Subject Design of side arm charger foundations - for Wagon tippler Complex
Designed by S.Krishna sh
Project RAYALASEEMA THERMAL POWER PROJECT(1X600MW) (COAL HANDLING PACKAGE)
Subject Design of supporting system for side arm charger & Wagon tippler shed foundations
CONTENTS
1 INTRODUCTION
3 DESIGN
INTRODUCTION
This Document contains design calculations pertaining to Side Arm Charger foundation system & wagon for the
tippler shed foundations for proposed RTPP project
Designed by S.Krishna sh
Proj RAYALASEEMA THERMAL POWER PROJECT(1X600MW) (COAL HANDLING PACKAGE)
Sub Design of side arm charger foundations - for Wagon tippler Complex
Analysis and Design of Side Arm Charger Foundation
General The side arm Charger track and rollers will rest on 2300 wide and 1000 mm wide beam
resting on RC frame consists of RC column spaced at aprox 3.0 to 4.0m c/c and tie beams are
provided at various intervals and the foundations are resting on firm strata/
The columns are tied at various intermediate levels as shown in GA..
The basic general arrangement and loading is taken from civil requirement of side arm charger
drawing no. 7M0024 00100001 , SHEET 1 TO 3 , GA and load data of wagon tippler complex
Design Loading on side arm charger track and guide rollers are as mentioned
below 8 tm
19 20 20
7.25 19 I I
2t
2.25 20.5
12.105
10.105+1*2
As the loading is spaced at 10.105m c/c and the effective length of block is considered 10.105+1*2 =12.105
m, H
stopper block
Proj RAYALASEEMA THERMAL POWER PROJECT(1X600MW) (COAL HANDLING PACKAGE)
Sub Design of side arm charger foundations - for Wagon tippler Complex
elevation
plan
-12.5m lvl
-20.6m lvl
details SAC foundation
PROJECT RAYALASEEMA THERMAL POWER PROJECT(1X600MW) (COAL HANDLING PACKAGE)
TITLE Design of side arm charger foundations - for Wagon tippler Complex
Loading
Design of footing
Ox = 1.025 m
Oy = 0.88 m
BMx = 48.16 tm
bx = 2.50 m
M/bd2 = 0.55
pt = 0.13
Ast = 1927.88 sqmm
Ast per metre width = 771.15 sqmm
Provide Y16-150 = 1350.00 sqmm minimum Ast = 780 sqmm
pt = 0.23
Bmy = 69.16 tm
by = 3.00 m
M/bd2 = 0.66
pt = 0.16
Ast = 2783.46 sqmm
Ast per metre width = 927.82 sqmm
Provide Y16-150 = 1350.00 sqmm minimum Ast = 780 sqmm
pt = 0.23
details SAC foundation
PROJECT RAYALASEEMA THERMAL POWER PROJECT(1X600MW) (COAL HANDLING PACKAGE)
TITLE Design of side arm charger foundations - for Wagon tippler Complex
Shear Design :
tpeff. = 0.59
(A) Check for Two Way shear (ie Punching shear)
Desiged P = 245.15 t
a1 = 1.040 m
a2 = 1.840 m
t1 = 0.650 m
t2 = 0.650 m
a1 = 2.500 m
a2 = 3.000 m
_ indicates
shear section
falls out of the
footing