FR-F 800
F800
1 ENERGY SAVING
The consumed power of a variable-torque load, such Utilizing the motor capability to the full
as fans, pumps, and blowers, is proportional to the
Optimum excitation control
cube of its rotation speed.
Adjusting the air volume by the inverter rotation speed •Optimum excitation control continuously adjusts the excitation
control can lead to energy savings. current to an optimum level to provide the highest motor efficiency.
[Example of blower operation characteristic] With a small load torque, a substantial energy saving can be achieved.
120 For example, at 4% motor load torque for a general-purpose motor,
Damper control the motor efficiency under Optimum excitation control is about 30%
Consumed power (%)*1
100
higher than the motor efficiency under V/F control.
80 100
Motor efficiency [%]
60
General-purpose 80 Optimum excitation control
motor (SF-PR)
40 driven by inverter
60 More energy saving
20 V/F control
*1: Rated motor 40
output is 100%.
0
40 60 80 100
20
Air volume (%) [Compared to our 0 20 40 60 80 100 [Compared to our
conventional product] conventional product]
Motor load factor [%]
(When the inverter running frequency is 60 Hz and the SF-PR 4P motor (15 kW) is used)
The offline auto tuning function to measure circuit constants of the motor Mitsubishi general-purpose General-purpose motor
(induction) motor SF-HR by other manufacturers
enables optimal operation of motors even when motor constants vary,
when a motor of other manufacturers is used, or when the wiring
distance is long. As well as Mitsubishi general-purpose motors,
Mitsubishi PM motors (MM-EFS, MM-THE4), sensorless operation can be
performed for other manufacturers' general-purpose motors*2 and other
manufacturers' permanent magnet (PM) motors*2.
The tuning function enables the Advanced optimum excitation control of Mitsubishi general-purpose PMmotor
PM motorby
by
(induction) motor SF-PR othermanufacturers
other manufacturers
other manufacturers' general-purpose motors*2, which increases the use Mitsubishi IPM motor
MM-EFS
in the energy saving applications.
*2: Depending on the motor characteristics, tuning may not be available.
1
Inverter Optimum for Fan and Pump Applications
Efficiency
[IE code] IE2 (high efficiency) Superline eco series
(SF-HR)
As an international standard of the efficiency, IEC60034-30 (energy-efficiency classes for single-
speed, three-phase, cage-induction motors) was formulated in October 2008. The efficiency is IE1 (standard efficiency)
Superline series
classified into four classes from IE1 to IE4. The larger number means the higher efficiency. (SF-JR)
Below the class
Low
*3: The details of IE4 are specified in IEC 60034-31.
Further energy saving with the premium high-efficiency IPM motor Excellent compatibility with the
MM-EFS / MM-THE4 [Comparison of efficiency]
high-performance energy-saving motor
100
embedded in the rotor, achieves even Motor constants are stored in the inverter.
Total efficiency (%)
90
.5
22
30
37
45
55
75
90
0
2
0
1.
2.
3.
5.
7.
11
13
16
Energy saving monitor / Pulse train output of output power FR-CV / FR-HC2
The energy saving effect can be common converter (FR-CV) or the high power factor converter
FWD
FWD
REV
REV
STOP
checked using an operation panel, (FR-HC2) through a common PN bus. The regenerated energy is
RESET
RESET
by the inverter can be output in pulses. The cumulative power returned to the power supply,
amount can be easily checked. saving on the energy consumption. FR-CV
FR-CV
(This function cannot be used as a meter to certify electricity billings.) The 355K or higher models are
ore With the Mitsubishi energy measuring module, the energy saving effect can be inverter-converter separated types, FR-F800 FR-F800 FR-F800
Furtherm displayed, measured, and collected.
FR-F800 FR-F800 FR-F800
which are suitable for power regeneration. 2
2 FUNCTIONS IDEAL
FOR FANS AND PUMPS
The rating can be selected between the two types (LD (light duty) or Load Rating Overload current rating
SLD (superlight duty)) depending on the load of the fan/pump to be Superlight
SLD rating
110% 60 s, 120% 3 s (inverse-time characteristics)
duty at surrounding air temperature 40˚C
used. The optimum inverter capacity can be selected suitable for the
120% 60 s, 150% 3 s (inverse-time characteristics)
motor to be used. Light duty LD rating
at surrounding air temperature 50˚C
For the 200 V class 90K or higher and the 400 V class 75K or higher, For the list of inverters by rating, refer to page 11.
a motor with one-rank higher capacity can be combined.
System cost reduction PID multiple loops (two loops) Water volume control with multiple pumps
Two PID operation units are Multi-pump function
available in the inverter. The
By controlling the pumps connected in parallel (up to four
inverter can perform PID control of Manipulated Motor Pump
amount 1 M
pumps) by the PID control by one inverter, water volume, etc.
the motor operation and control PID P
operation
Measured value 1
can be adjusted.
the external equipment at the unit1 Detector
One of the connected pumps is driven by the inverter. Other
same time. The system cost can PID Manipulated amount 2
operation pumps are driven by commercial power supply. The number
be reduced because no external unit 2
Measured value 2
of pumps to be driven by commercial power supply is
PID controller is required for Detector Valve automatically adjusted according to the water volume.
controlling the external equipment.
Pump
Direct setting of the PID set point
The PID set point can be set directly from the operation panel. Pump
Pump
Visibility improvement Option
Sensor
LCD operation
With the optional panel panel
LCD operation LCD operation panel (FR-LU08)
(Option)
(FR-LU08), the unit can be changed
from "%" to other easy-to-see units.
Maintenance and adjustment is Energy saving in low-speed operation
facilitated by using a familiar unit of air
volume, temperature, etc. for indication. PID output shutoff (sleep) function
Unit conversion
The speed/torque relationship is stored while no fault occurs. Foreign matter on the impellers or fans
By comparing the present load status with the stored load of pumps can be removed by repeating
characteristics, Torque
Torque forward/reverse rotation and stopping of
out-of-range warnings can Torque
Torque 55 the motor. (Use this function when a
<Overload range>
be output if applicable. Clogged filter, back flush does not pose a problem.)
clogged pipe, etc.
Mechanical faults such as Torque This function can be also automatically
Fault detection
Torque 44 width
registered trademark of
Echelon Corporation,
Regeneration avoidance function DeviceNet™ is a trademark of Programmable
controller
Programmable
controller
the ODVA, and PROFIBUS is
The operation frequency is automatically increased to prevent the a trademark of the PROFIBUS Inverter
User Organization.
regenerative overvoltage fault from occurring. This function is Inverter Inverter
useful when a load is forcibly rotated by another fan in the duct. Air Control of
conditioning various
control pumps
Fan Pump
Extended
three typesFunctions
programmable controller
Network
Support for up to of options
MC
Three types
Support forofup
plug-in options
to three can of
types be options
attached.
The functions of the inverter can be extended through
Sensor signal
Sensor
For control
power supply
Three types
network. Forofexample,
plug-in options canI/O
additional beterminals
attached.can be used.
24 VDC
power The functions of the inverter can be extended through
supply
FAN network. For example, additional I/O terminals can be used. 4
3 SECURITY & SAFETY
5
Protection of Critical Parameter Settings
Misoperation prevention by setting a password
•Setting a 4-digit password can restrict parameter reading/writing.
Renewal Assurance
Compatibility with existing models
•The inverter installation method •The terminal response adjustment function allows a user to
is the same as that for the adjust the response speed in accordance with the existing
FR-F700(P) series, eliminating facility. (The response time is shorter for the FR-F800 series.)
any concerns over replacement •In addition to the FR-F700(P) series' parameter settings, the
(except for some capacity FR-F500 series parameter settings (to be supported soon)
models). can be easily copied to the FR-F800 series by using the
Furthermore, the FR-F700(P) conversion function of FR Configurator2.
series control circuit terminal
blocks can be installed with the
use of an option (FR-A8TAT).
Personal computer
FR-F700 (P) FR-F800
6
4 COMPATIBILITY
WITH THE ENVIRONMENT
•Harmonic
•By attaching current may filter connector to the ON or OFF
the EMC •The
•WithF800 series
a high power inverters are equipped
factor converter with built-in
(FR-HC2), the inverter is
adversely
position, the affect the EMC filter can be set
built-in capacitive
equivalent filters (capacitors) and
to a self-excitation common bridge
three-phase mode chokes
circuit in
power supply. To 1*2. When it is enabled, the inverter
enabled/disabled* (55K or lower). Suppression
the "Harmonic By installing aGuidelines
DC reactorfor(FR-HEL),
Specific which is
suppress
conforms such to theharmonic
EMC Directive (EN61800-3/1st Environment available
Consumers" as an
in option, theyrealizes
Japan, and can confirm to the Architectural
the equivalent capacity
current,
Categorythe C1/C2*3) by itself. Standard
conversion Specifications (Electric
coefficient K5=0. Installation)
For the 355K or and the the
higher,
AC reactor DC reactor
*1:power-factor-improving
Enabling the EMC filter increases leakage (FR-HAL)
current. (FR-HEL)
Architectural Standard Specifications
converter is separated. (Machinery
Therefore, installation Installation)
space can be
*2:compact
The input side common
AC reactor mode choke, which is built in the 55K or lower inverter, (2010
saved revision) supervised
when connecting thebyFR-HC2.
the Ministry of Land,
is always enabled regardless of the EMC filter ON/OFF connector setting.
(FR-HAL) and the DC reactor (FR-HEL) are available. (For the Infrastructure, Transport and Tourism of Japan.
*3: Refer to the EMC Installation Guidelines for the required specifications.
75K or higher inverter, always connect a DC reactor. Select a •With a high power factor converter (FR-HC2), the inverter is
DC reactor according to the applied motor capacity.) equivalent to a self-excitation three-phase bridge circuit in
•By attaching the EMC filter connector to the ON or OFF the "Harmonic Suppression Guidelines for Specific
position, the built-in EMC filter can be set Consumers" in Japan, and realizes the equivalent capacity
enabled/disabled*1*2. When it is enabled, the inverter conversion coefficient K5=0. For the 355K or higher, the
conforms to the EMC Directive (EN61800-3/2nd Environment converter is separated. Therefore, installation space can be
Category C3*3) by itself. saved when connecting the FR-HC2.
*1: Enabling the EMC filter increases leakage current.
*2: The input side common mode choke, which is built in the 55K or lower inverter,
is always enabled regardless of the EMC filter ON/OFF connector setting.
Protected in Hazardous Environments
*3: Refer to the EMC Installation Guidelines for the required specifications. Global Compatibility
Capacitive filter Common mode choke DC reactor
55K or lower Standard
Special-purpose inverters
(built-in)with circuit(built-in)
Standard board coating
Option (sold separately) •The F800 series inverters are compatible with UL, cUL, EC
75K or higher Standard
(IEC60721-3-3 (built-in)
3C2/3S2) andOption
plated separately) Option
(sold conductors are(sold separately)
available Directives (CE marking).
for improved environmental resistance. •Being RoHS compliant, the FR-F800 inverters are friendly to
For the details, please contact your sales representative. people and the environment.
7
5 EASY SETUP
& EASY TO USE
Inverter
USB cable NEW Easy-to-read operation panel
•A trial version, which contains start-up functions, is available. It A 5-digit, 12-segment display has been adopted for the operation
can be downloaded at Mitsubishi Electric FA Global Website. panel (FR-DU08) for a more natural FR-DU08 FR-LU08
(12-segment type) (LCD type)
character display. Furthermore,
another operation panel (FR-LU08)
Easy wiring to the control circuit
PU MON IM
FWD
available.
terminals.
As compared to the conventional screw terminals, spring
clamp terminals are highly reliable and can be easily wired. To Aid with Maintenance
Round crimping terminals can also be used by employing a
control terminal option. Reduced wiring check time PU
EX T
NE T
MON
PRM
P.RUN
IM
PM
FWD
REE V
R
SSTTOP
OP
RES ET
Assures the
Easy wiring. tensile strength of the
Split-type covers are adapted for all
Just insert. DIN standards. capacity models. Maintenance is now easy
because all an operator has to do is to
remove the cover for the target wiring area.
Inverter
Symbol Voltage class Symbol Structure, functionality Symbol*1 Description Symbol Type Circuit board coating Plated
Symbol (IEC60721-3-3 3C2/3S2 compatible) conductor
2 200 V class 0 Standard model LD rated inverter -1 FM None Without Without
0.75K to 315K
4 400 V class capacity (kW) -2 CA*2 -60 With Without
-06 With With
Three-phase 0.75K 1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K 18.5K 22K 30K 37K 45K 55K 75K 90K 110K
200 V class 00046 00077 00105 00167 00250 00340 00490 00630 00770 00930 01250 01540 01870 02330 03160 03800 04750
FR-F820-[]
0.75K 1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K 18.5K 22K 30K 37K 45K 55K 75K 90K 110K
00023 00038 00052 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160 01800 02160 02600
Three-phase
400 V class
132K 160K 185K 220K 250K 280K 315K
FR-F840-[]
03250 03610 04320 04810 05470 06100 06830
Symbol Voltage class Symbol Structure, functionality Symbol*1 Description Symbol Type Circuit board coating Plated
Symbol (IEC60721-3-3 3C2/3S2 compatible) conductor
4 400 V class Separated LD rated inverter -1 FM None Without Without
2 355K to 560K
converter type capacity (kW) -2 CA*2 -60 With Without
-06 With With
Three-phase 355K 400K 450K 500K 560K
400 V class 07700 08660 09620 10940 12120
FR-F842-[]
*1: Models can be alternatively indicated with the rated inverter current (SLD rating).
*2: Specification differs by the type as follows.
Initial setting
Type Monitor output Built-in Control Rated Pr.19 Pr.570
EMC filter logic frequency Base frequency voltage Multiple rating setting
FM Terminal FM (pulse train output) 9999 1
OFF Sink logic 60Hz
(terminal FM equipped model) Terminal AM (analog voltage output (0 to ±10 VDC)) (same as the power supply voltage) (LD rating)
CA Terminal CA (analog current output (0 to 20 mADC)) 8888 0
ON Source logic 50Hz
(terminal CA equipped model) Terminal AM (analog voltage output (0 to ±10 VDC)) (95% of the power supply voltage) (SLD rating)
Converter unit
F R - CC2 - H 355K - 60
Symbol Voltage class Symbol Description Circuit board coating Plated
Symbol (IEC60721-3-3 3C2/3S2 compatible) conductor
H 400 V class Applicable motor -60 With Without
355K to 630K
capacity (kW) -06 With With
: Released model
9
Standard Specifications
Rating (Standard model)
200 V class
00046 00077 00105 00167 00250 00340 00490 00630 00770 00930 01250 01540 01870 02330 03160 03800 04750
Model FR-F820-[ ]
0.75K 1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K 18.5K 22K 30K 37K 45K 55K 75K 90K 110K
Applicable motor SLD 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90/110 132
capacity (kW) *1 LD 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110
Rated current SLD 4.6 7.7 10.5 16.7 25 34 49 63 77 93 125 154 187 233 316 380 475
Output
(A) LD 4.2 7 9.6 15.2 23 31 45 58 70.5 85 114 140 170 212 288 346 432
Overload SLD 110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature 40°C
current
rating *3 LD 120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature 50°C
Approx. mass (kg) 1.9 2.1 3.0 3.0 3.0 6.3 6.3 8.3 15 15 15 22 42 42 54 74 74
* 1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
* 2 The rated output capacity indicated assumes that the output voltage is 220 V for 200 V class.
* 3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter’s rated output current. For repeated duty, allow time for the
inverter and motor to return to or below the temperatures under 100% load.
* 4 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However, the
maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about .
* 5 FR-DU08: IP40 (except for the PU connector section)
400 V class
00023 00038 00052 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160 01800 02160 02600 03250 03610 04320 04810 05470 06100 06830
Model FR-F840-[ ]
0.75K 1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K 18.5K 22K 30K 37K 45K 55K 75K 90K 110K 132K 160K 185K 220K 250K 280K 315K
75/
Applicable motor SLD 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 110 132 160 185 220 250 280 315 355
90
capacity (kW) *1 LD 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 185 220 250 280 315
Rated capacity SLD 1.8 2.9 4 6.3 10 13 19 24 29 36 47 59 71 88 137 165 198 248 275 329 367 417 465 521
(kVA) *2 LD 1.6 2.7 3.7 5.8 8.8 12 18 22 27 33 43 53 65 81 110 137 165 198 248 275 329 367 417 465
Rated current SLD 2.3 3.8 5.2 8.3 12.6 17 25 31 38 47 62 77 93 116 180 216 260 325 361 432 481 547 610 683
Output
(A) LD 2.1 3.5 4.8 7.6 11.5 16 23 29 35 43 57 70 85 106 144 180 216 260 325 361 432 481 547 610
Overload SLD 110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature 40°C
current
rating *3 LD 120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature 50°C
Approx. mass (kg) 2.5 2.5 2.5 3.0 3.0 6.3 6.3 8.3 8.3 15 15 23 41 41 43 52 55 71 78 117 117 166 166 166
*1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
* 2 The rated output capacity indicated assumes that the output voltage is 440 V for 400 V class.
* 3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter’s rated output current. For repeated duty, allow time for the
inverter and motor to return to or below the temperatures under 100% load.
* 4 The maximum output voltage does not exceed the power supply volt age. The maximum output voltage can be changed within the setting range. However, the
maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about .
* 5 FR-DU08: IP40 (except for the PU connector section)
* 6 For the power voltage exceeding 480 V, set Pr.977 Input voltage mode selection.
Control power supply auxiliary input Single phase 380 to 500 V 50 Hz/60 Hz
Permissible control power supply auxiliary
Frequency 5%, voltage 10%
input fluctuation
Protective structure (IEC 60529) Open type (IP00)
Cooling system Forced air cooling
Approx. mass (kg) 163 163 243 243 243
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
The rated output capacity indicated assumes that the output voltage is 440 V.
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about .
LD rating reference value
FR-DU08: IP40 (except for the PU connector section)
For the power voltage exceeding 480 V, set Pr.977 Input voltage mode selection.
11
Common specifications
Soft-PWM control, high carrier frequency PWM control (selectable among V/F control (Optimum excitation control, etc.),
Control method
Advanced magnetic flux vector control (Advanced optimum excitation control, etc.), and PM motor control)
Output frequency range 0.2 to 590 Hz (The upper-limit frequency is 400 Hz under Advanced magnetic flux vector control, and PM motor control.)
0.015 Hz/60 Hz (terminal 2, 4: 0 to 10 V/12 bits)
Frequency
Analog input 0.03 Hz/60 Hz (0 to 5 V/11 bits or 0 to 20 mA/approx. 11 bits for terminals 2 and 4, 0 to 10 V/12 bits for terminal 1)
setting
0.06 Hz/60 Hz (0 to 5 V/11 bits for terminal 1)
resolution
Control specifications
The input signal can be changed using Pr.178 to Pr.189 (input terminal function selection).
Pulse train input 100 kpps
Maximum frequency, minimum frequency, multi-speed operation, acceleration/deceleration pattern, thermal protection, DC
injection brake, starting frequency, JOG operation, output stop (MRS), stall prevention, regeneration avoidance, increased
magnetic excitation deceleration, DC feeding, frequency jump, rotation display, automatic restart after instantaneous
power failure, electronic bypass sequence, remote setting, retry function, carrier frequency selection, fast-response current
limit, forward/reverse rotation prevention, operation mode selection, slip compensation, speed smoothing control, traverse,
Operational functions
auto tuning, applied motor selection, RS-485 communication, PID control, PID pre-charge function, cooling fan operation
selection, stop selection (deceleration stop/coasting), power-failure deceleration stop function, PLC function, life diagnosis,
maintenance timer, current average monitor, multiple rating, test run, 24 V power supply input for control circuit, safety stop
function, self power management, BACnet communication, PID gain tuning, cleaning, load characteristics storage,
emergency drive
Output signal Inverter running, Up to frequency, Instantaneous power failure/undervoltage, Overload warning, Output frequency
Open collector output (five detection, Fault
terminals) The output signal can be changed using Pr.190 to Pr.196 (output terminal function selection).
Relay output (two terminals) Fault codes of the inverter can be output (4 bits) from the open collector.
Pulse train output 50 kpps
Pulse train Max. 2.4 kHz: one terminal (output frequency)
output (FM type) The monitored item can be changed using Pr.54 FM/CA terminal function selection.
Current output Max. 20 mADC: one terminal (output current)
For meter
(CA type) The monitored item can be changed using Pr.54 FM/CA terminal function selection.
Indication
With circuit board coating (conforming to IEC60721-3-3 3C2/3S2): 95% RH or less (non-condensing)
Surrounding air humidity
Without circuit board coating: 90% RH or less (non-condensing)
Storage temperature -20°C to +65°C
Atmosphere Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt, etc.)
Altitude/vibration Maximum 1000 m above sea level, 5.9 m/s2 or less at 10 to 55 Hz (directions of X, Y, Z axes)
Available only for the standard model.
This protective function is not available in the initial status.
Temperature applicable for a short time, e.g. in transit.
For the installation at an altitude above 1,000 m (up to 2,500 m), derate the rated current 3% per 500 m.
2.9 m/s2 or less for the FR-F840-04320(185K) or higher.
12
CA type
FR-F820-00770(18.5K) to 01250(30K),
DC reactor FR-F840-00470(22K) to 01800(75K)
(FR-HEL)∗1 DC reactor
Sourse logic Brake unit (FR-HEL)∗1
Main circuit terminal (Option) Brake unit
(Option)
Control circuit terminal Jumper
Earth Jumper
Jumper
(Ground) Earth
(Ground)
P1 P/+ PX∗7 PR∗7 N/-
P1 P/+ P3 PR∗7 N/-
MCCB MC
R/L1 Inrush current U
Three-phase V Motor
S/L2 limit circuit M
AC power W
T/L3
supply ON EMC filter Earth (Ground)
Jumper R1/L11 ON/OFF
∗2 S1/L21 OFF connecter
Earth
(Ground)
Main circuit
Control input signals Control circuit Relay output∗8
(No voltage input allowed)∗3
STF C1
Forward rotation start
STR B1
Reverse rotation start Relay output 1
A1 (Fault output)
STP(STOP)
Start self-holding selection
RH C2
High speed
RM B2
Multi-speed Middle speed Relay output 2
selection A2
RL
Low speed
JOG ∗4 RUN Open collector output∗9
Jog operation Running
RT SU
Second function selection Up to frequency
MRS IPF
Output stop Instantaneous
RES OL power failure
Reset Overload
Terminal 4 input selection AU FU
(Current input selection) Frequency detection
SOURCE
∗10
Sink/source common
Common for external power SD
24V
supply transistor
Contact input common PC
24VDC power supply
For the FR-F820-03160(75K) or higher, the FR-F840-01800(75K) or higher, always connect a DC reactor (FR-HEL), which is available as an option. (To
select a DC reactor, refer to page 18, page 106, and select one according to the applicable motor capacity.)
When a DC reactor is connected to the FR-F820-02330(55K) or lower or the FR-F840-01160(55K) or lower, if a jumper is installed across the terminals P1
and P/+, remove the jumper before installing the DC reactor.
When using separate power supply for the control circuit, remove the jumper between R1/L11 and S1/L21.
The function of these terminals can be changed with the input terminal assignment (Pr.178 to Pr.189).
Terminal JOG is also used as the pulse train input terminal. Use Pr.291 to choose JOG or pulse.
Terminal input specifications can be changed by analog input specification switchover (Pr.73, Pr.267). To input a voltage, set the voltage/current input
switch OFF. To input a current, set the voltage/current input switch ON. Terminals 10 and 2 are also used as a PTC input terminal. (Pr.561)
It is recommended to use 2 W 1 kΩ when the frequency setting signal is changed frequently.
Do not use terminals PR and PX. Do not remove the jumper connected to terminals PR and PX.
The function of these terminals can be changed with the output terminal assignment (Pr.195, Pr.196).
The function of these terminals can be changed with the output terminal assignment (Pr.190 to Pr.194).
No function is assigned in the initial status. Assign the function using Pr.186 CS terminal function selection.
13
Converter unit (FR-CC2)
When the sink logic is selected
Sink logic
Main circuit terminal Connection is not available
MCCB MC DC reactor
R/L1 Inrush current P/+
Three-phase limit circuit P/+
AC power S/L2 N/-
T/L3 N/-
supply
ON EMC filter
R1/L11 ON/OFF
Jumper
S1/L21 OFF connecter
Instantaneous
power failure
SINK
FAN
Contact input common SD Cooling fan fault
24V
PC SE
24VDC power supply SD
(Common for external power supply transistor)
Open collector output common
Sink/source common
24V external power +24
supply input C1 Relay output
SD
Common terminal
PU B1 Relay output
connector (Fault output)
A1
USB
mini B TXD+ RS-485 terminals
connector
TXD- Data transmission
RXD+
RXD- Data reception
SG
GND
Connector for manufacturer setting connector 1 Terminating
VCC 5V (Permissible load
resistor
current 100mA)
88R
88S
When using separate power supply for the control circuit, remove the jumpers from R1/L11 and S1/L21.
The function of these terminals can be changed with the input terminal assignment (Pr.178, Pr.187, Pr.189).
The function of these terminals can be changed with the output terminal assignment (Pr.195).
The function of these terminals can be changed with the output terminal assignment (Pr.190 to Pr.194).
The connector is for manufacturer setting. Do not use.
Plug-in options cannot be used.
For manufacturer setting. Do not use.
For the FR-CC2-H400K to H630K, two EMC filter ON/OFF connectors are provided.
14
Outline Dimension Drawings
Standard model
H1
H1
H
H
W1 W1 W1
W D
W
(Unit: mm)
*This is a sample outline dimension drawing. The shape differs by the model.
200 V class
Inverter model W W1 H H1 D C
FR-F820-00046(0.75K) 110
110 95
FR-F820-00077(1.5K) 125
FR-F820-00105(2.2K)
FR-F820-00167(3.7K) 150 125 260 245 140
6
FR-F820-00250(5.5K)
FR-F820-00340(7.5K)
170
FR-F820-00490(11K) 220 195
FR-F820-00630(15K) 300 285
FR-F820-00770(18.5K)
190
FR-F820-00930(22K) 250 230 400 380
10
FR-F820-01250(30K)
FR-F820-01540(37K) 325 270 530 195
FR-F820-01870(45K) 550
435 380 525
FR-F820-02330(55K) 250
FR-F820-03160(75K) 410 700 675 12
FR-F820-03800(90K) 465
400 740 715 360
FR-F820-04750(110K)
400 V class
Inverter model W W1 H H1 D C
FR-F840-00023(0.75K)
FR-F840-00038(1.5K)
FR-F840-00052(2.2K) 150 125 140
FR-F840-00083(3.7K) 260 245
FR-F840-00126(5.5K) 6
FR-F840-00170(7.5K)
170
FR-F840-00250(11K)
220 195
FR-F840-00310(15K)
300 285
FR-F840-00380(18.5K)
190
FR-F840-00470(22K)
250 230 400 380
FR-F840-00620(30K) 10
FR-F840-00770(37K) 325 270 530 195
FR-F840-00930(45K)
550
FR-F840-01160(55K) 435 380 525 250
FR-F840-01800(75K)
FR-F840-02160(90K)
620 595 300
FR-F840-02600(110K)
465 400
FR-F840-03250(132K)
740 715 360 12
FR-F840-03610(160K)
FR-F840-04320(185K)
498 200 985
FR-F840-04810(220K)
FR-F840-05470(250K) 1010 380
FR-F840-06100(280K) 680 300 984
FR-F840-06830(315K)
15
Separated
l Separated converter
converter type
type
w Inverter
FR-F842-07700(355K), 08660(400K)
185 23
3-φ12 hole 8-φ25 hole
(17)
(15)
1300
1330
1296
12 4.5 4.5
15
17
70 200 200 (70) 185
540 440
(Unit: mm)
185 23
3-φ12 hole 8-φ25 hole
(15)
(17)
1550
1580
1546
12 4.5 4.5
17
15
(Unit: mm)
16
w Converter unit
FR-CC2-H355K
(15)
(17)
∗1
∗1
1296
1300
1330
12 4.5 4.5
15
17
100 200 200 (100) 185
600 440
(17)
∗1
∗1
1546
1550
1580
12 4.5 4.5
15
17
18
Specifications
400 V class
Type Rated current [A] Rated motor capacity [kW] Operating conditions Specifications
FR-A846-00023 2.1 1.5 0.75 0.4 Ambient temperature -10 ºC to +40 ºC (non-freezing)
FR-A846-00038 3.5 2.5 1.5 0.75 Compliance to IEC 60721-3-3 class 3C2,
Ambient humidity
maximum 95 % RH (non-condensing)
FR-A846-00052 4.8 4 2.2 1.5
Altitude Maximum 1000 m above sea level
FR-A846-00083 7.6 6 3.7 2.2
Protection rating IP55
FR-A846-00126 11.5 9 5.5 3.7
Vibration resistance Max. 0.6 G
FR-A846-00170 16 12 7.5 5.5
Break chopper Built-in up to 55 k
FR-A846-00250 23 17 11 7.5
FR-A846-00310 29 23 15 11
FR-A846-00380 35 31 18.5 15
FR-A846-00470 43 38 22 18.5
FR-A846-00620 57 44 30 22
FR-A846-00770 70 57 37 30
FR-A846-00930 85 71 45 37
FR-A846-01160 106 86 55 45
* LD= Light duty (120 % at 60 s, 150 % at 3 s); ND= Normal duty (150 % at 60 s,
1
200 % at 3 s)
Dimensions
Inverter type W W1 H H1 D C
FR-A846-00023 (0.4K) to
520 508 271 8
00170 (5.5K) *1
238 201
FR-A846-00250(7.5K) to
650 632.5 285 10
00470(18.5K) *1
FR-A846-00620(22K) to
345 300 790 770 357 12
01160(45K) *1
FR-A846-01800(55K) to
350 1360 1334
02600(90K) *1
420 456.6 15
FR-A846-03250(110K) to
290 1510 1482
03610(132K) *1
All dimensions in mm
19
Harmonic Mitigation Solution
Energy Saving!
Low Pass Harmonic Filters eliminate most of the wasted energy associated with harmonics and
reduce True RMS kVA.
<20 5%
20<50 8%
50<100 12%
20
Model selection
PQ FR - PQ X 0015 A A 2
Code Enclosure
0 Loose Parts
1 IP 00 (Open Panel)
2 IP 20
3 IP 42
4 IP 54
Code Frequency
A 50Hz
B 60Hz
A 380V – 415V
B 208V – 240V
C 440V – 480V
D 600V – 690V
0015 15A
0026 26A
.... ..A
Code THID
Code Series
Air Inlet
R S T N U V W
21
Weight and dimension
TOP VIEW
TOP VIEW
Air Outlet
Air Outlet
Air Inlet
Air Inlet
22
Weight and dimension
Air Inlet
Air Inlet
Product specifications:
· Suitable for any source impedance and for Generators
· Suitable for 380 to 415 volts (+/- 5%)
· Suitable for system frequency of 50 Hz +/- 1 Hz
· Typical voltage regulation is +3% / -5%
· Typical input harmonic current distortion is less than 10% (Background THVD ≤ 2%)
23
Technical specification
System Voltage 200, 240, 380, 400, 415, 440, 480, 600, 690 Volts
Voltage Line Unbalance Up to 3% Line Voltage Unbalance (note: THiD will increase above normal levels when line voltage is unbalance
Source Impedance Minimum 0.5% to 6% ( Utility) Minimum 10% to Maximum 15% (Generator)
Reduced KVA Demand As much as 30% (when current distortion is reduce from 100% to 5%)
Reduced Current Demand As much as 30% (when current distortion is reduce from 100% to 5%)
24
Service & Support
FA Center in North
ASEAN FA Centre
MITSUBISHI ELECTRIC ASIA PTE LTD.
307 Alexandra Road, Mitsubishi Electric Building Singapore 159943
TEL 65-6470-2480
FAX 65-6476-7439
URL http://www.mitsubishielectric.com.sg
Applicable Standards
Mitsubishi Electric’s 800 Series Inverter has been designed, manufactured, and tested in accordance with the latest applicable standards as follow:
Manufacturer of the 800 Series Inverter, Nagoya Works, is a certified ISO 9001 and ISO 14000 facility
25
Z E R T I F I K A T ♦ C E R T I F I C A T E ♦ 认证证书 ♦ C E P T И φ И K A T ♦ CERTIFICADO ♦ CERTIFICAT
Certificate Mark :