Panel Mounted Multi Power Meter
Panel Mounted Multi Power Meter
51U–❑❑❑–❑❑
MODEL R
S
T
T-R
P. 1 / 16 ES-6481 Rev.9
51U
GENERAL SPECIFICATIONS ■PULSE OUTPUT: totalizing watt in forward flow or
var in lag.
Construction: 110 mm-square (4 5/16 in.) panel
Scaling factor: 0.01, 0.1, 1, 10, 100 kWh/pulse
surface, cylindric body
(default: 1)
Connection
Contact rating: 110V DC @0.1A (resistive load)
Input & auxiliary power: M4 screw terminals
110V AC @0.1A (resistive load)
Output: M3 screw terminals
Pulse width time: 100 – 150 msec.
Housing material: plastic (black)
(pulse rate ≤12000 pulses/h)
Isolation: input to output to power; not isolated
between analog outputs
■TRANSMISSION OUTPUT (Multi-Meter Protocol)
Scaling: primary values for CT and VT; tertiary
Transmission: conform to RS-485, EIA
value for GVT (Inform M-System CT and
Transmission distance: 1 kilometer max. (≤31 units)
VT ratios when ordering.)
Cable: shielded twisted-pair cable (CPEV-S 0.9 dia.)
CT: 5 – 8000A (up to 15000A for Code K)
Terminator: incorporated
VT: 110 – 77kV
GVT: 63.5 – 190.5V
■DEMAND ALARM CONTACT OUTPUT
Time lag for demand: 0 sec., 30 sec. or 1, 2, 3, 5, 7,
Alarm setpoint: 5 – 100%; adjustable in 0.5% incre-
10, 15, 30 min. (default: 15 min.)
ments
Sampling cycle: 400 µsec. (DO NOT connect a
Contact rating: 110V DC @0.1A (resistive load)
device such like inverters.)
ON resistance: ≤50Ω
Measurable frequency ranges: 45 – 44 Hz, 55 – 65
Hz, 45 – 65 Hz
Low-end cutout: Display shows 0 for the input less I/O RANGES
than the following: approx. 1% for current, Proportional to 4 – 20mA DC
watt and var; approx. 3% for voltage.
DISPLAY ITEMS RATING INPUT RANGE
Current 5A 0 – 5A
INPUT Voltage 1ø / 2w 1 – 2 105V 0 – 150V
■VOLTAGE INPUT 1ø / 3w 1 – N 105V 0 – 150V
(must be balanced with 3-phase connection) 2 – N 105V 0 – 150V
Operational range 1 – 2 210V 0 – 300V
Voltage, watt, var, zero-phase voltage: 0 – 100% of rat- 3ø / 3w line 110V 0 – 150V
ing 220V 0 – 300V
Power factor: ≥30V 3ø / 4w line 110V 0 – 150V
Frequency: ≥30V phase 110 / √ 3 V 0 – 150 / √ 3 V
Overload capacity: 200% of rating for 60 sec., Watt 110V / 5A 0 – 1 kW (0 – 5 kW)
115% for 3 hours 110V / 5A -1 – +1 kW (-0.5 – +0.5 kW)
220V / 5A 0 – 2 kW
Input burden: 0.3VA/phase
220V / 5A -2 – +2 kW
Var 110V / 5A 0 – lag1 kvar
■CURRENT INPUT
(0 – lag500 var)
(may be unbalanced with 3-phase connection) 110V / 5A lead1 – lag1 kvar
Operational range (lead500 – lag 500 var)
Current, watt, var, demand: 0 – 100% of rating 220V / 5A 0 – lag2 kvar
220V / 5A lead2 – lag2 kvar
Power factor: ≥5% of rating
Overload capacity: 4000% of rating for 1 sec., 2000% Power factor –– lead 50 – 100 – lag 50 %
for 60 sec., 115% for 3 hours Frequency –– 45.0 – 55.0 Hz
Input burden: 0.1VA/phase 55.0 – 65.0 Hz
45.0 – 65.0 Hz
DISPLAY
S.R. A V RESET
PERFORMANCE in percentage of span
Accuracy
Voltage, current: ±1.0%
E F G H J
Watt, var: ±1.5%
A. Display
Power factor: ±3.0%
LED: 10 mm (.39") 7 segment, orange
Frequency: ±0.5%
Display items:
Demand: ±1.5%
NO. OF
Zero-phase voltage: ±1.5% DISPLAY ITEMS DIGITS REMARKS
Max. zero-phase voltage: ±1.5% Current A (1, N, 2) 4 Single-phase / 3-wire
Watthours: ±2.0% (load current 5 – 100%, power factor 1.0) A (R, S, T) 4 3-phase / 3-wire or 4-wire
±2.5% (load current 10 – 100%, power Voltage V (RS, ST, TR) 4 3-phase / 3-wire or 4-wire
factor 0.5, lag current) V (RN, SN, TN) 4 3-phase / 4-wire
Varhours: ±2.5% (load current 10 – 100%, power factor 0) Watt kW 4 – indicator (reverse flow),
±2.5% (load current 20 – 100%, power factor 0.866) ×1, ×10 scaling factor ind. LED
Watthours kWh 5 ×1, ×10, ×100 scaling factor LED
±3.0% (load current 10%, power factor 0.866)
Var kvar 4 – indicator (lead),
Temp. conditioning incl. in the accuray: 23 ±10°C
×1, ×10 scaling factor ind. LED
(73.4 ±18°F) Varhours kvarh 5 ×1, ×10, ×100 scaling factor LED
Freq. conditioning incl. in the accuracy: 45 – 65 Hz Power factor PF 3 – indicator (lead)
Response time: ≤2 sec. (0 – 100% ±1%) Frequency Hz 3
Ripple: 0.5% p-p max. Zero-phase voltage V0 4
Auxiliary supply voltage effect: ±0.1% over voltage Max. zero-phase volt. MV0 4
Demand DA 4 Measuring/displaying
range
preset element only
Power failure protection: VT/CT scaling factors, Max. demand MDA 4
watthours, max. zero-phase voltage and When values exceed the preset values, corresponding LEDs blink.
demand are stored in non-volatile memory.
Insulation resistance: ≥100MΩ with 500V DC B. Multiplication factor: watt, watthours, var or
Dielectric strength: 2000V AC @1 minute varhours on the display (A)
(voltage input to current input to trans- C. Line current indicators: Pressing DISPLAY (J) or
mission section to display switch input to "A" (F) button changes lines (elements).
aux. power to ground terminal) D. Line current indicators: Pressing DISPLAY (J) or
2000V AC @1 minute "V" (G) button changes lines.
(circuit to ground terminal; not applica- E. Primary rating: indicating the primary rating of
ble to analog or transmission terminal) current, voltage, watt or demand
Surge withstand voltage: 1.2/50 µsec., ±4.5kV F. Line current switch
(input to output or ground; not applica- G. Line voltage switch
ble to analog or transmission terminal) H. Reset: resetting the max. zero-phase voltage or
max. demand; same as the external reset
input via output terminals
J. Display: changing display items, turning the light
on or off; same as the Dis. input via
output terminals
P. 3 / 16 ES-6481 Rev.9
51U
EXTERNAL DIMENSIONS mm (inch)
■SINGLE-PHASE / 2-WIRE or 3-WIRE, 3-PHASE / 3-WIRE CONNECTION
35 (1.38)
110 ±1 (4.33 ±.04) 18 73 ±1 (2.87 ±.04) 19 M4 SCREW
(.71) (.75)
8(.31)
8(.31)
6(.24)
M5 SCREW M3 SCREW
35 (1.38)
110 ±1 (4.33 ±.04) 18 73 ±1 (2.87 ±.04) 19 M4 SCREW
(.71) (.75)
8(.31)
8(.31)
6(.24)
16
M5 SCREW (.63) M3 SCREW
10
(3.54 ±0.2)
2
90 ±0.5
+1 0
dia
.
160 (6.30) min.
2– 6 (.24) dia.
SOURCE
K CT L
LOAD
Hz = Frequency 1
k l
2
DA = Demand (current)
MDA = Maximum demand (current)
OUTPUT (selectable display items codes) 1S
V1 1L
0 : None (J K W with reset input) V2
1 : 4 – 20mA DC, 3 points (C D U)
2 : 4 – 20mA DC, 2 points + pulse (E F N P)
3 : 4 – 20mA DC, 2 points + reset input (J) Suffix Codes
C, D, E, F, N, P, W V1 V2 1S 1L
4 : RS-485 (all codes selectable except K W)
J, K (measuring current only) 1S 1L
AUXILIARY POWER SUPPLY U (measuring voltage only) V1 V2
M : 85 – 264V AC
R : 24V DC ■ OUTPUT
P : 110V DC •Without Outputs •4 – 20mA DC, 3 points
Dis. (See the following pages.)
REMOTE CONTROL
1 : 85 – 132V AC or 85 – 143V DC •4 – 20mA DC, 2 points
POWER + pulse 1 point
2 : 20 – 30V DC (See the following pages.)
DISPLAY
3 : 170 – 264V AC •RS-485 SIWTCHING
•4 – 20mA DC, 2 points
+ reset input
Dis. (See the following pages.)
ORDERING INFORMATION
Specify code number. (e.g. 51U-0D4-M1)
Ter + – SL POWER
TERMINATOR DISPLAY
SWITCHING Close across the terminator
RS-485 when the unit is located at
the end of transmission line.
P. 5 / 16 ES-6481 Rev.9
51U
DISPLAY ITEMS & OUTPUTS
Items shown in brackets can be displayed when you change settings.
A A A A
V V V x1 kW
x10 kW
x1 kWh x1 kWh
x1 kW x10 kWh x10 kWh
x10 kW x100 kWh x100 kWh
+ – + – + – + – + – + – + – + – + –
CH1 CH2 Dis. CH1 CH2 CH3 Dis. CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 A CH1 A CH1 A CH1 A
CH2 V CH2 V CH2 V CH2 0 – 0.5 kW
Dis. Display switch. inp. CH3 0 – 0.5 kW PULSE kWh (-0.5 – +0.5 kW)
(-0.5 – +0.5 kW) Dis. Display switch. inp. PULSE kWh
Dis. Display switch. inp. Dis. Display switch. inp.
A DA
A V DA
MDA
DA
A MAX
A x1 kW
x10 kW V
MDA x1 kWh x1 kWh
ALARM
x10 kWh
A SET A x10 kWh
x100 kWh x100 kWh
+ – + – + – + – + – + –
CH1 CH2 RESET Dis. ALARM RESET Dis. CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 A ALARM DA alarm output CH1 V CH1 A
CH2 DA (MDA) RESET MDA ext. reset inp. CH2 0 – 0.5 kW CH2 V
RESET MDA ext. reset inp. Dis. Display switch. inp. (-0.5 – +0.5 kW) CH1/CH2 (DA, MDA)
Dis. Display switch. inp. CH1/CH2 (A) PULSE kWh
PULSE kWh Dis. Display switch. inp.
Dis. Display switch. inp.
Suffix Code: U Suffix Code: W
V A
Hz V
ALARM
SET A
DISPLAY DISPLAY
+ – + –
CH1 CH2 Dis. ALARM RESET Dis.
TERM. ITEMS TERM. ITEMS
CH1 V ALARM DA alarm output
CH2 Hz RESET MDA ext. reset inp.
Dis. Display switch. inp. Dis. Display switch. inp.
SOURCE
Q : A × 3, PF, kW 1
LOAD
k l
N
S : A × 3 or PF, kW, kWh 2
K L
k l
U : V × 3, Hz
W : A × 3 or DA or MDA, V × 3, alarm setpoint 1S
V1 1L
Y : Hz, PF, kWh VN 2S
V2 2L
V = Line voltage A = Line current
kW = Kilowatt kWh = Kilowatthours
PF = Power factor Hz = Frequency Suffix Codes
DA = Demand (current) C, D, E, F, L, M, N, P, Q, S, W, Y V1 VN V2 1S 1L 2S 2L
MDA = Maximum demand (current) A, J, K (measuring current only) 1S 1L 2S 2L
B, U (measuring voltage only) V1 VN V2
OUTPUT (selectable display items codes)
■ OUTPUT
0 : None (J K W with reset input)
1 : 4 – 20mA DC, 3 points (A B C D L Q U) •Without Outputs •4 – 20mA DC, 3 points
Dis. (See the following pages.)
2 : 4 – 20mA DC, 2 points + pulse (E F M N P)
•4 – 20mA DC, 2 points
3 : 4 – 20mA DC, 2 points + reset input (J) + pulse 1 point
POWER
4 : RS-485 (all codes selectable except K W) DISPLAY
(See the following pages.)
AUXILIARY POWER SUPPLY •RS-485 SIWTCHING
•4 – 20mA DC, 2 points
M : 85 – 264V AC + reset input
Dis. (See the following pages.)
R : 24V DC
P : 110V DC
Ter + – SL POWER
REMOTE CONTROL TERMINATOR DISPLAY
1 : 85 – 132V AC or 85 – 143V DC SWITCHING Close across the terminator
RS-485 when the unit is located at
2 : 20 – 30V DC the end of transmission line.
3 : 170 – 264V AC
ORDERING INFORMATION
Specify code number. (e.g. 51U-1D4-M1)
P. 7 / 16 ES-6481 Rev.9
51U
DISPLAY ITEMS & OUTPUTS
Items shown in brackets can be displayed when you change settings.
1 1–N 1 1
A V N
2 A N
2 A
N 2–N 1–N 1–N
A V 2–N
1–2 V 2–N
1–2 V
2 1–2
A V x1 kW
x10 kW
+ – + – + – + – + – + – + – + – + – + – + –
CH1 CH2 CH3 Dis. CH1 CH2 CH3 Dis. CH1 CH2 Dis. CH1 CH2 CH3 Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 A1 CH1 V1N CH1 A1 (AN, A2) CH1 A1 (AN, A2)
CH2 AN CH2 V2N CH2 V1N (V2N, V12) CH2 V1N (V2N, V12)
CH3 A2 CH3 V12 Dis. Display switch. inp. CH3 0 – 1 kW
Dis. Display switch. inp. Dis. Display switch. inp. (-1 – +1 kW)
Dis. Display switch. inp.
1 1 1 1
N
2 A N
2 A N
2 A N
2
DA
A
1–N DA 1
2–N
1–2 V x1 kW
x10 kW
N
2 A MAX
A
x1 kWh x1 kWh MDA
ALARM
x10 kWh x10 kWh
x100 kWh x100 kWh A SET A
+ – + – + – + – + – + –
CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis. CH1 CH2 RESET Dis. ALARM RESET Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 A1 (AN, A2) CH1 A1 (AN, A2) CH1 A1 (AN, A2) ALARM DA alarm output
CH2 V1N (V2N, V12) CH2 0 – 1 kW CH2 DA (MDA) RESET MDA ext. reset inp.
PULSE kWh (-1 – +1 kW) RESET MDA ext. reset inp. Dis. Display switch. inp.
Dis. Display switch. inp. PULSE kWh Dis. Display switch. inp.
Dis. Display switch. inp.
1–N 1 A
Hz % 2–N
1–2 V N
2
DA
MDA
1–N
% x1 kW
x10 kW
x1 kW
x10 kW
2–N
1–2 V
x1 kWh x1 kWh x1 kWh
x1 kW x10 kWh x10 kWh x10 kWh
x10 kW x100 kWh x100 kWh x100 kWh
+ – + – + – + – + – + – + – + – + –
CH1 CH2 CH3 Dis. CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 Hz CH1 PF CH1 V1N (V2N, V12) CH1 A1 (AN, A2)
CH2 PF CH2 0 – 1 kW CH2 0 – 1 kW CH2 V1N (V2N, V12)
CH3 0 – 1 kW (-1 – +1 kW) (-1 – +1 kW) CH1/CH2 (DA, MDA)
(-1 – +1 kW) PULSE kWh CH1/CH2 (A1, AN, A2) PULSE kWh
Dis. Display switch. inp. Dis. Display switch. inp. PULSE kWh Dis. Display switch. inp.
Dis. Display switch. inp.
Specifications subject to change without notice.
P. 8 / 16 ES-6481 Rev.9
Suffix Code: Q Suffix Code: S Suffix Code: U Suffix Code: W
1 1 A 1–N 1 A
N DA
N
2 A N
2
% 2–N
1–2 V 2 MDA
1–N
% x1 kW
x10 kW Hz 2–N
1–2 V
x1 kWh
ALARM
x1 kW
x10 kW
x10 kWh
x100 kWh
SET A
+ – + – + – + – + – + – + –
CH1 CH2 CH3 Dis. CH1 CH2 PULSE Dis. CH1 CH2 Dis. ALARM RESET Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 A1 (AN, A2) CH1 A1 (AN, A2) CH1 V1N (V2N, V12) ALARM DA alarm output
CH2 PF CH2 0 – 1 kW CH2 Hz RESET MDA ext. reset inp.
CH3 0 – 1 kW (-1 – +1 kW) Dis. Display switch. inp. Dis. Display switch. inp.
(-1 – +1 kW) CH1/CH2 (PF)
Dis. Display switch. inp. PULSE kWh
Dis. Display switch. inp.
Suffix Code: Y
Hz
%
x1 kWh
x10 kWh
x100 kWh
DISPLAY
•Output Connection
+ – + –
CH1 CH2 PULSE Dis.
TERM. ITEMS
CH1 Hz
CH2 PF
PULSE kWh
Dis. Display switch. inp.
P. 9 / 16 ES-6481 Rev.9
51U
A : A×3
B :V×3 V1 V2 V3 1S 1L 3S 3L
Input
C : A × 3, V × 3
Output
D : A × 3, V × 3, kW
E : A × 3, V × 3, kWh CH1 CH2 CH3 Dis
F : A × 3, kW, kWh
G : Hz, PF, kvar
H : V × 3, MV0, V0 ■ POWER
DC or AC
J : A × 3, DA, MDA POWER
K : A × 3 or DA, MDA, alarm setpoint
L : Hz, PF, kW
M : PF, kW, kWh P N E
N : V × 3, kW, kWh
P : A × 3 or DA or MDA, V × 3, kWh ■ INPUT
Q : A × 3, PF, kW K CT L
SOURCE
SOURCE
R R
LOAD
LOAD
k l
R : A × 3, PF, kvar S
K L
S
T T
S : A × 3 or PF, kW, kWh k l
U VV U U V W O
T : A × 3, PF, kvarh VT
u vv u
GVT
u v w Oa
1S f
U : V × 3, Hz V1 1L V1
V2 3S V2
W : A × 3 or DA or MDA, V × 3, alarm setpoint V3 3L V3
X : A × 3, kvar, kvarh
Y : Hz, PF, kWh
V = Line voltage A = Line current Suffix Codes
V1 V2 V3 1S 1L 3S 3L V1 V2 V3 G1 G4
kW = Kilowatt kvar = Kilovar
C, D, E, F, G, L, M, N, P, Q, R, S, T, W, X, Y H (measuring max. zero-phase voltage)
PF = Power factor Hz = Frequency 1S 1L 3S 3L 220V AC can be directly connected
kWh = Kilowatthours kvarh = Kilovarhours A, J, K (measuring current only) to V1, V2 and V3 terminals without
DA = Demand (current) V1 V2 V3 VT.
MDA = Maximum demand (current) B, U (measuring voltage only)
V0 = Zero-phase voltage ■ OUTPUT
MV0 = Maximum zero-phase voltage
•Without Outputs •4 – 20mA DC, 3 points
Dis. (See the following pages.)
OUTPUT (selectable display items codes)
0 : None (H J K W with reset input) •4 – 20mA DC, 2 points
POWER + pulse 1 point
1 : 4 – 20mA DC, 3 points (A B C D G L Q R U) (See the following pages.)
DISPLAY
2 : 4 – 20mA DC, 2 points + pulse •RS-485 SIWTCHING
•4 – 20mA DC, 2 points
(E F M N P S T X Y) + reset input
3 : 4 – 20mA DC, 2 points + reset input (H J) Dis. (See the following pages.)
R R–S R R
A V S
T A S
T A
S S–T R–S R–S
A V S–T
T–R V S–T
T–R V
T T–R
A V x1 kW
x10 kW
+ – + – + – + – + – + – + – + – + – + – + –
CH1 CH2 CH3 Dis. CH1 CH2 CH3 Dis. CH1 CH2 Dis. CH1 CH2 CH3 Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 AR CH1 VRS CH1 AR (AS, AT) CH1 AR (AS, AT)
CH2 AS CH2 VST CH2 VRS (VST, VTR) CH2 VRS (VST, VTR)
CH3 AT CH3 VTR Dis. Display switch. inp. CH3 0 – 1 kW
Dis. Display switch. inp. Dis. Display switch. inp. (-1 – +1 kW)
Dis. Display switch. inp.
R R R–S
S
T A S
T A Hz S–T
T–R V
R–S MV0
S–T
T–R V x1 kW
x10 kW % V
x1 kWh x1 kWh V0
x10 kWh
x100 kWh
x10 kWh
x100 kWh
x1 kvar
x10 kvar V
+ – + – + – + – + – + – + – + – + –
CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis. CH1 CH2 CH3 Dis. CH1 CH2 RESET Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 AR (AS, AT) CH1 AR (AS, AT) CH1 Hz CH1 VRS (VST, VTR)
CH2 VRS (VST, VTR) CH2 0 – 1 kW CH2 PF CH2 MV0
PULSE kWh (-1 – +1 kW) CH3 0 – lag1 kvar RESET MV0 ext. reset inp.
Dis. Display switch. inp. PULSE kWh (lead1 – lag1 kvar) Dis. Display switch. inp.
Dis. Display switch. inp. Dis. Display switch. inp.
R R
S
T A S
T
DA
A Hz %
DA R
S
T A MAX
A % x1 kW
x10 kW
MDA x1 kWh
ALARM
x1 kW x10 kWh
A SET A x10 kW x100 kWh
+ – + – + – + – + – + – + –
CH1 CH2 RESET Dis. ALARM RESET Dis. CH1 CH2 CH3 Dis. CH1 CH2 PULSE Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 AR (AS, AT) ALARM DA alarm output CH1 Hz CH1 PF
CH2 DA (MDA) RESET MDA ext. reset inp. CH2 PF CH2 0 – 1 kW
RESET MDA ext. reset inp. Dis. Display switch. inp. CH3 0 – 1 kW (-1 – +1 kW)
Dis. Display switch. inp. (-1 – +1 kW) PULSE kWh
Dis. Display switch. inp. Dis. Display switch. inp.
P. 11 / 16 ES-6481 Rev.9
51U
Suffix Code: N Suffix Code: P Suffix Code: Q Suffix Code: R
R–S R A R R
S–T
T–R V S
T
DA
MDA
S
T A S
T A
R–S
x1 kW
x10 kW
S–T
T–R V % %
x1 kWh x1 kWh
x10 kWh x10 kWh x1 kW x1 kvar
x100 kWh x100 kWh x10 kW x10 kvar
+ – + – + – + – + – + – + – + – + – + –
CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis. CH1 CH2 CH3 Dis. CH1 CH2 CH3 Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 VRS (VST, VTR) CH1 AR (AS, AT) CH1 AR (AS, AT) CH1 AR (AS, AT)
CH2 0 – 1 kW CH2 VRS (VST, VTR) CH2 PF CH2 PF
(-1 – +1 kW) CH1/CH2 (DA, MDA) CH3 0 – 1 kW CH3 0 – lag1 kvar
CH1/CH2 (AR, AS, AT) PULSE kWh (-1 – +1 kW) (lead1 – lag1 kvar)
PULSE kWh Dis. Display switch. inp. Dis. Display switch. inp. Dis. Display switch. inp.
Dis. Display switch. inp.
R A R R–S R
S
T
% S
T A S–T
T–R V S
T A
R–S
x1 kW
x10 kW % Hz S–T
T–R V
x1 kWh x1kvarh
ALARM
x10 kWh
x100 kWh
x10kvarh
x100kvarh
SET A
+ – + – + – + – + – + –
CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis. CH1 CH2 Dis. ALARM RESET Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 AR (AS, AT) CH1 AR (AS, AT) CH1 VRS (VST, VTR) ALARM DA alarm output
CH2 0 – 1 kW CH2 PF CH2 Hz RESET MDA ext. reset inp.
(-1 – +1 kW) PULSE kvarh Dis. Display switch. inp. Dis. Display switch. inp.
CH1/CH2 (PF) Dis. Display switch. inp.
PULSE kWh
Dis. Display switch. inp.
Suffix Code: X Suffix Code: Y
R
S
T A Hz
x1 kvar
x10 kvar %
x1 kvarh x1 kWh
x10 kvarh x10 kWh
x100 kvarh x100 kWh
DISPLAY DISPLAY
+ – + – + – + –
CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis.
TERM. ITEMS TERM. ITEMS
CH1 AR (AS, AT) CH1 Hz
CH2 0 – lag1 kvar CH2 PF
(lead1 – lag1 kvar) PULSE kWh
PULSE kvarh Dis. Display switch. inp.
Dis. Display switch. inp.
D : A × 3, V × 3, kW
E : A × 3, V × 3, kWh
F : A × 3, kW, kWh ■ POWER & INPUT
G : Hz, PF, kvar K CT L
R
SOURCE
k lK L
LOAD
J : A × 3, DA, MDA S
k lK L
T
L : Hz, PF, kW N
k l
V V
M : PF, kW, kWh U U U V 1S
1L
VT 2S
N : V × 3, kW, kWh u vu vu v 2L
3S
P : A × 3 or DA or MDA, V × 3, kWh V1 3L
DC or AC V2
Q : A × 3, PF, kW POWER
V3
VN
R : A × 3, PF, kvar
S : A × 3 or PF, kW, kWh
T : A × 3, PF, kvarh
Suffix Codes
U : V × 3, Hz P N E V1 V2 V3 VN
X : A × 3, kvar, kvarh C, D, E, F, G, L, M, N, P, Q, R, S, T, X, Y
P N E
Y : Hz, PF, kWh A, J (measuring current only)
V = Line voltage A = Line current P N E V1 V2 V3 VN
kW = Kilowatt kvar = Kilovar B, U (measuring voltage only)
PF = Power factor Hz = Frequency
kWh = Kilowatthours kvarh = Kilovarhours
DA = Demand (current)
MDA = Maximum demand (current)
V0 = Zero-phase voltage Suffix Codes
1S 1L 2S 2L 3S 3L
MV0 = Maximum zero-phase voltage
C, D, E, F, G, L, M, N, P, Q, R, S, T, X, Y
OUTPUT (selectable display items codes) 1S 1L 2S 2L 3S 3L
A, J (measuring current only)
0 : None (J with reset input)
1 : 4 – 20mA DC, 3 points (A B C D G L Q R U) B, U (measuring voltage only)
2 : 4 – 20mA DC, 2 points + pulse
■ OUTPUT
(E F M N P S T X Y)
•Without Outputs •4 – 20mA DC, 3 points
3 : 4 – 20mA DC, 2 points + reset input (J) Dis. (See the following pages.)
4 : RS-485
•4 – 20mA DC, 2 points
AUXILIARY POWER SUPPLY POWER + pulse 1 point
M : 85 – 264V AC (See the following pages.)
DISPLAY
•RS-485 SIWTCHING
R : 24V DC •4 – 20mA DC, 2 points
P : 110V DC + reset input
Dis. (See the following pages.)
REMOTE CONTROL
1 : 85 – 132V AC or 85 – 143V DC
Ter + – SL POWER
2 : 20 – 30V DC TERMINATOR DISPLAY
Close across the terminator
3 : 170 – 264V AC SWITCHING
when the unit is located at
RS-485
the end of transmission line.
ORDERING INFORMATION
Specify code number. (e.g. 51U-4D4-M1)
P. 13 / 16 ES-6481 Rev.9
51U
DISPLAY ITEMS & OUTPUTS
Items shown in brackets can be displayed when you change settings.
Suffix Code: A Suffix Code: B Suffix Code: C Suffix Code: D
R R – N(S) PHASE R R
A LINE
V
S
T A S
T A
S S – N(T) PHASE R – N(S) PHASE R – N(S) PHASE
S – N(T) S – N(T)
A LINE
V T – N(R)
LINE
V T – N(R)
LINE
V
T T – N(R) PHASE
LINE
A V
x1 kW
x10 kW
+ – + – + – + – + – + – + – + – + – + – + –
CH1 CH2 CH3 Dis. CH1 CH2 CH3 Dis. CH1 CH2 Dis. CH1 CH2 CH3 Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 AR CH1 VRS CH1 AR (AS, AT) CH1 AR (AS, AT)
CH2 AS CH2 VST CH2 VRS (VST, VTR) CH2 VRS (VST, VTR)
CH3 AT CH3 VTR CH1/CH2 (VRN, VSN, VTN) CH3 0 – 1 kW
Dis. Display switch. inp. CH1/2/3 (VRN, VSN, VTN) Dis. Display switch. inp. (-1 – +1 kW)
Dis. Display switch. inp. CH1/2/3 (VRN, VSN, VTN)
Dis. Display switch. inp.
R R R
S
T A S
T A Hz S
T A
R – N(S) PHASE DA R
S – N(T) x1 kW
T – N(R)
LINE
V x10 kW % S
T A
x1 kWh x1 kWh MDA
x10 kWh x10 kWh x1 kvar
x100 kWh x100 kWh x10 kvar A
+ – + – + – + – + – + – + – + – + –
CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis. CH1 CH2 CH3 Dis. CH1 CH2 RESET Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 AR (AS, AT) CH1 AR (AS, AT) CH1 Hz CH1 AR (AS, AT)
CH2 VRS (VST, VTR) CH2 0 – 1 kW CH2 PF CH2 DA (MDA)
CH1/CH2 (VRN, VSN, VTN) (-1 – +1 kW) CH3 0 – lag1 kvar RESET MDA ext. reset inp.
PULSE kWh PULSE kWh (lead1 – lag1 kvar) Dis. Display switch. inp.
Dis. Display switch. inp. Dis. Display switch. inp. Dis. Display switch. inp.
R – N(S) PHASE R A
Hz % S – N(T)
T – N(R)
LINE
V
S
T
DA
MDA
R – N(S) PHASE
% x1 kW
x10 kW
x1 kW
x10 kW
S – N(T)
T – N(R)
LINE
V
x1 kWh x1 kWh x1 kWh
x1 kW x10 kWh x10 kWh x10 kWh
x10 kW x100 kWh x100 kWh x100 kWh
+ – + – + – + – + – + – + – + – + –
CH1 CH2 CH3 Dis. CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis.
R R R A R
S
T A S
T A S
T
% S
T A
% % x1 kW
x10 kW %
x1 kWh x1kvarh
x1 kW x1 kvar x10 kWh x10kvarh
x10 kW x10 kvar x100 kWh x100kvarh
+ – + – + – + – + – + – + – + – + – + –
CH1 CH2 CH3 Dis. CH1 CH2 CH3 Dis. CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 AR (AS, AT) CH1 AR (AS, AT) CH1 AR (AS, AT) CH1 AR (AS, AT)
CH2 PF CH2 PF CH2 0 – 1 kW CH2 PF
CH3 0 – 1 kW CH3 0 – lag1 kvar (-1 – +1 kW) PULSE kvarh
(-1 – +1 kW) (lead1 – lag1 kvar) CH1/CH2 (PF) Dis. Display switch. inp.
Dis. Display switch. inp. Dis. Display switch. inp. PULSE kWh
Dis. Display switch. inp.
R – N(S) PHASE R
S – N(T) LINE S
A Hz
T – N(R)
V T
Hz x1 kvar
x10 kvar
%
x1 kvarh x1 kWh
x10 kvarh x10 kWh
x100 kvarh x100 kWh
+ – + – + – + – + – + –
CH1 CH2 Dis. CH1 CH2 PULSE Dis. CH1 CH2 PULSE Dis.
TERM. ITEMS TERM. ITEMS TERM. ITEMS
CH1 VRS (VST, VTR) CH1 AR (AS, AT) CH1 Hz
CH2 Hz CH2 0 – lag1 kvar CH2 PF
CH1/CH2 (VRN, VSN, VTN) (lead1 – lag1 kvar) PULSE kWh
Dis. Display switch. inp. PULSE kvarh Dis. Display switch. inp.
Dis. Display switch. inp.
P. 15 / 16 ES-6481 Rev.9
51U
SYSTEM CONFIGURATION EXAMPLE
Nest Bus
32 Units Max.
32 Points Max.
Communication Interface
for 51-UNIT Use
model: SMDU
R
Multi Power Meter R R
model: 51U
S S S
T T T
A A A
R-S R-S R-S
S-T S-T S-T
T-R T-R T-R
V V V