GENERAL NOTES:

OK 14
1. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL RELEVANT
ARCHITECTS AND ENGINEERS DRAWINGS AND SPECIFICATIONS.
1143 250 757 ON 2. DO NOT SCALE THIS DRAWING. ANY AMBIGUITIES, OMISSIONS AND ERRORS
977 50 375 ON DRAWINGS SHALL BE BROUGHT TO THE ENGINEERS ATTENTION
IMMEDIATELY. ALL DIMENSIONS MUST BE CHECKED / VERIFIED ON SITE.

CC1
3. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS NOTED OTHERWISE.
300 THK RC SLAB CAST IN DOWELS T.B.C.
MOVEMENT JOINT
Level 01 DETAIL AS PER 4. FOR GENERAL NOTES REFER TO DRAWING: 073707-CUR-ZZ-XX-DR-S-20001.
TOC +78.050 m 300 THK RC SLAB SECTION 4-4 300 THK RC SLAB
78.350 m Level 00 5. CONCRETE GRADES:
W3 74.950 m • RC SLABS C40/50
• RC COLUMNS AND WALLS C50/60
CB1 WATER STOP • RC BEAMS C40/50
300 THK RC SLAB
KICKER • FOUNDATIONS C35/45

MOVEMENT JOINT W4 W4
NOTES:

150

1200
Level B1 300 THK RC SLAB 250mm RC WALL 250mm RC WALL
LIFT PIT
72.910 m • TO LOWER THE POSSIBILITY OF THE SULPHATES ATTACK ON
THE CONCRETE, SULPHATE RESISTING CEMENT MIX SHOULD BE USE
383 250 2910 250 890 IN CONCRETE WHERE IN CONTACT WITH AGGRESSIVE GROUND.
SULPHATE RESISTING CONCRETE CLASS TBC. PENDING SI REPORT
TOC +73.750 m LABORATORIES RESULTS;
W2 • FOR THE INTEGRAL WATERPROOF CONCRETE STRUCTURES LIQUID
Level 00 DPM TO SPECIALIST DESIGN ADMIXTURE WILL BE IN USE. FOR DETAILS AND SPECIFICATIONS
74.950 m REFER TO ARCHITECTS AND SPECIALIST DOCUMENTS AND DETAILS.
50mm BLINDING

NOTE:
MOVEMENT JOINT TYPICAL
SECTION MINIMUM GAP T.B.C.
SECTION 2-2
300 THK RC SLAB SCALE: 1 : 20
Level B1 Level B1
72.910 m 72.910 m

2H16 DOWELS AT SECANT PILED WALL 800


EVERY MATE PILE DPM TO SPECIALIST DESIGN

00
Ø6
1500 THK RC PILED RAFT
SECANT PILED WALL 50mm BLINDING

600mm PILE

400
SECTION 1-1 W2
400 THK RC WALL LIQUID WATERPROOF CONCRETE
SCALE: 1 : 50 ADMIXTURE TO SPECIALIST DETAILS
TO PROVIDE WATERPROOFING
SYSTEM REQUIRED BY ARCHITECT'S
SECTION 5-5 SPECIFICATIONS. SECTION 3-3
SCALE: 1 : 20 SCALE: 1 : 20
CL
WATERSEAL TO ALL WATERPROOFING TO SPECIALIST DETAILS
SPECIALIST DETAILS 14 - MASTIC MEMBRANE TO EDGE OF MJ
- MASTIC MEMBRANE

EXPANSION JOINT
14 - LIQUID MEMBRANE
- WATERPROOFING MEMBRANE
EXPANSION JOINT SYSTEM TO
SYSTEM TO SPECIALIST DETAILS 50 350 50
SPECIALIST DETAILS
4 No. M16 ANCHORS WITH

50
DPM TO SPECIALIST DETAILS EXTERNAL MIN 150mm EMBEDMENT
300 THK RC SLAB CAST-IN DOWEL 300 THK RC SLAB
CONCRETE ENCASEMENT

450
RC SLAB

350
CL

1 15mm THK STEEL


SC BASEPLATE
S355

50
50 50

DPM TO SPECIALIST DETAILS AB W2 W2


INTERNAL
450
ALL WATERPROOFING TO SPECIALIST DETAILS 400 THK RC WALL 400 THK RC WALL
BLINDING - MASTIC MEMBRANE TO EDGE OF MJ WATERSEAL TO SPECIALIST DETAILS
- MASTIC MEMBRANE
- LIQUID MEMBRANE SSL +74.950 m
- WATERPROOFING MEMBRANE TYPICAL ENCASED STEEL
SSL +74.950 m COLUMN BASE DETAIL
SCALE: 1 : 10
SECTION 4-4 SECTION 6-6
SCALE: 1 : 10 SCALE: 1 : 10
P02 STAGE 3 ISSUE 22/05/20 NJ SE
INTERNAL EXTERNAL P01 PRELIMINARY - DESIGN COORDINATION IN PROGRESS 27/04/20 NJ SE
Rev: Description: Date: By: Chkd:

RC SLAB WATERSTOP BAR TO


SPECIALST DETAILS EXTERNAL INTERNAL

RC WALL CONSTRUCTION JOINT -


MIN. 50mm FORMED OR STEEL COLUMN SCHEDULE 40 Compton Street, London, EC1V 0BD
WATERSTOP BAR TO 020 7324 2240
TOOLED SMOOTH TO
SPECIALST DETAILS REF. SIZE london@curtins.com
LIQUID MEMBRANE WATERSTOP RECEIVE WATERSTOP www.curtins.com
SC1 SRC305x305x118
50

COMPRESSIVE JOINT TAPE SC2 UC152x152x23 Civils & Structures • Transport Planning • Environmental • Infrastructure • Geotechnical • Conservation & Heritage • Principal Designer
Birmingham • Bristol • Cambridge • Cardiff • Douglas • Dublin • Edinburgh • Glasgow • Kendal • Leeds • Liverpool • London • Manchester • Nottingham
50 TO SPECIALIST DETAILS SC3 SHS200x200x12.5
SC4 SHS150x150x12.5 Status:

DPM BY SPECIALIST
SUITABLE FOR STAGE APPROVAL S4
RC WALL SHEDULE Project:
CONSTRUCTION JOINT -
DPM BY SPECIALIST RC WALL
MIN. 50mm FORMED OR REF. WALL SIZE CAMDEN AND ISLINGTON NEW
50mm BLINDING TOOLED SMOOTH TO
RECEIVE WATERSTOP
W1 450 THK RC WALL MENTAL HEALTH FACILITY

Model Name:073707-CUR-00-ZZ-M3-S19-00001_CENTRAL
COMPRESSIVE JOINT TAPE W2 400 THK RC WALL
TO SPECIALIST DETAILS W3 350 THK RC WALL Drg Title:
PENETRATION W4 250 THK RC WALL
W5 150 THK RC WALL
TYPICAL RC SLAB DPM BY SPECIALIST RC WALL
GROUND FLOOR SECTIONS
CONSTRUCTION JOINT - SECTION
RC COLUMN SCHEDULE
SCALE: 1 : 10
DIMENSIONS (mm)
REF. COMMENTS
TYPICAL PENETRATION CC1
D
250
B
1000
Size:

A1
Date:

04.2020
Drawn By: Designed By: Checked By:

THROUGH RC WALL OR SLAB - TYPICAL RC WALL CC2 250 800


Scale: As indicated
NJ AP SE
CC3 250 700
PLAN / SECTION CONSTRUCTION JOINT - PLAN CC4 450 450
Project No: Originator: Volume: Level: Type: Role: Category / Number: Rev:

SCALE: 1 : 10 SCALE: 1 : 10 CC5 450 CIRCULAR 073707 - CUR - 00 - B1 - DR - S - 21000 - P02