Professional Documents
Culture Documents
8KV
SUBSTATION HAWIYAH-2
IN TAIF
Harmonic Analysis
SUMMARY .................................................................................... 2
1. MEASUREMENTS ....................................................................... 4
2. SYSTEM DATA........................................................................... 5
3. HARMONIC ANALYSIS .............................................................. 12
4. CONCLUSIONS........................................................................ 20
APPENDIX A ............................................................................... 21
APPENDIX B ............................................................................... 36
c. Verify that the ratings of the selected capacitor banks and detuning
reactors are adequate.
It is shown that the installation of the capacitor banks with the selected
detuning reactors reduce significantly the level of harmonic distortion in the
13.8 kV system. Additionally, it is shown that the ratings of the capacitors
are adequate for the measured harmonic pollution as well as for possible
potential increase of the harmonics.
8. IEEE Std C37.99-2000: IEEE Guide for the protection of shunt capacitor
banks.
Simulation software
The CYME 5.04 Rev 8 was used for the simulation of the network under
study.
The measurements of voltage and current (average values per hour) and
the corresponding analysis presented in terms of harmonics showed that
the level of distortion in the 11 kV system is low as voltage THD reached
values up to 1.10% of the fundamental (60 Hz) component voltage. Note
that the limit given by IEEE 519 for this voltage level is 5%. A detailed
presentation of the measurements is given in a report produced by
PROTASIS SA.
Capacitor Banks
3-phase capacitor bank rating: 8904 kVAR.
Capacitor bank voltage rating: 15.93 kV (phase-to-phase).
Nominal frequency: 60 Hz.
Rated capacitor bank capacitance: 93.036 μF.
Connected as double star ungrounded neutral.
Harmonic filter
Tuned frequency: 279.71 Hz (single tuned).
Effective Harmonic Filter Bank Rating: 7002 kVAR at 13.8 kV.
110 kV
13.8 kV
- C1 - - C2 -
- C3 - - C4 -
- C5 - - C6 -
- C7 -
For the measurement period the load of the two substations was similar.
However the worst case load is considered in this study. The load of
Substation Hawiyah had higher Current THD which indicates higher non-
linear load. Each transformer in the Taif’s Substation Hawiyah was, on
average 6.27 MW (total 18.82 MW). This load is considerable therefore the
measured harmonics is representative of the harmonic infeed for each
transformer of the new substation (6.27 MW for each transformer).
12.0
10.0
8.0
(A)
6.0
4.0
2.0
0.0
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Harmonic Order (n)
n (Amps) n (Amps)
2 0.95314 14 0.58559
3 4.06105 15 0.69600
4 0.73336 16 0.57461
5 10.58429 17 0.83637
6 0.64055 18 0.57644
7 8.12817 19 0.88312
8 0.60387 20 0.57072
9 1.01022 21 0.60163
10 0.59662 22 0.57074
11 7.94093 23 0.70754
12 0.59323 24 0.57420
13 2.99770 25 0.64605
Average I thd = 16.61 Amps
Consider the simplified circuit below. The harmonic loads are modeled as
current sources. The formula for the hth harmonic current Is,h that flows to
the system is also given. The current Is,h flowing into the system has its
maximum value when the denominator is minimum. This is the case when
the impedance of the capacitor Xcap (=-j/hωC) is equal to Xs (=jhωL)
where L is the inductance of the source. The value of h which satisfies this
requirement is called the resonant harmonic frequency (hr).
Xcap
hr
Xs
Parallel resonance
c. Verify that the ratings of the selected capacitor banks and detuning
reactors are adequate.
The limit for the voltage level under study (13.8 kV), according to IEEE
Std. 519-1992 (Recommended Practices and Requirements for Harmonic
Control in Electrical Power systems) is 5.0%.
b. For the load of the substation a power factor of 0.7 is used for the
analysed schemes. This is an extreme value, lower than the values of
the power factor during the measurements, and it guarantees that the
worst case conditions are taken into account.
c. The source side is modelled calculated using the short circuit current
and the X/R ratios given as above and the formulas below
X 1 R1 X R
Z1
Z1 VN I SC _ 3 ph , R1 ,
1 X R
2
Z0
Z 2 Z 1 , Z 0 3 V N I SC _ 1 ph Z 1 Z 2 , R0 , X 0 R0 X R .
1 X R
2
f. The same harmonic load infeed is considered for all busbars as shown
in Figure 6.
g. The study has taken in consideration the number of the feeders shown
in the SLD of the substation and cable with length 4.5km for each one,
which is an adequate length for cable feeders.
- C1 - - C2 -
- C3 - - C4 -
- C5 - - C6 -
- C7 -
Linear load
Non-linear load
Regarding the stress on the capacitor banks and the relevant limits:
(1) According to IEC Std 60 871-1;871-4 the total rms current through the
capacitor units should be less than 130% of the capacitor unit nominal
current based on rated kVAR and rated voltage.
130% of the capacitor unit nominal current based on rated kVAR and rated
voltage is 419.44 A.
(2) IEEE Std 1036-1992 allows for continuous operation of the capacitor at
a voltage 110% above the rms-rated voltage and 120% above the peak of
the rated voltage. Note that this voltage includes the harmonics and the
voltage rise seen by the capacitor due to the reactor.
The capacitor bank rated voltage is 15.93 kV. 110% of the capacitor bank
rated voltage is 17.53 kV.
(3) The final requirement for the bank is to check that the dielectric heating
of the capacitor is acceptable. The dielectric heating is evaluated by the
inequality:
|ΣV(h)I(h)||1.35Qrated|
For the capacitor bank rated kVAR Qrated is 8904 kVAR and 1.35Qrated is
equal to 12020.4 kVAR.
Frequency scans show the impedance of the system for each frequency as
it seen by a harmonic infeed from the 13.8 kV side. A peak in the
frequency scan means that if a harmonic current is injected from the load
side at the frequency of the peak, it will cause voltage harmonic
amplification (parallel resonance).
Aim of this study is to verify that the installation of the capacitor banks
does not increase the harmonic distortion of the system beyond the
acceptable limits and that the ratings of the selected capacitor banks and
reactors are adequate. Initially, the base case schemes are analyzed with
conditions similar to the ones during the measurements, that is 6.27 MW
for each transformer. Next, a higher load level is analyzed (42 MW for each
transformer) considering an equally increased (with scale factor 6.694)
harmonic infeed from the load that is served by the substation.
In Appendix A, Tables with all the relative results are given for each
scenario studied. These results are:
- System impedance (the impedance of the system at it is seen from the
13.8 kV side)
- 13.8 kV bus Voltage (for each harmonic order and in total, in terms of
rms)
- Filter current (for each harmonic order and in total in terms of rms)
- Capacitor Voltage (for each harmonic order and in total, in terms of rms)
- The product ΙnVn (n: harmonic order)
- The resulting voltage harmonic distortion (in terms of Total Harmonic
Distortion – THD) for 13.8 kV busbars.
3. The analysis shows that the stress on the equipment is well below
the limits specified by the standards considering the corresponding
ratings (provided in the previous sections). As frequency scans
show, higher substation load provides damping (lower frequency
response).
Harmonic analysis results for the Taif’s New Substation show that:
3. For the scenarios studied, the stress on the capacitors banks is not
increased due to the presence of harmonics. In all these scenarios,
there was a substantial margin for all the relevant parameters with
respect to the limits provided by the standards.
NOTES
- Current values shown refer to each capacitor bank separately.
- Harmonics up to 25th are used for the calculations.
- The calculations presented in the Tables are according to IEEE
Std-1531.-2003: IEEE Guide for Application and Specification of
Harmonic Filters
same
same
same
same
NOTES
- Current values shown refer to each capacitor bank separately.
- Harmonics up to 25th are used for the calculations.
- The calculations presented in the Tables are according to IEEE
Std-1531.-2003: IEEE Guide for Application and Specification of
Harmonic Filters
same
same
Same
Same