Any Deviation
between Technical Reply on
Make Observation /
BOQ Item Technical Specification as per Approved Makes Specification as Observation /
BOQ Item Description Proposed by Technical Specification offered by OEM Recommendat
No. Agreement as per Agreement per agreement Recommendatio
Agency ion of M/s Egis
and offered by n of M/s Egis
OEM
Motor Driven Pump Sets:
Capacity 2850 LPM at 100 m head
Type: Horizontal Split case Multistage
centrifugal Axially Spit casing pump with side
Providing, Fixing, electric driven main fire Hydrant /
suction ‐ side discharge
Sprinkler pumps suitable for automatic operation
Usage: For Hydrant System and Sprinkler
complete in all respect as required & specified and
System
consisting of the following:
Performance Testing Std: As per OEM Std. (ISO‐
Horizontal type multistage, end suction , top discharge ,
9906‐Gr2B / IS 9137 Class C)
centrifugal, split casing pump of cast iron body and
bronze impeller with stainless steel shaft , mechanical GRUNDFOS/ MOC:Body: CI (IS:210 Gr FG260) With
seal, to ensure minimum pressure of 3.5 kg/cm2 at KIRLOSKAR* Impellers: Bronze (IS:318, Gr LTB2) reference to
highest and farthest outlet at specified flow of 2850 This chapter covers the general /BEACONS*/ Neck Ring : Bronze (IS:318, Gr LTB5) EGIS Letter ‐
LPM & 100 m head conforming to IS‐ 1520 complete requirement of water pumps for MATHER & Shaft: SS 410 (SS ASTM A 276 CL 410) Egis India/ AAI/
with all accessories etc. as required The pump shall be main fire pump, jockey PLATT*/ Stuffing Box: Mechanical Seal LKO/ 2019/
capable of furnishing not less than 150% of rated (pressurization) pump and CROMPTON*/
WILO (Mather Base Frame: Mild Steel 44888/ 353
1110.00 capacity at a head not less than 65% or rated head. The sprinkler pump. WASP*/ KSB* Comply
& Platt) Splitcase
shut off head shall not exceed 120% of rated head. CAPACITY: The discharge and /JYOTI*/ BE*/
Driver: Motor, 90kW, Squirrel cage Induction Multistage
Suitable HP Squirrel cage Induction motor suitable for head of the pumps shall be as VOL TAS* /
motor suitable for operation on 415VAC, 3 Centrifugal
operation on 415V, 3 phase, 50Hz, AC supply suitable mentioned in Schedule of GREAVES*/
phase, 50Hz,TEFC type confirming to IS 12615 Pump with
for the above pump rating , TEFC type confirming to Quantities. KALAMA*/
with IP:55 protection (MOTOR, IS‐325 IS Side Suction to
IS‐325 with IP:55 protection for enclosure, horizontal AMRUT*/ PEC*/
OBSOLATED AND REPLACED BY LATEST IS STD. be provided
foot mounted with class F insulation, flexible coupling & BE*/ SUGUNA*
Which Is : IS 12615 /
coupling guard with the pump complete as redocument
Motr Testing Std : IEC 60034 )
bed plate fabricated from MS channel / ISMB with
spring type vibration isolators. The pump set base shall
be held by bolts grouted in the suitable RCC ( 1:2:4)
foundation duly plastered including foundation bolts, IS Condition:
washers complete as reqd. Fire Pumps shall be capable of delivering not
less than 150% of the rated capacity of water
at a head of not less than 65% of the rated
head. The shut‐off head shall not exceed 120%
of the rated head.
Comments Compliance Statement of Technical Datasheets for Fire Fighting System at Lucknow Airport
Any Deviation between Reply on
Approved Makes Make Observation /
BOQ Item Technical Specification Observation /
BOQ Item Description Technical Specification as per Agreement as per Proposed by Technical Specification offered by OEM Recommendation
No. as per agreement and Recommendatio
Agreement Agency of M/s Egis
offered by OEM n of M/s Egis
Providing, Fixing, of Diesel engine driven standby fire pump suitable
for automatic operation complete in all respect as required &
specified and consisting of the following: Horizontal type multistage, Engine Driven Pump Sets:
end suction , top discharge , centrifugal, split casing pump of cast iron Capacity 2850 LPM at 100 m head
body and bronze impeller with stainless steel shaft , mechanical seal,
to ensure minimum pressure of 3.5 kg/cm2 at highest and farthest
outlet at specified flow of 2850 LPM & 100 m head conforming to IS‐ Type: Horizontal Split case Multistage
1520 complete with all accessories etc. as required The pump shall be centrifugal Axially Spit casing pump with side
capable of furnishing not less than 150% of rated capacity at a head suction ‐ side discharge
not less than 65% or rated head. The shut off head shall not exceed Usage: For Hydrant System and Sprinkler
120% of rated head. Heat Exchanger ( Water ) cooled diesel engine System
developing required BHP suitable for the pump, flexible coupling & Performance Testing Std: As per OEM Std.
coupling guard with the pump & common bed plate for mounting of (ISO‐9906‐Gr2B / IS 9137 Class C)
engine & pump shall confirming to relevant BS/IS standard with auto
starting mechanism. The common base frame shall be held by bolts
MOC:Body: CI (IS:210 Gr FG260)
grouted in the concrete including foundation bolts, washers as
Impellers: Bronze (IS:318, Gr LTB2)
required, vibration damping arrangement by cushy foot & engine With reference to
Neck Ring : Bronze (IS:318, Gr LTB5)
panel with battery charger provided by engine manufacturer, Wilo EGIS Letter ‐ Egis
Shaft: SS 410 (SS ASTM A 276 CL 410)
connection to engine starting panel, lead acid batteries of 12V/24V, This chapter covers the general requirement of water (Mather & India/ AAI/ LKO/
Stuffing Box: Mechanical Seal
180AH with casing, lugs, stand & terminations to diesel engine, pumps for main fire pump, jockey (pressurization) pump ASHOK LEYLAND Platt Pump 2019/ 44888/ 353
Base Frame: Mild Steel
1111.00 charger complete in all respect. Exhaust pipe of required length ( and sprinkler pump. / KIRLOSKAR OIL / with Comply Splitcase
discharge to leave above roof level as per standard) with 50mm thick CAPACITY: The discharge and head of the pumps shall be CUMMINS KIRLOSKAR Multistage
glass wool pipe section, covered with aluminium cladding, residential as mentioned in Schedule of Quantities. Engine Driver: Diesel Engine, 127 BHP, 1500RPM / Centrifugal Pump
silencer muffler, instruments & protection‐stop solenoid for auto stop (KOEL) Heat Exchanger Cooled with Side Suction
in the event of fault with auto indications, day oil tank of 200 ltrs. with Battery: 24 V, (12V*2 nos.)180AH to be provided
first charge of diesel fabricated out of 4mm MS sheet with inlet/ outlet Diesel Tank: 200 Ltrs with all necessary
ON/OFF valves, level indicator, drain pipe, 15mm dia MS fuel line accessories
complete as reqd. Common bed plate of fabricated MS channel / ISMB
with vibration isolator. The base frame shall be held by bolts grouted
in the suitable cement concrete foundation duly plastered including
foundation bolts, washers as required.
IS Condition:
Fire Pumps shall be capable of delivering not
less than 150% of the rated capacity of water
at a head of not less than 65% of the rated
head. The shut‐off head shall not exceed 120%
of the rated head.
Comments Compliance Statement of Technical Datasheets for Fire Fighting System at Lucknow Airport
Any Deviation between Reply on
Approved Makes Make Observation /
BOQ Item Technical Specification as Observation /
BOQ Item Description Technical Specification as per Agreement as per Proposed by Technical Specification offered by OEM Recommendat
No. per agreement and offered Recommendatio
Agreement Agency ion of M/s Egis
by OEM n of M/s Egis
Motor Driven Pump Sets:
Capacity 180 LPM at 100 m & 35 m head
Providing, Fixing, electric driven Pressurization Pump Type:Horizontal Certrifugal type end suction,
suitable for automatic operation complete as required top discharge
& as specified and consisting of the following: Usage: For Hydrant System, Sprinkler System
GRUNDFOS/
Horizontal type end suction, top discharge, centrifugal, and Water Curtain System.
KIRLOSKAR*
Jockey pump of cast iron body and bronze impeller, Performance Testing Std: As per OEM Std.
/BEACONS*/
with SS shaft, to ensure at highest and farthest outlet (ISO‐9906‐Gr2B / IS 9137 Class C)
This chapter covers the general MATHER &
confirming to IS‐1520 complete with all accessories as
requirement of water pumps for main PLATT*/ MOC:Body: CI (IS:210 Gr FG260)
required. Suitable HP Squirrel cage induction motor
fire pump, jockey (pressurization) pump CROMPTON*/ Wilo Impellers: Bronze (IS:318, Gr LTB2)
suitable for 415 V, 3 phase,50Hz, AC supply for the
1112.00 and sprinkler pump. WASP*/ KSB* (Mather & Neck Ring : Bronze (IS:318, Gr LTB5) Comply ‐
above pump T.E.F.C. type confirming to IS ‐ 325 with
CAPACITY: The discharge and head of /JYOTI*/ BE*/ Platt) Shaft: SS 410 (SS ASTM A 276 CL 410)
IP:55 protection for enclosure, horizontal foot
the pumps shall be as mentioned in VOL TAS* / Stuffing Box: Mechanical Seal
mounted, class‐F insulation, flexible coupling & coupling
Schedule of Quantities. GREAVES*/ Base Frame: Mild Steel
guard with the pump complete in all respects.
KALAMA*/
Common base frame shall be fabricated from MS
AMRUT*/ PEC*/
channel / ISMB with vibration isolator. The base frame Driver: Motor, 15 kW & 3.7 kW, Squirrel cage
BE*/ SUGUNA*
shall be held by bolts grouted in the suitable RCC (1:2:4) Induction motor suitable for operation on
foundation duly plastered including foundation bolts, 415VAC, 3 phase, 50Hz,TEFC type confirming
washers complete as reqd. to IS 12615 with IP:55 protection (MOTOR, IS‐
325 IS OBSOLATED AND REPLACED BY LATEST
IS STD. Which Is : IS 12615 /
Motr Testing Std : IEC 60034 )
Comments Compliance Statement of Technical Datasheets for Fire Fighting System at Lucknow Airport
Any Deviation between Reply on
Make Observation /
BOQ Item Approved Makes Technical Specification Observation /
BOQ Item Description Technical Specification as per Agreement Proposed by Technical Specification offered by OEM Recommendat
No. as per Agreement as per agreement and Recommendatio
Agency ion of M/s Egis
offered by OEM n of M/s Egis
Motor Driven Pump Sets:
Capacity 1620 LPM at 35 m head
Providing, Fixing, of electric driven main fire Water curtain pumps
suitable for automatic operation complete in all respect as required & Type: Horizontal Split case Multistage
specified and consisting of the following: Horizontal type multistage, centrifugal Axially Spit casing pump with side
end suction, top discharge , centrifugal, split casing pump of cast iron suction ‐ side discharge
GRUNDFOS/ Usage: For Water Curtain System
body and bronze impeller with stainless steel shaft, to ensure With
KIRLOSKAR* Performance Testing Std: As per OEM Std.
minimum pressure of 3.5 kg/cm2 at highest and farthest outlet at reference to
/BEACONS*/ (ISO‐9906‐Gr2B / IS 9137 Class C)
specified flow of 1620 LPM & 35 m head conforming to IS‐ 1520 EGIS Letter ‐
This chapter covers the general MATHER &
complete with mechanical seals, safety relief valve, complete with all Egis India/ AAI/
requirement of water pumps for main PLATT*/
accessories etc as required. The pump shall be capable of furnishing MOC:Body: CI (IS:210 Gr FG260) LKO/ 2019/
fire pump, jockey (pressurization) pump CROMPTON*/ Wilo
not less than 150% of rated capacity at a head not less than 65% or 44888/ 353
1113.00 and sprinkler pump. WASP*/ KSB* (Mather & Impellers: Bronze (IS:318, Gr LTB2) Comply
rated head. The shut off head shall not exceed 120% of rated head. Neck Ring : Bronze (IS:318, Gr LTB5) Splitcase
CAPACITY: The discharge and head of the /JYOTI*/ BE*/ Platt)
Suitable HP Squirrel cage Induction motor suitable for operation on Shaft: SS 410 (SS ASTM A 276 CL 410) Multistage
pumps shall be as mentioned in Schedule VOL TAS* /
415V, 3 phase, 50Hz, AC supply for the above pump TEFC type Stuffing Box: Mechanical Seal Centrifugal
of Quantities. GREAVES*/
confirming to IS‐325 with IP:55 protection for enclosure, horizontal Base Frame: Mild Steel Pump with
KALAMA*/
foot mounted with class F insulation, flexible coupling & coupling Side Suction to
AMRUT*/ PEC*/
guard with the pump complete as reqd. be provided
BE*/ SUGUNA*
Common bed plate fabricated from MS channel / ISMB with spring
type vibration isolators. The pump set base shall be held by bolts Driver: Motor, 18.5 kW, Squirrel cage Induction
grouted in the suitable RCC (1:2:4) foundation duly plastered including motor suitable for operation on 415VAC, 3
foundation bolts, washers complete as reqd. phase, 50Hz,TEFC type confirming to IS‐325
with IP:55 protection
Compliance Statement of Technical Datasheet for Motors ‐ Fire Fighting System at Lucknow Airport
Any Deviation between
CATEGORY OF TEST Observation /
Approved Makes as per Make Proposed by Technical Specification as
BOQ Item No. BOQ Item Description Technical Specification as per Agreement CERTIFICATE / Technical Specification offered by OEM Recommendation of M/s
Agreement Agency per agreement and offered
INSPECTION Egis
by OEM
Any Deviation between Technical Observation /
Approved Makes as per Make Proposed by
BOQ Item No. BOQ Item Description Technical Specification as per Agreement Technical Specification offered by OEM Specification as per agreement and Recommendation of M/s
Agreement Agency
offered by OEM Egis
IS Condition:
Fire Pumps shall be capable of delivering not
less than 150% of the rated capacity of water
at a head of not less than 65% of the rated
head. The shut‐off head shall not exceed 120%
of the rated head.