SOLVE THE PROBLEM:


Given:
4 – Storey Hospital Building
Puerto Princesa, Palawan
Reinforced Concrete Building
Structural System: Special Moment-Resisting Frames
Storey Height, h = GF@4.5m + 3@3m = 13.5 m
Building Dimension: 5 m x 12 m
Weight per Floor = 7.3 kPa
Seismic Source Type: A
Distance to nearest fault line: 10 km
Soil Profile Type: SD
TB = 1 sec

Required:
1. All Seismic Considerations;
2. Period (T);
3. Base Shear (V); and
4. Lateral Seismic Force at Every Floor.

General Procedure for Solving Static Force:


1. List of all Seismic Considerations:
a. Occupancy Category
b. Seismic Importance Factor
c. Seismic Zone Factor
d. Seismic Coefficient: Ca and Cv
e. Near Source Factor: Na and Nv
*Seismic Source Type
f. Structural Design
g. Response Modification Factor: R
2. Computation of the Total Weight of Each Floor
3. Computation of Structural Period: T
4. Computation of Base Shear: V
5. Computation of Lateral Seismic Force: Fx

 
1. LIST OF ALL SEISMIC CONSEDIRATIONS:

a. OCCUPANCY CATEGORY

The structure is a 4-storey hospital building.


Therefore, the structure falls under
Occupancy Category I: Essential Facilities.

OCCUPANCY CATEGORY: I

1. LIST OF ALL SEISMIC CONSEDIRATIONS:

b. IMPORTANCE FACTOR

The structure is at Occupancy


Category I. Therefore, its Seismic
Importance Factor (I) is 1.50.

SEISMIC IMPORTANCE FACTOR: I = 1.50


1. LIST OF ALL SEISMIC CONSEDIRATIONS:
1. LIST OF ALL SEISMIC CONSEDIRATIONS:
c. SEISMIC ZONE FACTOR
e. NEAR SOURCE FACTOR: Na and Nv
Puerto Princesa, Palawan is situated at
Zone 2. Therefore, the Seismic Zone
The building’s Seismic Source Type
Factor (Z) is 0.20.
is A. Therefore, Near Source Factor:
Na and Nv are 1.0 and 1.2,
respectively.

Note: Na and Nv are not included in


computation of Ca and Cv because
the building is situated at Seismic
Zone 2.
SEISMIC ZONE FACTOR: Z = 0.20

1. LIST OF ALL SEISMIC CONSEDIRATIONS:


NEAR SOURCE FACTOR: Na = 1.0 & Nv = 1.2

d. SEISMIC COEFFICIENT: Ca and Cv

The hospital’s Soil Profile Type is


SD and it is located at Zone 2.
Therefore, Seismic Coefficient: Ca
and Cv are 0.28 and 0.40,
respectively.

SEISMIC COEFFICIENT: Ca = 0.28 & Cv = 0.40


1. LIST OF ALL SEISMIC CONSEDIRATIONS:

g. RESPONSE MODIFICATION FACTOR: R

The hospital’s structural


system is Special Moment
– Resist Frame (SMRF).
Therefore, the Response
Modification Factor is 8.5.

1. LIST FACTOR:
RESPONSE MODIFICATION OF ALL SEISMIC
R = 8.5 CONSEDIRATIONS:

f. STRUCTURAL DESIGN

The structural design of the


building is a reinforced
concrete building. Therefore,
its Ct is equal to 0.0731.

STRUCTURAL DESIGN: REINFORCED CONCRETE - SMRF


Ct = 0.0731
Height h Level
Weight w w*h Vertical
above at Height
1. COMPUTATION OF THE TOTAL WEIGHT OF EACH FLOOR Distribution
Shear h, kN Factor
Base, m
Given: Roof 13.5 438 5913 0.375
 Building Dimension: 5m x 12 m 4th 10.5 438 4599 0.292
 Weight per Floor: 7.3 kPa 3rd 7.5 438 3285 0.208
 Number of Floor: 4 2nd 4.5 438 1971 0.125
GF 0 0 0 0
(WkPa)(Afloor) = Weach floor sum 1752 15768
2
(7.3 kN/m )(5m)(12m) = 438 kN

(Weach floor)(nfloor) = Wtotal


(438 kN)(4) = 1752 kN

The building’s total weight is equal to 1752 kN with 438 kN at 2nd floor up to the roof.

TOTAL WEIGHT: WTOTAL = 1752 KN

2. COMPUTATION OF STRUCTURAL PERIOD: T


Given:
 Ct = 0.0731
 Height = 13.5m
 TB = 1 sec
3
3/ 4
T A=Ct ( hn ) 4 =0.0731 ( 13.5 ) =0.515 sec
T B=1 sec

But TB should not exceed 1.4TA


1.4 T A=1.4 ( 0.515 )
T =0.721 sec

Note: 1.4TA is used because the value of T shall not exceed


40% in Seismic Zone 2.

STRUCTURAL PERIOD: T = 0.721 sec

3. COMPUTATION OF BASE SHEAR: V


Given:
 Ca = 0.28
 Cv = 0.40
 I = 1.50
 R = 8.5
 T = 0.721 sec
 WTOTAL = 1752 KN

CvI 0.40(1.5)
V= W= 1752=171.526 kN
RT 8.5( 0.721)

2.5 CaI 2.5(0.28)(1.5)


Vmax= W= 1752=216.424 kN
R 8.5

Vmin=0.11CaIW =0.11 ( 0.28 ) ( 1.5 ) 1752=80.942 kN

Since V did not exceed to Vmax and not less than Vmin.
Therefore, base shear V is equal to 171.526 kN.

BASE SHEAR: V = 171.526 KN

4. COMPUTATION OF LATERAL SEISMIC FORCE: Fx


Given:
 V = 171.526 KN
 T = 0.721 sec

Ft =0.07 TV =0.07 (0.721)(171.526)


Ft =8.657 sec

Checking: 0.25 V =0.25 ( 171.526 )=42.882

Since Ft does not exceed to 0.25V, therefore, Ft = 8.657.

For roof
( V −Ft ) Wxhx
Fx= =(V −Ft )( Vertical Dist Factor )
∑ wihi
( 171.526−8.657 ) 5913
Fx= =( 171.526−8.657)(0.375)
15768
Fx=61.076 kN
F roof =Fx+ Ft =61.076+ 8.657
F roof =69.733 kN

For 4th floor


( V −Ft ) Wxhx
Fx= =(V −Ft )( Vertical Dist Factor )
∑ wihi
( 171.526−8.657 ) 4599
Fx= =(171.526−8.657)(0.292)
15768
F 4 th =47.558 kN

For 3rd Floor


( V −Ft ) Wxhx
Fx= =(V −Ft )( Vertical Dist Factor )
∑ wihi
( 171.526−8.657 ) 3285
Fx= =(171.526−8.657)(0.208)
15768
F 3rd =33.877 kN

For 2nd Floor


( V −Ft ) Wxhx
Fx= =(V −Ft )( Vertical Dist Factor )
∑ wihi
( 171.526−8.657 ) 1971
Fx= =(171.526−8.657)(0.125)
15768
F 2nd =20.359 kN

For Ground Floor


( V −Ft ) Wxhx
Fx= =(V −Ft )( Vertical Dist Factor )
∑ wihi
( 171.526−8.657 ) 0
Fx= =(171.526−8.657)( 0)
15768
F GF=0 kN
LATERAL SEISMIC FACTOR: Fx
F roof =69.733 kN
F 4 th =47.558 kN
F 3rd =33.877 kN
F 2nd =20.359 kN
F GF=0 kN

SUMMARY TABLE
1. List of all Seismic Considerations:
a. Occupancy Category Category I: Essential Facilities
b. Seismic Importance Factor I = 1.50
c. Seismic Zone Factor Z = 0.20
d. Seismic Coefficient: Ca and Cv Ca = 0.28
Cv = 0.40
e. Near Source Factor: Na and Nv Na = 1.0
*Seismic Source Type A Nv = 1.2
f. Structural Design Ct = 0.0731
a. Response Modification Factor: R R = 8.5
*Structural Design – Reinforced
Concrete - SMRF
2. Computation of the Total Weight of Each Floor WGF = 0 KN
W2nd = 438 KN
W3rd = 438 KN
W4th = 438 KN
Wroof = 438 KN
WTOTAL = 1752 KN
3. Computation of Structural Period: T T = 0.721 sec
4. Computation of Base Shear: V V = 171.526 KN
5. Computation of Lateral Seismic Force: Fx F roof =69.733 kN
F 4 th =47.558 kN
F 3rd =33.877 kN
F 2nd =20.359 kN
F GF=0 kN