Calculating the operation current in Bias Differential Relays

(Settings will be transfer from characteristic sheet, update test point with entering
desired "I bias")

Id> IR2 m1 m2 I ref Kamp LV Kamp HV


Settings
0.16 1.8 0.30 0.60 5 1.397 1.351

Points on the Curve Expected currents Notes:


TEST POINT I bias I diff. I LV I HV 1. Must disable the Filtering - Zero seq
1 0 0.160 0.573 0.592 2. If Filtering is set, the slope test resul
2 1 0.436 4.360 2.894 3. This applies when using single curre
3 2 0.796 8.584 5.929
4 3 1.396 13.238 8.520
5 4 1.996 17.892 11.110

REF test for SUM(I)

IdG> Kamp ph Kamp Y


Settings
0.25 3.187 3.187

TEST POINT I R(single ph.)


1 0 0.39
2 1 0.40
3 2 0.40
4 3 0.41
5 4 0.41
e the Filtering - Zero sequence Filtering
s set, the slope test results will be different from expected.
s when using single current source testing he slope charactristics
W in d in g a W in d in g b

Inom,CT,a: Vnom,a: Sref: Vnom,b: Inom,CT,b:

150 A 130.0 kV 25.0 MVA 25.2 kV 800

Inom,a: Iref,a: Vector group ID: Iref,b: Inom,b:

5 A 111.0 A 11 572.8 A 5 A

kamp,a: I0,a filtering: I0,b filtering: kamp,b:

1.351 without with 1.397

IA,a: P631/P632 IA,b:

5.929 A IR,1: Id,1,trip at IR,1: Id,1: 8.584 A


0 ° -150 °
2.000 0.796 0.796
IL2,a: IL2,b:
IR,2: Id,2,trip at IR,2: Id,2:
5.929 A 8.584 A
-120 ° 2.000 0.796 0.796 -270 °

IC,a: IR,3: Id,3,trip at IR,3: Id,3: IC,b:

5.929 A 2.000 0.796 0.796 8.584 A


-240 ° -30 °
Measuring System 1: Measuring System 2: Measuring System 3: Scaling:

NO TRIP NO TRIP NO TRIP

Id / Iref

5
2

0
0 1 2 3 4 5
Tripping Characteristic Measuring System 1 IR / Iref
Measuring System 2 Measuring System 3

Id>: m1: IR,m2: m2:

0.16 0.30 1.8 0.60