EQ CREDIT 5
INDOOR CHEMICAL & POLLUTANT SOURCE CONTROL
Kitchen
Pantry
Copier/Reprography
PATNI CAMPUS AT NOIDA
Elaborate exhaust arrangement for each of these areas has been planned through dedicated mechanical exhaust system. Following norms for ventilation of each of these
areas shall be followed:
1 Toilets & Janitor Exhaust @10 air changes per hour with equivalent draw of conditioned air from adjacent
Exhausts areas.
OWNER
The system shall consist of ceiling mounted in line fans installed on respective floor. PATNI COMPUTERS
2 Kitchen Exhaust @ 40 Air changes per hour & outdoor makeup air @ 35 Air changes per hour
injected through compensating type hoods over cooking stations.
The system shall consist of ceiling mounted in line fans installed on respective floor. ARCHITECT
Mr Vidur Bhardwaj
4 Copier/ 7 Pascal Negative Pressure in the room. M/s Design And Development,
Reprography
The system shall consist of ceiling mounted in line fans installed on respective floor.
A-7, Neeti Bagh
New Delhi-110 049
Tel: 011- 46031500
Make-up air in all the above areas shall be drawn from adjacent occupied spaces. Email: vidurb@vsnl.com
Care shall be taken to ensure that all exhaust locations are at least 25 feet away from fresh air intakes of air handling units.