INCREASED VENTILATION, 30% ABOVE ASHRAE 62.1 REQUIREMENTS INCREASED VENTILATION, 30% ABOVE
ASHRAE 62.1 REQUIREMENTS
Air-conditioning of the Patni Campus has been designed considering increased ventilation, 30% above ASHRAE 62.1
requirements. The Chart of fresh air is enclosed herewith.
OWNER
PATNI COMPUTERS
ARCHITECT
Mr Vidur Bhardwaj
M/s Design And Development,
A-7, Neeti Bagh
New Delhi-110 049
Tel: 011- 46031500
Email: vidurb@vsnl.com
SUMMARY OF OUTDOOR AIR ADDITION TO INDOOR ENVIRONMENTAL QUALITY
CREDIT 2
MECHANICALLY VENTILATED SPACES
MINIMUM VENTILATION RATE AS PER ASHRAE STANDARD 62.1.2004 SUMMARY OF OUTDOOR AIR ADDITION TO
MECHANICALLY VENTILATED SPACES
S. SPACE AREA HEIGHT NO. OF PEOPLE AREA TOTAL DESIGN
NO. (SQ. FT) (FT.) PERSONS OUTDOOR OUTDOOR COMBINED OUTDOOR
AIR RATE AIR RATE OUTDOOR AIR
5CFM/ 0.06CFM/SFT AIR INTAKE INTAKE
PERSON (CFM)
TOWER -1
1 GROUND FLOOR 28330 13 472 2360 1700 4060 5278
(OFFICES)
COMMON AREA
1 GROUND FLOOR 3845 13 40 200 230 430 559
(OFFICES)