming that the Basic Switching Impulse Level (BSL) of the 13.8 kV
reactors is approximately equal to: