Required:
1. All Seismic Considerations;
2. Period (T);
3. Base Shear (V); and
4. Lateral Seismic Force at Every Floor.
1. LIST OF ALL SEISMIC CONSEDIRATIONS:
a. OCCUPANCY CATEGORY
OCCUPANCY CATEGORY: I
b. IMPORTANCE FACTOR
1. LIST FACTOR:
RESPONSE MODIFICATION OF ALL SEISMIC
R = 8.5 CONSEDIRATIONS:
f. STRUCTURAL DESIGN
The building’s total weight is equal to 1752 kN with 438 kN at 2nd floor up to the roof.
CvI 0.40(1.5)
V= W= 1752=171.526 kN
RT 8.5( 0.721)
Since V did not exceed to Vmax and not less than Vmin.
Therefore, base shear V is equal to 171.526 kN.
For roof
( V −Ft ) Wxhx
Fx= =(V −Ft )( Vertical Dist Factor )
∑ wihi
( 171.526−8.657 ) 5913
Fx= =( 171.526−8.657)(0.375)
15768
Fx=61.076 kN
F roof =Fx+ Ft =61.076+ 8.657
F roof =69.733 kN
SUMMARY TABLE
1. List of all Seismic Considerations:
a. Occupancy Category Category I: Essential Facilities
b. Seismic Importance Factor I = 1.50
c. Seismic Zone Factor Z = 0.20
d. Seismic Coefficient: Ca and Cv Ca = 0.28
Cv = 0.40
e. Near Source Factor: Na and Nv Na = 1.0
*Seismic Source Type A Nv = 1.2
f. Structural Design Ct = 0.0731
a. Response Modification Factor: R R = 8.5
*Structural Design – Reinforced
Concrete - SMRF
2. Computation of the Total Weight of Each Floor WGF = 0 KN
W2nd = 438 KN
W3rd = 438 KN
W4th = 438 KN
Wroof = 438 KN
WTOTAL = 1752 KN
3. Computation of Structural Period: T T = 0.721 sec
4. Computation of Base Shear: V V = 171.526 KN
5. Computation of Lateral Seismic Force: Fx F roof =69.733 kN
F 4 th =47.558 kN
F 3rd =33.877 kN
F 2nd =20.359 kN
F GF=0 kN