Comments Compliance Statement of Technical Datasheets for Fire Fighting System at Lucknow Airport

Any Deviation 
between Technical  Reply on 
Make  Observation / 
BOQ Item  Technical Specification as per  Approved Makes  Specification as  Observation / 
BOQ Item Description Proposed by  Technical Specification offered by OEM Recommendat
No. Agreement as per Agreement per agreement  Recommendatio
Agency ion of M/s Egis
and offered by  n of M/s Egis
OEM 

Motor Driven Pump Sets: 
Capacity 2850 LPM at 100 m head

Type: Horizontal Split case Multistage 
centrifugal Axially Spit casing  pump with side 
Providing, Fixing, electric driven main fire Hydrant / 
suction ‐ side discharge   
Sprinkler pumps suitable for automatic operation 
Usage: For Hydrant System and Sprinkler 
complete in all respect as required & specified and 
System
consisting of the following:
Performance Testing Std: As per OEM Std. (ISO‐
Horizontal type multistage, end suction , top discharge , 
9906‐Gr2B / IS 9137 Class C)
centrifugal, split casing pump of cast iron body and 
bronze impeller with stainless steel shaft , mechanical  GRUNDFOS/  MOC:Body: CI (IS:210 Gr FG260)  With 
seal, to ensure minimum pressure of 3.5 kg/cm2 at  KIRLOSKAR*  Impellers: Bronze (IS:318, Gr LTB2) reference to 
highest and farthest outlet at specified flow of 2850  This  chapter  covers  the  general   /BEACONS*/ Neck Ring : Bronze (IS:318, Gr LTB5) EGIS Letter ‐ 
LPM & 100 m head conforming to IS‐ 1520 complete  requirement  of  water  pumps  for   MATHER &  Shaft: SS 410 (SS ASTM A 276 CL 410) Egis India/ AAI/ 
with all accessories etc. as required The pump shall be  main  fire  pump,  jockey   PLATT*/  Stuffing Box: Mechanical Seal LKO/ 2019/ 
capable of furnishing not less than 150% of rated  (pressurization) pump and  CROMPTON*/
WILO (Mather  Base Frame: Mild Steel 44888/ 353
1110.00 capacity at a head not less than 65% or rated head. The  sprinkler pump.  WASP*/ KSB*  Comply
& Platt) Splitcase 
shut off head shall not exceed 120% of rated head.  CAPACITY:  The  discharge  and   /JYOTI*/ BE*/ 
Driver: Motor, 90kW, Squirrel cage Induction  Multistage 
Suitable HP Squirrel cage Induction motor suitable for  head  of  the  pumps  shall  be  as   VOL TAS* / 
motor suitable for operation on 415VAC, 3  Centrifugal 
operation on 415V, 3 phase, 50Hz, AC supply suitable  mentioned  in  Schedule  of   GREAVES*/ 
phase, 50Hz,TEFC type confirming to IS 12615  Pump with 
for the above pump rating , TEFC type confirming to  Quantities. KALAMA*/ 
with IP:55 protection (MOTOR, IS‐325 IS  Side Suction to 
IS‐325 with IP:55 protection for enclosure, horizontal  AMRUT*/ PEC*/
OBSOLATED AND REPLACED BY LATEST IS STD.  be provided  
foot mounted with class F insulation, flexible coupling &  BE*/ SUGUNA*
Which Is :  IS 12615 / 
coupling guard with the pump complete as redocument 
Motr Testing Std : IEC 60034 )
bed plate fabricated from MS channel / ISMB with 
spring type vibration isolators. The pump set base shall 
be held by bolts grouted in the suitable RCC ( 1:2:4) 
foundation duly plastered including foundation bolts,  IS Condition: 
washers complete as reqd.  Fire Pumps shall be capable of delivering not 
less than 150% of the rated capacity of water 
at a head of not less than 65% of the rated 
head. The shut‐off head shall not exceed 120% 
of the rated head.
Comments Compliance Statement of Technical Datasheets for Fire Fighting System at Lucknow Airport

Any Deviation between  Reply on 
Approved Makes  Make  Observation / 
BOQ Item  Technical Specification  Observation / 
BOQ Item Description Technical Specification as per Agreement as per  Proposed by  Technical Specification offered by OEM Recommendation 
No. as per agreement and  Recommendatio
Agreement Agency of M/s Egis
offered by OEM  n of M/s Egis

Providing, Fixing, of Diesel engine driven standby fire pump suitable 
for automatic operation complete in all respect as required & 
specified and consisting of the following: Horizontal type multistage,  Engine Driven Pump Sets: 
end suction , top discharge , centrifugal, split casing pump of cast iron  Capacity 2850 LPM at 100 m head
body and bronze impeller with stainless steel shaft , mechanical seal, 
to ensure minimum pressure of 3.5 kg/cm2 at highest and farthest 
outlet at specified flow of 2850 LPM & 100 m head conforming to IS‐  Type: Horizontal Split case Multistage 
1520 complete with all accessories etc. as required The pump shall be  centrifugal Axially Spit casing  pump with side 
capable of furnishing not less than 150% of rated capacity at a head  suction ‐ side discharge   
not less than 65% or rated head. The shut off head shall not exceed  Usage: For Hydrant System and Sprinkler 
120% of rated head. Heat Exchanger ( Water ) cooled diesel engine  System
developing required BHP suitable for the pump, flexible coupling &  Performance Testing Std: As per OEM Std. 
coupling guard with the pump & common bed plate for mounting of  (ISO‐9906‐Gr2B / IS 9137 Class C)
engine & pump shall confirming to relevant BS/IS standard with auto 
starting mechanism. The common base frame shall be held by bolts 
MOC:Body: CI (IS:210 Gr FG260)
grouted in the concrete including foundation bolts, washers as 
Impellers: Bronze (IS:318, Gr LTB2)
required, vibration damping arrangement by cushy foot & engine   With reference to 
Neck Ring : Bronze (IS:318, Gr LTB5)
panel with battery charger provided by engine manufacturer,  Wilo  EGIS Letter ‐ Egis 
Shaft: SS 410 (SS ASTM A 276 CL 410)
connection to engine starting panel, lead acid batteries of 12V/24V,  This  chapter  covers  the  general  requirement  of  water   (Mather &  India/ AAI/ LKO/ 
Stuffing Box: Mechanical Seal
180AH with casing, lugs, stand & terminations to diesel engine,  pumps  for  main  fire  pump,  jockey  (pressurization) pump  ASHOK LEYLAND  Platt Pump  2019/ 44888/ 353
Base Frame: Mild Steel
1111.00 charger complete in all respect. Exhaust pipe of required length (  and sprinkler pump.  / KIRLOSKAR OIL / with  Comply Splitcase 
discharge to leave above roof level as per standard) with 50mm thick  CAPACITY:  The  discharge  and  head  of  the  pumps  shall  be   CUMMINS KIRLOSKAR  Multistage 
glass wool pipe section, covered with aluminium cladding, residential  as  mentioned  in  Schedule  of  Quantities. Engine  Driver: Diesel Engine, 127 BHP, 1500RPM /  Centrifugal Pump 
silencer muffler, instruments & protection‐stop solenoid for auto stop  (KOEL)  Heat Exchanger Cooled with Side Suction 
in the event of fault with auto indications, day oil tank of 200 ltrs. with  Battery: 24 V, (12V*2 nos.)180AH  to be provided  
first charge of diesel fabricated out of 4mm MS sheet with inlet/ outlet  Diesel Tank: 200 Ltrs with all necessary 
ON/OFF valves, level indicator, drain pipe, 15mm dia MS fuel line  accessories
complete as reqd. Common bed plate of fabricated MS channel / ISMB 
with vibration isolator. The base frame shall be held by bolts grouted 
in the suitable cement concrete foundation duly plastered including 
foundation bolts, washers as required.

IS Condition: 
Fire Pumps shall be capable of delivering not 
less than 150% of the rated capacity of water 
at a head of not less than 65% of the rated 
head. The shut‐off head shall not exceed 120% 
of the rated head.
Comments Compliance Statement of Technical Datasheets for Fire Fighting System at Lucknow Airport

Any Deviation between  Reply on 
Approved Makes  Make  Observation / 
BOQ Item  Technical Specification as  Observation / 
BOQ Item Description Technical Specification as per Agreement as per  Proposed by  Technical Specification offered by OEM Recommendat
No. per agreement and offered  Recommendatio
Agreement Agency ion of M/s Egis
by OEM  n of M/s Egis

Motor Driven Pump Sets: 
Capacity 180 LPM at 100 m & 35 m head 

Providing, Fixing, electric driven Pressurization Pump  Type:Horizontal Certrifugal type end suction, 
suitable for automatic operation complete as required  top discharge
& as specified and consisting of the following: Usage: For Hydrant System, Sprinkler System 
GRUNDFOS/ 
Horizontal type end suction, top discharge, centrifugal,  and Water Curtain System.
KIRLOSKAR* 
Jockey pump of cast iron body and bronze impeller,  Performance Testing Std: As per OEM Std. 
/BEACONS*/
with SS shaft, to ensure at highest and farthest outlet  (ISO‐9906‐Gr2B / IS 9137 Class C)
This  chapter  covers  the  general   MATHER & 
confirming to IS‐1520 complete with all accessories as 
requirement  of  water  pumps  for  main   PLATT*/  MOC:Body: CI (IS:210 Gr FG260)
required. Suitable HP Squirrel cage induction motor 
fire  pump,  jockey  (pressurization) pump  CROMPTON*/ Wilo  Impellers: Bronze (IS:318, Gr LTB2)
suitable for 415 V, 3 phase,50Hz, AC supply for the 
1112.00 and sprinkler pump.  WASP*/ KSB*  (Mather &  Neck Ring : Bronze (IS:318, Gr LTB5) Comply  ‐ 
above pump T.E.F.C. type confirming to IS ‐ 325 with 
CAPACITY:  The  discharge  and  head  of   /JYOTI*/ BE*/  Platt) Shaft: SS 410 (SS ASTM A 276 CL 410)
IP:55 protection for enclosure, horizontal foot 
the  pumps  shall  be  as  mentioned  in   VOL TAS* /  Stuffing Box: Mechanical Seal
mounted, class‐F insulation, flexible coupling & coupling 
Schedule  of  Quantities. GREAVES*/  Base Frame: Mild Steel
guard with the pump complete in all respects.
KALAMA*/ 
Common base frame shall be fabricated from MS 
AMRUT*/ PEC*/
channel / ISMB with vibration isolator. The base frame  Driver: Motor, 15 kW & 3.7 kW, Squirrel cage 
BE*/ SUGUNA*
shall be held by bolts grouted in the suitable RCC (1:2:4)  Induction motor suitable for operation on 
foundation duly plastered including foundation bolts,  415VAC, 3 phase, 50Hz,TEFC type confirming 
washers complete as reqd. to IS 12615 with IP:55 protection (MOTOR, IS‐
325 IS OBSOLATED AND REPLACED BY LATEST 
IS STD. Which Is :  IS 12615 / 
Motr Testing Std : IEC 60034 )
Comments Compliance Statement of Technical Datasheets for Fire Fighting System at Lucknow Airport

Any Deviation between  Reply on 
Make  Observation / 
BOQ Item  Approved Makes  Technical Specification  Observation / 
BOQ Item Description Technical Specification as per Agreement Proposed by  Technical Specification offered by OEM Recommendat
No. as per Agreement as per agreement and  Recommendatio
Agency ion of M/s Egis
offered by OEM  n of M/s Egis

Motor Driven Pump Sets: 
Capacity 1620 LPM at 35 m head

Providing, Fixing, of electric driven main fire Water curtain pumps 
suitable for automatic operation complete in all respect as required &  Type: Horizontal Split case Multistage 
specified and consisting of the following: Horizontal type multistage,  centrifugal Axially Spit casing  pump with side 
end suction, top discharge , centrifugal, split casing pump of cast iron  suction ‐ side discharge   
GRUNDFOS/  Usage: For Water Curtain System
body and bronze impeller with stainless steel shaft, to ensure   With 
KIRLOSKAR*  Performance Testing Std: As per OEM Std. 
minimum pressure of 3.5 kg/cm2 at highest and farthest outlet at  reference to 
/BEACONS*/ (ISO‐9906‐Gr2B / IS 9137 Class C)
specified flow of 1620 LPM & 35 m head conforming to IS‐ 1520  EGIS Letter ‐ 
This  chapter  covers  the  general   MATHER & 
complete with mechanical seals, safety relief valve, complete with all  Egis India/ AAI/ 
requirement  of  water  pumps  for  main   PLATT*/ 
accessories etc as required. The pump shall be capable of furnishing  MOC:Body: CI (IS:210 Gr FG260) LKO/ 2019/ 
fire  pump,  jockey  (pressurization) pump  CROMPTON*/ Wilo 
not less than 150% of rated capacity at a head not less than 65% or  44888/ 353
1113.00 and sprinkler pump.  WASP*/ KSB*  (Mather &  Impellers: Bronze (IS:318, Gr LTB2) Comply
rated head. The shut off head shall not exceed 120% of rated head.  Neck Ring : Bronze (IS:318, Gr LTB5) Splitcase 
CAPACITY:  The  discharge  and  head  of  the   /JYOTI*/ BE*/  Platt)
Suitable HP Squirrel cage Induction motor suitable for operation on  Shaft: SS 410 (SS ASTM A 276 CL 410) Multistage 
pumps  shall  be  as  mentioned  in  Schedule   VOL TAS* / 
415V, 3 phase, 50Hz, AC supply for the above pump TEFC type  Stuffing Box: Mechanical Seal Centrifugal 
of  Quantities. GREAVES*/ 
confirming to IS‐325 with IP:55 protection for enclosure, horizontal  Base Frame: Mild Steel Pump with 
KALAMA*/ 
foot mounted with class F insulation, flexible coupling & coupling  Side Suction to 
AMRUT*/ PEC*/
guard with the pump complete as reqd. be provided  
BE*/ SUGUNA*
Common bed plate fabricated from MS channel / ISMB with spring 
type vibration isolators. The pump set base shall be held by bolts  Driver: Motor, 18.5 kW, Squirrel cage Induction 
grouted in the suitable RCC (1:2:4) foundation duly plastered including  motor suitable for operation on 415VAC, 3 
foundation bolts, washers complete as reqd. phase, 50Hz,TEFC type confirming to IS‐325 
with IP:55 protection
Compliance Statement of Technical Datasheet for Motors ‐ Fire Fighting System at Lucknow Airport

Any Deviation between 
CATEGORY OF TEST Observation / 
Approved Makes as per  Make Proposed by  Technical Specification as 
BOQ Item No. BOQ Item Description Technical Specification as per Agreement  CERTIFICATE / Technical Specification offered by OEM Recommendation of M/s 
Agreement Agency per agreement and offered 
INSPECTION Egis
by OEM 

1110.00 Providing,  Fixing, electric driven main fire Hydrant / Sprinkler pumps suitable for automatic  CA Page No. 1073 of Volume‐II BHARAT BIJLEE/ KIROLSKAR* / CGL CATEGORY ‐ 2 Motor for Main Hydrant / Sprinkler Pump: Comply


operation complete in all respect as required  & specified and consisting of the following: Cl. No. 17.2 MOTORS FOR ELECTRIC DRIVEN PUMPS ALSTOM*/ SIEMENS*/  Qty: 2 Nos.
Horizontal type multistage, end suction , top discharge , centrifugal, split casing pump of cast iron  17.2.1 Electrically driven pumps shall be provided with totally enclosed fan cooled induction JYOTHI* / ABB*/  Type: 3 Phase AC Squirrel Cage Induction Motor.
body and bronze impeller with stainless steel shaft , mechanical seal, to ensure minimum pressure  motors. For fire pumps, the motors should be rated not to draw starting current more than CROMPTON*/ NGEF* Voltage: 415 ± 10% V
of 3.5 kg/cm2 at highest and farthest outlet at specified flow of 2850 LPM & 100 m head  3 times normal running current. Frequency: 50±5% Hz
conforming  to IS‐ 1520 complete with  all accessories etc. as required. The pump shall be capable  17.2.2 Motors for Main fire pumps shall be at least equivalent to the horse power required to drive the  Insulation: TEFC
of furnishing not less than 150% of rated capacity  at a head not less than 65% or rated head. The  pump at 150% of its rated discharge and shall be designed for continuous full load duty and shall be design  Insulation Class: F Class
shut off head shall  not exceed 120% of rated head. proven in similar service. Type of Protection: IP 55
Suitable HP Squirrel cage Induction motor suitable for operation on 415V, 3 phase, 50Hz, AC  17.2.3 Motors shall be suitable for 415 volts +/ ‐ 10%, 3 Phase, 50 Hz, A.C supply with class –F Applicable Standard: IS12615, IEC60034‐1
supply suitable  for the above pump rating , TEFC type confirming to IS ‐325 with IP:55  insulation, TEFC and conform to IS: 325. Mounting: Horizontal Foot‐B3
protection for enclosure, horizontal foot mounted with class F insulation, flexible coupling &  17.2.4 Motors shall be capable of handling the required starting torque of the pumps. KW required at Rated Duty Parameter: 64.82 KW
coupling guard with the pump complete as reqd.. Common bed plate fabricated from MS channel  17.2.5 Contractor shall provide heating arrangements (Space Heaters) for the main fire pump motor to  KW required at 150%  of Rated Capacity: 77.41 KW
/ ISMB with spring type vibration isolators. The pump set base shall be held by bolts grouted  in the ensure that motor windings shall remain dry. KW offered: 90 KW
suitable  RCC ( 1:2:4)  foundation duly plastered including foundation bolts, washers complete as  Space Heater: 60 Watt X 2 
reqd. Voltage : 220‐240V 
Frame: ND280M
for starting current we recommanded to used Soft starter panel which part of 
other vendor.

1112.00 Providing,  Fixing,  electric  driven  Pressurization  Pump  suitable  for  automatic  operation   CA Page No. 1073 of Volume‐II BHARAT BIJLEE/ KIROLSKAR* / CGL CATEGORY ‐ 2 Motor for Jockey Pump for Hydrant / Sprinkler System: Comply


complete  as  required  &  as  specified  and consisting of the following: Cl. No. 17.2 MOTORS FOR ELECTRIC DRIVEN PUMPS ALSTOM*/ SIEMENS*/  Qty: 2 Nos.
Horizontal type end suction, top discharge, centrifugal, Jockey pump of cast iron body and bronze  17.2.1 Electrically driven pumps shall be provided with totally enclosed fan cooled induction JYOTHI* / ABB*/  Type: 3 Phase AC Squirrel Cage Induction Motor.
impeller, with SS shaft, to ensure at highest and farthest outlet confirming to IS‐1520 complete  motors. For fire pumps, the motors should be rated not to draw starting current more than CROMPTON*/ NGEF* Voltage: 415 ± 10% V
with all accessories as required. 3 times normal running current. Frequency: 50±5% Hz
Suitable HP Squirrel cage induction motor suitable for 415 V, 3 phase,50Hz, AC supply for the  17.2.2 Motors for Main fire pumps shall be at least equivalent to the horse power required to drive the  Insulation: TEFC
above pump  T.E.F.C. type confirming to IS ‐ 325 with  IP:55 protection for enclosure, horizontal  pump at 150% of its rated discharge and shall be designed for continuous full load duty and shall be design  Insulation Class: F Class
foot mounted, class‐F insulation, flexible coupling & coupling guard with the pump complete in  proven in similar service. Type of Protection: IP 55
all respects. 17.2.3 Motors shall be suitable for 415 volts +/ ‐ 10%, 3 Phase, 50 Hz, A.C supply with class –F Applicable Standard: IS12615, IEC60034‐1
Common  base  frame  shall  be  fabricated  from  MS  channel  /  ISMB  with  vibration  isolator.   insulation, TEFC and conform to IS: 325. Mounting: Horizontal Foot‐B3
The  base  frame  shall  be  held  by  bolts grouted in the suitable RCC (1:2:4) foundation duly  17.2.4 Motors shall be capable of handling the required starting torque of the pumps. KW Offered: 15 KW (150% Condition is Not Applicable)
plastered including foundation bolts, washers complete as reqd. 17.2.5 Contractor shall provide heating arrangements (Space Heaters) for the main fire pump motor to  Space Heater: Not Required
ensure that motor windings shall remain dry. Frame: ND160M
for starting current we recommanded to used Soft starter panel which part of 
other vendor.
Motor for Jockey Pump for Water Curtain System:
Qty: 1 No.
Type: 3 Phase AC Squirrel Cage Induction Motor.
Voltage: 415 ± 10% V
Frequency: 50±5% Hz
Insulation: TEFC
Insulation Class: F Class
Type of Protection: IP 55
Applicable Standard: IS12615, IEC60034‐1
Mounting: Horizontal Foot‐B3
KW Offered: 3.7 KW (150% Condition is Not Applicable)
Space Heater: Not Required
Frame: ND100L
for starting current we recommanded to used Soft starter panel which part of 
other vendor.

1113.00 Providing,  Fixing,  of  electric  driven  main  fire  Water  curtain  pumps  suitable  for  automatic   CA Page No. 1073 of Volume‐II BHARAT BIJLEE/ KIROLSKAR* / CGL CATEGORY ‐ 2 Motor for Water Curtain Pump: Comply


operation  complete  in  all  respect  as required  & specified and consisting of the following: Cl. No. 17.2 MOTORS FOR ELECTRIC DRIVEN PUMPS ALSTOM*/ SIEMENS*/  Qty: 1 No.
Horizontal type multistage, end suction, top discharge , centrifugal, split casing pump of cast iron  17.2.1 Electrically driven pumps shall be provided with totally enclosed fan cooled induction JYOTHI* / ABB*/  Type: 3 Phase AC Squirrel Cage Induction Motor.
body and bronze impeller with stainless steel shaft, to ensure minimum pressure of 3.5 kg/cm2 at  motors. For fire pumps, the motors should be rated not to draw starting current more than CROMPTON*/ NGEF* Voltage: 415 ± 10% V
highest and farthest outlet at specified flow of 1620 LPM & 35 m head conforming  to IS‐ 1520  3 times normal running current. Frequency: 50±5% Hz
complete with  mechanical seals,  safety relief valve, complete witth all accessories etc as  17.2.2 Motors for Main fire pumps shall be at least equivalent to the horse power required to drive the  Insulation: TEFC
required. pump at 150% of its rated discharge and shall be designed for continuous full load duty and shall be design  Insulation Class: F Class
The pump shall be capable of furnishing not less than 150% of rated capacity  at a head not less  proven in similar service. Type of Protection: IP 55
than 65% or rated head. The shut off head shall  not exceed 120% of rated head. 17.2.3 Motors shall be suitable for 415 volts +/ ‐ 10%, 3 Phase, 50 Hz, A.C supply with class –F Applicable Standard: IS12615, IEC60034‐1
Suitable HP Squirrel cage Induction motor suitable for operation on 415V, 3 phase, 50Hz, AC  insulation, TEFC and conform to IS: 325. Mounting: Horizontal Foot‐B3
supply for the above pump TEFC type confirming  to  IS‐325  with  IP:55  protection  for   17.2.4 Motors shall be capable of handling the required starting torque of the pumps. KW required at Rated Duty Parameter: 12.38 KW
enclosure,  horizontal  foot  mounted  with  class  F  insulation,  flexible  coupling  & coupling  17.2.5 Contractor shall provide heating arrangements (Space Heaters) for the main fire pump motor to  KW required at 150%  of Rated Capacity: 15.28 KW
guard with the pump complete as reqd. ensure that motor windings shall remain dry. KW Offered: 18.5 KW
Common bed plate fabricated from MS channel / ISMB with spring type vibration isolators. The  Space Heater: Not Required
pump set base shall be held by bolts grouted  in the suitable RCC (1:2:4) foundation duly  Frame: ND160L
plastered including foundation bolts, washers complete as reqd. for starting current we recommanded to used Soft starter panel which part of 
other vendor.
Comments Compliance Statement of Technical Datasheets for Fire Fighting System at Lucknow Airport

Any Deviation between Technical  Observation / 
Approved Makes as per  Make Proposed by 
BOQ Item No. BOQ Item Description Technical Specification as per Agreement Technical Specification offered by OEM Specification as per agreement and  Recommendation of M/s 
Agreement Agency
offered by OEM  Egis

Providing, Fixing, of Diesel engine driven standby fire pump suitable for automatic operation  CA Page No. 1076 of Volume‐II Sr. No. 17.9.3


complete in all respect as required & specified and consisting of the following: Horizontal type  Cl. No. 17.9 DIESEL FIRE PUMP
multistage, end suction , top discharge , centrifugal, split casing pump of cast iron body and  17.9 DIESEL ENGINE
a> Radiator with Hoses, Fan, 
bronze impeller with stainless steel shaft , mechanical seal, to ensure minimum pressure of  17.9.2 Engine Rating ‐ The engine shall be cold starting type without the necessity of preliminary Water pump, Drive 
3.5 kg/cm2 at highest and farthest outlet at specified flow of 2850 LPM & 100 m head  heating of the engine cylinders or combustion chamber (for example, by wicks, cartridge, arrangement and guard not 
conforming to IS‐ 1520 complete with all accessories etc. as required The pump shall be  heater plugs etc). The engine shall be multi‐ cylinder / vertical four stroke cycle, water
capable of furnishing not less than 150% of rated capacity at a head not less than 65% or rated cooled diesel engine, developing suitable HP at the operating speed specified to drive the
Engine Driven Pump Sets:  applicabel in Heat Exchanger 
head. The shut off head shall not exceed 120% of rated head. Heat Exchanger ( Water ) cooled  fire pump. Continuous capacity available for the load shall be exclusive of the power Capacity 2850 LPM at 100 m head Type Engine
diesel engine developing required BHP suitable for the pump, flexible coupling & coupling  requirement of auxiliaries of the diesel engine, and after correction for altitude, ambient b> Winterization arrangement 
guard with the pump & common bed plate for mounting of engine & pump shall confirming to  temperature and humidity for the specified environmental conditions as mentioned. This
relevant BS/IS standard with auto starting mechanism. The common base frame shall be held  shall be at least 20% greater than the maximum HP required to drive the pump at its duty
not applicabe in Heat 
by bolts grouted in the concrete including foundation bolts, washers as required, vibration  point. It shall also be capable of driving the pump at 150% of the rated discharge at 65% of Exchanger Type Engine.
damping arrangement by cushy foot & engine panel with battery charger provided by engine  rated head. The engine shall have 10% overload capacity for one hour in any period of 12 Sr. No. 17.9.8
manufacturer, connection to engine starting panel, lead acid batteries of 12V/24V, 180AH  hours continuous run. The engine shall develop full load within 15 seconds from the receipt
In Governing System As per 
with casing, lugs, stand & terminations to diesel engine, charger complete in all respect.  of signal to start. The diesel engine shall conform to BS 649/IS 1601/IS 10002, all amended Type: Horizontal Split case Multistage  manufacturer 
Exhaust pipe of required length ( discharge to leave above roof level as per standard) with  upto date.
50mm thick glass wool pipe section, covered with aluminium cladding, residential silencer  17.9.3 Engine Accessories ‐ The engine shall be complete with the following accessories:‐ centrifugal Axially Spit casing  pump with side  recommandation adjustable 
muffler, instruments & protection‐stop solenoid for auto stop in the event of fault with auto   Fly wheel dynamically balanced.
indications, day oil tank of 200 ltrs. with first charge of diesel fabricated out of 4mm MS sheet   Direct a coupling for pump and coupling guard.
suction ‐ side discharge    governor to control the engine 
with inlet/ outlet ON/OFF valves, level indicator, drain pipe, 15mm dia MS fuel line complete   Radiator with hoses, fan, water pump, drive arrangement and guard. Usage: For Hydrant System and Sprinkler  speed within 10% of itr rated 
as reqd. Common bed plate of fabricated MS channel / ISMB with vibration isolator. The base   Corrosion Resister. speed under all conditions of 
frame shall be held by bolts grouted in the suitable cement concrete foundation duly   Air cleaner dry type. System load up to full load.
plastered including foundation bolts, washers as required.  Fuel service tank support, semi‐rotary pump and fuel oil filter with necessary pipe work.
 Pump for lubricating oil and lub. oil filter.
Performance Testing Std: As per OEM Std.  an over speed shutdown 
 Elect. starting battery (12 V / 24V with 2 Nos. Battery). (ISO‐9906‐Gr2B / IS 9137 Class C) device to shutdown the engine 
 Exhaust silencer with necessary pipe work.
at a speed approximately 15% 
 Governor.
 Instrument panel housing all the gauges, including Tachometer, hour meter and starting above rated engine speed with 
switch with key (for manual staring). MOC:Body: CI (IS:210 Gr FG260) manual reset. 
 Necessary safety controls.
 Winterization arrangement. Impellers: Bronze (IS:318, Gr LTB2)
 Hand operated semi rotary pump for filing the service tank
1111.00 17.9.4 Fuel System: The fuel shall be gravity fed from the engine fuel storage tank to the engine
ASHOK LEYLAND / KIRLOSKAR 
OIL / KIRLOSKAR (KOEL) 
Neck Ring : Bronze (IS:318, Gr LTB5)
driven fuel pump. The engine fuel storage tank shall be mounted either over or adjacent to CUMMINS Shaft: SS 410 (SS ASTM A 276 CL 410)
the engine itself suitably wall / floor mounted with proper support.
The filter shall be suitable located to permit easy services. Stuffing Box: Mechanical Seal
All fuel tubing in the engine shall be with copper and fuel piping from day oil tank to engine
shall be MS C Class pipe with Reinforced flexible hose connection. Plastic tubing shall not be
Base Frame: Mild Steel
permitted.
The fuel tank shall be welded Steel Construction (3mm Thick) and of 200 Ltrs. capacity or of
capacity sufficient to allow the engine to run on full load for at least 8 hours. The tank shall
be complete with necessary supports, level indicator (Protected against mechanical injury)
inlet, outlet, overflow connection and drain plug and piping to the engine fuel tank. The Driver: Diesel Engine, 127 BHP, 1500RPM / 
outlet shall be so located as to avoid entry of any sediment into the fuel line to the engine.
Tank shall be provided with epoxy coat from inside and outside with one coat of Red oxide Heat Exchanger Cooled
primer and two or more Coats of Synthetic enamel paint of approved shade. Battery: 24 V, (12V*2 nos.)180AH 
A semi rotary hand pump for filling the daily service tank together with hose pipe of 5 m long with a foot 
valve etc shall also form part of scope of supply. Diesel Tank: 200 Ltrs with all necessary 
17.9.5 Starting system ‐ The starting system shall comprise necessary batteries 12V / 24V volts starter 
motor of adequate capacity and axle type gear to match with the toothed ring on t
accessories

IS Condition: 
Fire Pumps shall be capable of delivering not 
less than 150% of the rated capacity of water 
at a head of not less than 65% of the rated 
head. The shut‐off head shall not exceed 120% 
of the rated head.